APPENDIX A — LOCAL DISPLAY TABLES (cont)<br />
MODE — OUTPUTS<br />
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />
FANS FANS<br />
S.FAN Supply Fan Relay ON/OFF SFAN<br />
S.VFD Supply Fan VFD Speed 0-100 % SFAN_VFD<br />
E.VFD Exhaust Fan VFD Speed 0-100 % EFAN_VFD<br />
P.E.1 Power Exhaust Relay 1 ON/OFF PE1<br />
P.E.2 Power Exhaust Relay 2 ON/OFF PE2<br />
CDF.1 Condenser Fan Output 1 ON/OFF CONDFAN1<br />
CDF.2 Condenser Fan Output 2 ON/OFF CONDFAN2<br />
CDF.3 Condenser Fan Output 3 ON/OFF CONDFAN3<br />
CDF.4 Condenser Fan Output 4 ON/OFF CONDFAN4<br />
COOL COOLING<br />
A1 Compressor A1 Relay ON/OFF CMPA1<br />
A2 Compressor A2 Relay ON/OFF CMPA2<br />
A3 Compressor A3 Relay ON/OFF CMPA3<br />
B1 Compressor B1 Relay ON/OFF CMPB1<br />
B2 Compressor B2Relay ON/OFF CMPB2<br />
B3 Compressor B3 Relay ON/OFF CMPB3<br />
A1.CP Compressor A1 Capacity 0-100 % CMPA1CAP<br />
MLV Minimum Load Valve Relay ON/OFF MLV<br />
RHV Humidimizer 3-Way Valve ON/OFF HUM3WVAL<br />
C.EXV Condenser EXV Position 0-100 % COND_EXV<br />
B.EXV Bypass EXV Position 0-100 % BYP_EXV<br />
HEAT HEATING<br />
HT.1 Heat Relay 1 ON/OFF HS1<br />
HT.2 Heat Relay 2 ON/OFF HS2<br />
HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3<br />
HT.4 Relay 4 W2 Gas Valve 2 ON/OFF HS4<br />
HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5<br />
HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6<br />
H.I.R Heat Interlock Relay ON/OFF HIR forcible<br />
HTC.P Ht.Coil Act.Current Pos. 0-100 % HTCLRPOS<br />
ACTU ACTUATORS<br />
ECN.P Economizer Act.Curr.Pos. 0-100 % ECONRPOS<br />
EC2.P Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS<br />
ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible<br />
BP1.P BP 1 Actuator Curr.Pos. 0-100 % BP1_RPOS<br />
BP1.C BP 1 Comm<strong>and</strong> Position 0-100 % BP1_CPOS<br />
BP2.P BP 2 Actuator Curr.Pos. 0-100 % BP2_RPOS<br />
BP2.C BP 2 Comm<strong>and</strong> Position 0-100 % BP2_CPOS<br />
HTC.P Ht.Coil Act.Current Pos. 0-100 % HTCLRPOS<br />
HTC.C Ht.Coil Comm<strong>and</strong> Position 0-100 % HTCLCPOS<br />
HMD.P Humidifier Act.Curr.Pos. 0-100 % HUMDRPOS<br />
HMD.C Humidifier Comm<strong>and</strong> Pos. 0-100 % HUMDCPOS<br />
GEN.O GENERAL OUTPUTS<br />
HUM.R Humidifier Relay ON/OFF HUMIDRLY<br />
ALRM Remote Alarm / Aux Relay ON/OFF ALRM forcible<br />
170