06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

open, then the gas bypass modulating valve must remain<br />

at least 20% open. The effect of closing the condenser<br />

valve will be to increase the supply air temperature<br />

(additional reheat capacity). To view the actual valve<br />

position at any time, the user can use the Outputs menu<br />

(OutputsCOOLC.EXV).<br />

• <strong>Service</strong> TestCOOLB.EXV (HMV-2: Bypass EXV<br />

Position). On Humidi-MiZer equipped units, this item<br />

allows the user to exercise the valve that controls discharge<br />

gas bypass around the Circuit B condenser. To<br />

exercise the valve, RHV must first be switched to ON<br />

(<strong>Service</strong> TestCOOLRHV) <strong>and</strong> a Circuit B compressor<br />

must be comm<strong>and</strong>ed ON. The valve default position<br />

is 0% (completely closed). The user will be able to adjust<br />

the valve from 0 to 100% through this function. The only<br />

constraint on the valve position is that the percentage<br />

sum of the bypass valve <strong>and</strong> condenser valve (<strong>Service</strong><br />

TestCOOLC.EXV) must equal 100%. For example,<br />

if the condenser modulating valve is only 80% open,<br />

then the gas bypass modulating valve must remain at<br />

least 20% open. The effect of opening the bypass valve<br />

will be to increase the supply air temperature (additional<br />

reheat capacity). To view the actual valve position at any<br />

time, the user can use the Outputs menu (Outputs<br />

COOLB.EXV).<br />

Heating — The Heat Test Mode sub-menu will offer automatic<br />

fan start-up if not a gas fired heat unit. On gas heat units,<br />

the IGC feedback from the gas control units will bring the fan<br />

on as required.<br />

Within this sub-menu, control of the following is possible:<br />

• <strong>Service</strong> TestHEATHT.ST (Requested Heat Stage).<br />

When this item is non-zero, the currently configured heat<br />

type will energize the corresponding heat relay pattern<br />

that reflects the requested stage. In addition the upper<br />

limit will be clamped to reflect the maximum configured<br />

number of stages. When non-zero, the heat relays will be<br />

“read-only” <strong>and</strong> reflect the currently selected pattern.<br />

• <strong>Service</strong> TestHEATHT.1-6, <strong>Service</strong> TestHEAT<br />

H.I.R (Manual Heat Relay Control). If the “Heat Stage<br />

Request” item is set to zero, it will be possible to individually<br />

control the heat relays, including the heat interlock<br />

relay.<br />

• <strong>Service</strong> TestHEATHTC.C (Ht Coil Comm<strong>and</strong> Position).<br />

If configured for hydronic heat type, the user will<br />

be able to manually control the positioning of the actuator<br />

which controls hot water (0 to 100%).<br />

THIRD PARTY CONTROL<br />

Thermostat — The method of control would be through<br />

the thermostat inputs:<br />

Y1 = first stage cooling<br />

Y1 <strong>and</strong> Y2 = first <strong>and</strong> second stage cooling<br />

W1 = first stage heating<br />

W1 <strong>and</strong> W2 = first <strong>and</strong> second stage heating<br />

G = supply fan<br />

Alarm Output — The alarm output is 24-v at TB201-12<br />

<strong>and</strong> TB201-11. The contact will provide relay closure whenever<br />

the unit is under an alert or alarm condition (5 va maximum).<br />

Remote Switch — The remote switch may be configured<br />

for three different functions. Under ConfigurationUNIT, set<br />

RM.CF to one of the following:<br />

0 = no remote switch<br />

1 = occupied/unoccupied switch<br />

2 = start/stop switch<br />

3 = occupancy override switch<br />

Under ConfigurationSW.LG, RMI.L, the remote occupancy<br />

switch can be set to either a normally open or normally<br />

38<br />

closed switch input. Normal is defined as either unoccupied,<br />

start or “not currently overridden,” respective to the RM.CF<br />

configuration.<br />

With RM.CF set to 1, no time schedules are followed <strong>and</strong><br />

the unit follows the remote switch only in determining the state<br />

of occupancy.<br />

With RM.CF set to 2, the remote switch can be used to shut<br />

down <strong>and</strong> disable the unit, while still honoring timeguards on<br />

