APPENDIX B — CCN TABLES (cont)<br />

SERVICE-CONFIG TABLES (cont)<br />

TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT<br />

IAQ_<br />

Economizer Min.Position 0 - 100 % ECONOMIN 5<br />

IAQ Dem<strong>and</strong> Vent Min.Pos. 0 - 100 % IAQMINP 0<br />

Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000<br />

IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM OACFMMIN 0<br />

Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM OACFM_DB 400<br />

IAQ Analog Sensor Config 0 - 4 IAQANCFG 0<br />

IAQ 4-20 ma Fan Config 0 - 2 IAQANFAN 0<br />

IAQ Discrete Input Config 0 - 2 IAQINCFG 0<br />

IAQ Disc.In. Fan Config 0 - 2 IAQINFAN 0<br />

OAQ 4-20ma Sensor Config 0 - 2 OAQANCFG 0<br />

IAQ Econo Override Pos. 0 - 100 % IAQOVPOS 100<br />

IAQ Override flow 0 - 31000 CFM IAQOVCFM 10000<br />

Diff.Air Quality LoLimit 0 - 1000 DAQ_LOW 100<br />

Diff. Air Quality HiLimit 100 - 2000 DAQ_HIGH 700<br />

DAQ PPM Fan Off Setpoint 0 - 2000 DAQFNOFF 200<br />

DAQ PPM Fan On Setpoint 0 - 2000 DAQFNON 400<br />

Diff. AQ Responsiveness -5 - 5 IAQREACT 0<br />

OAQ Lockout Value 0 - 2000 OAQLOCK 0<br />

User determined OAQ 0 - 5000 OAQ_USER 400<br />

IAQ Low Reference 0 - 5000 IAQREFL 0<br />

IAQ High Reference 0 - 5000 IAQREFH 2000<br />

OAQ Low Reference 0 - 5000 OAQREFL 0<br />

OAQ High Reference 0 - 5000 OAQREFH 2000<br />

IAQ Purge Yes/No IAQPURGE No<br />

IAQ Purge Duration 5-60 min IAQPTIME 15<br />

IAQ Purge LoTemp Min Pos 0-100 % IAQPLTMP 10<br />

IAQ Purge HiTemp Min Pos 0-100 % IAQPHTMP 35<br />

IAQ Purge OAT Lockout 35-70 dF IAQPNTLO 50<br />

SP__<br />

Static Pressure Control Enable/Disable STATICFG Disable<br />

Static Pressure Sensor Enable/Disable SPSENS Disable<br />

Static Press. Low Range -10 - 0 SP_LOW 0<br />

Static Press. High Range 0 - 10 SP_HIGH 5<br />

Static Pressure Setpoint 0 - 5 "H2O SPSP 1.5<br />

VFD Minimum Speed 0 - 100 % STATPMIN 10<br />

VFD Maximum Speed 0 - 100 % STATPMAX 100<br />

VFD Fire Speed Over. 0 - 100 % STATPFSO 100<br />

Stat. Pres. Reset Config 0 - 4 (multi-text strings) SPRSTCFG 0<br />

SP Reset Ratio 0.00 - 2.00 SPRRATIO 0.20<br />

SP Reset Limit 0.00 - 2.00 SPRLIMIT 0.75<br />

SP Reset Econo. Position 0 - 100 % ECONOSPR 5<br />

Stat.Pres.PID Run Rate 5 - 120 sec SPIDRATE 15<br />

Static Press. Prop. Gain 0 - 5 STATP_PG 0.5<br />

Static Press. Intg. Gain 0 - 2 STATP_IG 0.5<br />

Static Press. Derv. Gain 0 - 5 STATP_DG 0.3<br />

SWLG<br />

Filter Status Inpt-Clean Open/Close FLTSLOGC Open<br />

IGC Feedback - Off Open/Close GASFANLG Open<br />

RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open<br />

Enthalpy Input - Low Open/Close ENTHLOGC Close<br />

Fan Status Sw. - Off Open/Close SFSLOGIC Open<br />

Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open<br />

Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open<br />

IAQ Disc.Input - Low Open/Close IAQINLOG Open<br />

Fire Shutdown - Off Open/Close FSDLOGIC Open<br />

Press. Switch - Off Open/Close PRESLOGC Open<br />

Evacuation Sw. - Off Open/Close EVACLOGC Open<br />

Smoke Purge Sw. - Off Open/Close PURGLOGC Open<br />

Dehumidify Sw. - Off Open/Close DHDISCLG Open<br />

TRIM<br />

Air Temp Lvg SF Trim -10 - 10 ^F SAT_TRIM 0<br />

RAT Trim -10 - 10 ^F RAT_TRIM 0<br />

OAT Trim -10 - 10 ^F OAT_TRIM 0<br />

SPT Trim -10 - 10 ^F SPT_TRIM 0<br />

Limit Switch Trim -10 - 10 ^F LSW_TRIM 0<br />

Air Temp Lvg Evap Trim -10 - 10 ^F CCT_TRIM 0<br />

A1 Discharge Temp Trim -10 - 10 ^F DTA1TRIM<br />

Suction Gas Temp A Trim -10 - 10 ^F RGTATRIM<br />

Suct.Press.Circ.A Trim -50 - 50 SPA_TRIM 0<br />

Suct.Press.Circ.B Trim -50 - 50 SPB_TRIM 0<br />

Dis.Press.Circ.A Trim -50 - 50 DPA_TRIM 0<br />

Dis.Press.Circ.B Trim -50 - 50 DPB_TRIM 0<br />

Static Press. Trim (ma) -2 - 2 SPMATRIM 0<br />

Bldg. Pressure Trim (ma) -2 - 2 BPMATRIM 0<br />

Outside Air CFM Trim (ma) -2 - 2 OAMATRIM 0<br />

Supply Air CFM Trim (ma) -2 - 2 SAMATRIM 0<br />

Return Air CFM (ma) -2 - 2 RAMATRIM 0<br />

184