Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Recommended Cooling Time<br />
(Minutes)<br />
Fig. 91 — Advanced Scroll Temperature<br />
Protection Label<br />
120<br />
110<br />
100<br />
90<br />
80<br />
70<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
0<br />
0 10 20 30 40 50 60 70 80 90<br />
Compressor Unloaded Run Time (Minutes)<br />
*Times are approximate.<br />
NOTE: Various factors, including high humidity, high ambient temperature,<br />
<strong>and</strong> the presence of a sound blanket will increase cooldown<br />
times.<br />
Fig. 92 — Recommended Minimum Cool-Down<br />
Time After Compressor is Stopped*<br />
Crankcase Heater — Each compressor has a crankcase heater<br />
to prevent absorption of liquid refrigerant by oil in the crankcase<br />
when the compressor is idle. Since 115-v power for the<br />
crankcase heaters is drawn from the unit control circuit, main<br />
unit power must be on for the heaters to be energized.<br />
IMPORTANT: After a prolonged shutdown or service<br />
job, energize the crankcase heaters for 24 hours before<br />
starting the compressor.<br />
EVAPORATOR-FAN MOTOR PROTECTION — A manual<br />
reset, calibrated trip, magnetic circuit breaker protects<br />
against overcurrent. Do not bypass connections or increase the<br />
size of the breaker to correct trouble. Determine the cause <strong>and</strong><br />
correct it before resetting the breaker.<br />
CONDENSER-FAN MOTOR PROTECTION — Each<br />
condenser-fan motor is internally protected against overtemperature.<br />
They are also protected against a severe overcurrent<br />
condition by manual reset, calibrated trip, magnetic circuit<br />
breakers on a common circuit. As with the circuit breakers,<br />
do not bypass connections or increase breaker size to correct<br />
trouble. Determine the cause <strong>and</strong> correct it before resetting the<br />
breaker.<br />
HIGH-PRESSURE SWITCHES — Settings for these switches<br />
are shown in Tables 104A <strong>and</strong> 104B. If either switch trips,<br />
that refrigerant circuit will be automatically locked out by the<br />
controls. To reset, recycle control power to unit.<br />
Table 104A — Pressure Switch Settings (psig)<br />
SWITCH CUTOUT CUT-IN<br />
High 650 10 500 15<br />
164<br />
Table 104B — Pressure Switch Settings (kPa)<br />
SWITCH CUTOUT CUT-IN<br />
High 4482 69 3447 103<br />
Relief Devices — All units have relief devices to protect<br />
against damage from excessive pressures (i.e., fire). These devices<br />
protect the high <strong>and</strong> low side.<br />
Control Circuit, 115 V — This control circuit is protected<br />
against overcurrent by a 10-amp circuit breaker. Breaker can<br />
be reset. If it trips, determine cause of trouble before resetting.<br />
Control Circuit, 24 V — This control circuit is protected<br />
against overcurrent by two 10-amp <strong>and</strong> four 3.2-amp circuit<br />
breakers. Breakers can be reset. If a breaker trips, determine<br />
cause of trouble before resetting.<br />
Gas Heat (48P Only)<br />
LIMIT SWITCHES — The maximum supply-air temperature<br />
is controlled by a limit switch located in the gas section. The<br />
limit is designed to trip at 100 F above the maximum temperature<br />
rise.<br />
When the limit trips, 2 flashes occur on the IGC board. The<br />
gas valve is deenergized. After cooling, the system will reset<br />
<strong>and</strong> fires gas again. If four trips occur, the system shuts down<br />
into Lockout <strong>and</strong> 4 flashes occur on the IGC board. The system<br />
must then be manually reset by power down <strong>and</strong> power up of<br />
the unit.<br />
LIMIT SWITCH THERMISTOR (Staged Gas Unit<br />
Only) — The limit switch thermistor is a factory-installed<br />
component. It is located next to the lower limit switch. The<br />
limit switch thermistor senses temperature at limit switch location<br />
<strong>and</strong> prevents the limit from tripping while the unit is operating<br />
at low airflow.<br />
ROLLOUT SWITCH — This switch senses any flame or excessive<br />
heat in the main burner compartment <strong>and</strong> deenergizes<br />
the gas valve. If this occurs, the gas heating system is locked<br />
out (7 flashes on IGC board) until the rollout switch is reset<br />
manually. Reset rollout switch manually by powering down<br />
<strong>and</strong> powering up of the unit.<br />
When the rollout switch trips, it usually indicates a flue<br />
blockage. Inspect the unit for any obstruction in the flue system,<br />
for holes in the flue box, a defective hall effect sensor, a<br />
defective inducer motor, or a loose combustion blower.<br />
Compressor Removal — All compressors can be removed<br />
from the compressor side of the unit.<br />
IMPORTANT: All compressor mounting hardware <strong>and</strong><br />
support brackets removed during servicing must be reinstalled<br />
prior to start-up.<br />
1. Disconnect power to unit; lockout power to compressor.<br />
2. Close suction <strong>and</strong> discharge service valves.<br />
3. Relieve refrigerant pressure into a refrigerant recovery<br />
system.<br />
4. Disconnect power wires at terminal box <strong>and</strong> disconnect<br />
conduit.<br />
5. Disconnect wires from crankcase heater.<br />
6. Lift compressor off mounting bolts <strong>and</strong> remove.<br />
Compressor Replacement — Perform the following:<br />
1. Reverse procedure in Compressor Removal section.<br />
2. Leak-check <strong>and</strong> evacuate system, recover refrigerant.<br />
3. Recharge system per pre-start-up <strong>and</strong> start-up sequences.<br />
Recheck oil levels.<br />
4. Energize crankcase heater for 24 hours prior to restart of<br />
system.