compressors. Time schedules, internal or external, may be run<br />

simultaneously with this configuration.<br />

With RM.CF set to 3, the remote input may override an<br />

unoccupied state <strong>and</strong> force the control to go occupied mode. As<br />

with the start/stop configuration, an internal or external time<br />

schedule may continue to control occupancy when the switch<br />

is not in effect.<br />

VFD Control — On VFD equipped supply fans, supply<br />

duct static pressure control may be left under unit control or be<br />

externally controlled. To control a VFD externally with a 4 to<br />

20 mA signal, set SP.RS to 4, under the ConfigurationSP<br />

menu. This will set the reset to VFD control. When SP.RS = 4,<br />

the static pressure reset function acts to provide direct VFD<br />

speed control where 4 mA = 0% speed <strong>and</strong> 20 mA = 100%<br />

(SP.MN <strong>and</strong> SP.MX will override). Note that SP.CF must be<br />

set to 1 (VFD Control) prior to configuring SP.RS = 4. Failure<br />

to do so could result in damage to ductwork due to overpressurization.<br />

In effect, this represents a speed control signal “pass<br />

through” under normal operating circumstances. The ComfortLink<br />

controller overrides the third party signal for critical<br />

operation situations, most notably smoke <strong>and</strong> fire control.<br />

Wire the input to the controls expansion module (CEM) using<br />

TB202-6 <strong>and</strong> TB202-7. An optional CEM board is required.<br />

See Appendix D <strong>and</strong> the VFD literature supplied with the<br />

unit for VFD configurations <strong>and</strong> field wiring connections to the<br />

VFD.<br />

Supply Air Reset — With the installation of the control<br />

expansion module (CEM), the ComfortLink controls are capable<br />

of accepting a 4 to 20 mA signal, to reset the supply-air<br />

temperature up to a maximum of 20 F.<br />

Under ConfigurationEDT.R set RS.CF to 3 (external 4<br />

to 20 mA supply air reset control). The 4 to 20 mA input to the<br />

control system (TB202-9 <strong>and</strong> TB202-8), will be linearized <strong>and</strong><br />

range from 0º to 20 F. For example, 4 mA = 0º F reset, 12 mA<br />

= 10º F reset <strong>and</strong> 20 mA = 20º F reset.<br />

Dem<strong>and</strong> Limit Control — The term dem<strong>and</strong> limit control<br />

refers to the restriction of the machine’s mechanical cooling<br />

capacity to control the amount of power that a machine<br />

may use.<br />

Dem<strong>and</strong> limiting is possible via two means:<br />

Two discrete inputs tied to dem<strong>and</strong> limit set point percentages.<br />

OR<br />

A 4 to 20 mA input that can reduce or limit capacity linearly to<br />

a set point percentage.<br />

In either case, it will be necessary to install a controls expansion<br />

module (CEM). The control interfaces to a switch input at<br />

TB202-10 <strong>and</strong> TB202-11.<br />

DEMAND LIMIT DISCRETE INPUTS — First, set DM.L.S<br />

in ConfigurationDMD.L to 1 (2 switches).<br />

When InputsGEN.IDL.S1 (Dem<strong>and</strong> Switch no. 1) is<br />

OFF, the control will not set any limit to the capacity, <strong>and</strong><br />

when ON, the control sets a capacity limit to the ConfigurationDMD.LD.L.S1<br />

set point.<br />

Likewise, when InputsGEN.IDL.S2 (Dem<strong>and</strong> Switch<br />

no. 2) is OFF, the control will not set any limit to the capacity,

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!