APPENDIX A — LOCAL DISPLAY TABLES (cont)<br />
MODE — TEMPERATURES<br />
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />
AIR.T AIR TEMPERATURES<br />
CTRL CONTROL TEMPS<br />
CTRLEDT Evaporator Discharge Tmp dF EDT<br />
CTRLLAT Leaving Air Temperature dF LAT<br />
CTRLMAT Mixed Air Temperature dF MAT<br />
CTRLR.TMP Controlling Return Temp dF RETURN_T forcible<br />
CTRLS.TMP Controlling Space Temp dF SPACE_T forcible<br />
SAT Air Tmp Lvg Supply Fan dF SAT<br />
OAT Outside Air Temperature -40 - 240 dF OAT forcible<br />
RAT Return Air Temperature dF RAT forcible<br />
SPT Space Temperature -40 - 240 dF SPT forcible<br />
SPTO Space Temperature Offset ^F SPTO forcible<br />
CCT Air Temp Lvg Evap Coil dF CCT<br />
S.G.LS Staged Gas LAT Sum dF LAT_SGAS<br />
S.G.L1 Staged Gas LAT 1 dF LAT1SGAS<br />
S.G.L2 Staged Gas LAT 2 dF LAT2SGAS<br />
S.G.L3 Staged Gas LAT 3 dF LAT3SGAS<br />
S.G.LM Staged Gas Limit Sw.Temp dF LIMSWTMP<br />
REF.T REFRIGERANT TEMPERATURES<br />
SCT.A Cir A Sat.Condensing Tmp dF SCTA<br />
SST.A Cir A Sat.Suction Temp. dF SSTA<br />
SCT.B Cir B Sat.Condensing Tmp dF SCTB<br />
SST.B Cir B Sat.Suction Temp. dF SSTB<br />
RGT.A Suction Gas Temp Circ A dF RGTA<br />
DT.A1 A1 Discharge Temperature dF DTA1<br />
MODE — PRESSURES<br />
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />
AIR.P AIR PRESSURES<br />
SP Static Pressure "H2O SP<br />
BP Building Pressure "H2O BP<br />
REF.P REFRIGERANT PRESSURES<br />
DP.A Cir A Discharge Pressure PSIG DP_A<br />
SP.A Cir A Suction Pressure PSIG SP_A<br />
DP.B Cir B Discharge Pressure PSIG DP_B<br />
SP.B Cit B Suction Pressure PSIG SP_B<br />
MODE — SETPOINTS<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
OHSP Occupied Heat Setpoint 40-99 dF OHSP 68<br />
OCSP Occupied Cool Setpoint 40-99 dF OCSP 75<br />
UHSP Unoccupied Heat Setpoint 40-99 dF UHSP 55<br />
UCSP Unoccupied Cool Setpoint 40-110 dF UCSP 90<br />
GAP Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5<br />
V.C.ON VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5<br />
V.C.OF VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2<br />
SASP Supply Air Setpoint 45-75 dF SASP 55<br />
SA.HI Supply Air Setpoint Hi 45-75 dF SASP_HI 55<br />
SA.LO Supply Air Setpoint Lo 45-75 dF SASP_LO 60<br />
SA.HT Heating Supply Air Setpt 80-120 dF SASPHEAT 85<br />
T.PRG Tempering Purge SASP -20-80 dF TEMPPURG 50<br />
T.CL Tempering in Cool SASP 5-75 dF TEMPCOOL 5<br />
T.V.OC Tempering Vent Occ SASP -20-80 dF TEMPVOCC 65<br />
T.V.UN Tempering Vent Unocc. SASP -20-80 dF TEMPVUNC 50<br />
168