06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Recommended Cooling Time<br />

(Minutes)<br />

Fig. 91 — Advanced Scroll Temperature<br />

Protection Label<br />

120<br />

110<br />

100<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

0<br />

0 10 20 30 40 50 60 70 80 90<br />

Compressor Unloaded Run Time (Minutes)<br />

*Times are approximate.<br />

NOTE: Various factors, including high humidity, high ambient temperature,<br />

<strong>and</strong> the presence of a sound blanket will increase cooldown<br />

times.<br />

Fig. 92 — Recommended Minimum Cool-Down<br />

Time After Compressor is Stopped*<br />

Crankcase Heater — Each compressor has a crankcase heater<br />

to prevent absorption of liquid refrigerant by oil in the crankcase<br />

when the compressor is idle. Since 115-v power for the<br />

crankcase heaters is drawn from the unit control circuit, main<br />

unit power must be on for the heaters to be energized.<br />

IMPORTANT: After a prolonged shutdown or service<br />

job, energize the crankcase heaters for 24 hours before<br />

starting the compressor.<br />

EVAPORATOR-FAN MOTOR PROTECTION — A manual<br />

reset, calibrated trip, magnetic circuit breaker protects<br />

against overcurrent. Do not bypass connections or increase the<br />

size of the breaker to correct trouble. Determine the cause <strong>and</strong><br />

correct it before resetting the breaker.<br />

CONDENSER-FAN MOTOR PROTECTION — Each<br />

condenser-fan motor is internally protected against overtemperature.<br />

They are also protected against a severe overcurrent<br />

condition by manual reset, calibrated trip, magnetic circuit<br />

breakers on a common circuit. As with the circuit breakers,<br />

do not bypass connections or increase breaker size to correct<br />

trouble. Determine the cause <strong>and</strong> correct it before resetting the<br />

breaker.<br />

HIGH-PRESSURE SWITCHES — Settings for these switches<br />

are shown in Tables 104A <strong>and</strong> 104B. If either switch trips,<br />

that refrigerant circuit will be automatically locked out by the<br />

controls. To reset, recycle control power to unit.<br />

Table 104A — Pressure Switch Settings (psig)<br />

SWITCH CUTOUT CUT-IN<br />

High 650 10 500 15<br />

164<br />

Table 104B — Pressure Switch Settings (kPa)<br />

SWITCH CUTOUT CUT-IN<br />

High 4482 69 3447 103<br />

Relief Devices — All units have relief devices to protect<br />

against damage from excessive pressures (i.e., fire). These devices<br />

protect the high <strong>and</strong> low side.<br />

Control Circuit, 115 V — This control circuit is protected<br />

against overcurrent by a 10-amp circuit breaker. Breaker can<br />

be reset. If it trips, determine cause of trouble before resetting.<br />

Control Circuit, 24 V — This control circuit is protected<br />

against overcurrent by two 10-amp <strong>and</strong> four 3.2-amp circuit<br />

breakers. Breakers can be reset. If a breaker trips, determine<br />

cause of trouble before resetting.<br />

Gas Heat (48P Only)<br />

LIMIT SWITCHES — The maximum supply-air temperature<br />

is controlled by a limit switch located in the gas section. The<br />

limit is designed to trip at 100 F above the maximum temperature<br />

rise.<br />

When the limit trips, 2 flashes occur on the IGC board. The<br />

gas valve is deenergized. After cooling, the system will reset<br />

<strong>and</strong> fires gas again. If four trips occur, the system shuts down<br />

into Lockout <strong>and</strong> 4 flashes occur on the IGC board. The system<br />

must then be manually reset by power down <strong>and</strong> power up of<br />

the unit.<br />

LIMIT SWITCH THERMISTOR (Staged Gas Unit<br />

Only) — The limit switch thermistor is a factory-installed<br />

component. It is located next to the lower limit switch. The<br />

limit switch thermistor senses temperature at limit switch location<br />

<strong>and</strong> prevents the limit from tripping while the unit is operating<br />

at low airflow.<br />

ROLLOUT SWITCH — This switch senses any flame or excessive<br />

heat in the main burner compartment <strong>and</strong> deenergizes<br />

the gas valve. If this occurs, the gas heating system is locked<br />

out (7 flashes on IGC board) until the rollout switch is reset<br />

manually. Reset rollout switch manually by powering down<br />

<strong>and</strong> powering up of the unit.<br />

When the rollout switch trips, it usually indicates a flue<br />

blockage. Inspect the unit for any obstruction in the flue system,<br />

for holes in the flue box, a defective hall effect sensor, a<br />

defective inducer motor, or a loose combustion blower.<br />

Compressor Removal — All compressors can be removed<br />

from the compressor side of the unit.<br />

IMPORTANT: All compressor mounting hardware <strong>and</strong><br />

support brackets removed during servicing must be reinstalled<br />

prior to start-up.<br />

1. Disconnect power to unit; lockout power to compressor.<br />

2. Close suction <strong>and</strong> discharge service valves.<br />

3. Relieve refrigerant pressure into a refrigerant recovery<br />

system.<br />

4. Disconnect power wires at terminal box <strong>and</strong> disconnect<br />

conduit.<br />

5. Disconnect wires from crankcase heater.<br />

6. Lift compressor off mounting bolts <strong>and</strong> remove.<br />

Compressor Replacement — Perform the following:<br />

1. Reverse procedure in Compressor Removal section.<br />

2. Leak-check <strong>and</strong> evacuate system, recover refrigerant.<br />

3. Recharge system per pre-start-up <strong>and</strong> start-up sequences.<br />

Recheck oil levels.<br />

4. Energize crankcase heater for 24 hours prior to restart of<br />

system.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!