SETTING UP THE SYSTEM — The IAQ configuration options<br />
are under the Local Display Mode ConfigurationIAQ.<br />
See Table 57.<br />
IAQ Analog Sensor Config (ConfigurationIAQ<br />
AQ.CFIQ.A.C) — This is used to configure the type of<br />
IAQ position control. It has the following options:<br />
• IQ.A.C = 0 (No analog input). If there is no other minimum<br />
position control, the economizer minimum position<br />
will be ConfigurationIAQEC.MN <strong>and</strong> there will be<br />
no IAQ control.<br />
• IQ.A.C = 1 (IAQ analog input). An indoor air (space or<br />
return air) CO 2 sensor is installed. If an outdoor air CO 2<br />
sensor is also installed, or OAQ is broadcast on the CCN,<br />
or if a default OAQ value is used, then the unit can perform<br />
IAQ control.<br />
• IQ.A.C = 2 (IAQ analog input with minimum position<br />
override) — If the differential between IAQ <strong>and</strong> OAQ<br />
is above ConfigurationIAQAQ.SPDAQ.H, the<br />
economizer minimum position will be the IAQ override<br />
position (ConfigurationIAQAQ.SPIQ.O.P).<br />
• IQ.A.C = 3 (4 to 20 mA minimum position) — With a 4<br />
to 20 mA signal connected to TB201 terminal 7 <strong>and</strong> 8,<br />
the economizer minimum position will be scaled linearly<br />
from 0% (4 mA) to EC.MN (20 mA).<br />
• IQ.A.C = 4 (10K potentiometer minimum position) — With<br />
a 10K linear potentiometer connected to TB201 terminal 7<br />
<strong>and</strong> 8, the economizer minimum position will be scaled linearly<br />
from 0% (0 kilo-ohms) to EC.MN (10 kilo-ohms).<br />
IAQ Analog Fan Config (ConfigurationIAQAQ.CF<br />
IQ.A.F) — This configuration is used to configure the control<br />
of the indoor fan. If this option is used then the IAQ sensor<br />
must be in the space <strong>and</strong> not in the return duct. It has the following<br />
configurations:<br />
• IQ.A.F = 0 (No Fan <strong>Start</strong>) — IAQ dem<strong>and</strong> will never<br />
override normal indoor fan operation during occupied or<br />
unoccupied period <strong>and</strong> turn it on.<br />
• IQ.A.F = 1 (Fan On If Occupied) — IAQ dem<strong>and</strong> will<br />
override normal indoor fan operation <strong>and</strong> turn it on (if<br />
off) only during the occupied period (CV operation with<br />
automatic fan).<br />
• IQ.A.F = 2 (Fan On Occupied/Unoccupied) — IAQ<br />
dem<strong>and</strong> will always override normal indoor fan operation<br />
<strong>and</strong> turn it on (if off) during both the occupied <strong>and</strong> unoccupied<br />
period. For IQ.A.F = 1 or 2, the fan will be turned on as<br />
described above when DAQ is above the DAQ Fan On Set<br />
Point (ConfigurationIAQAQ.SPD.F.ON). The fan<br />
will be turned off when DAQ is below the DAQ Fan Off Set<br />
Point (ConfigurationIAQAQ.SPD.F.OF). The control<br />
can also be set up to respond to a discrete IAQ input.<br />
The discrete input is connected to TB202 terminal 12 <strong>and</strong><br />
13.<br />
IAQ Discrete Input Config (ConfigurationIAQAQ.CF<br />
IQ.I.C) — This configuration is used to set the type of IAQ<br />
sensor. The following are the options:<br />
• IQ.I.C = 0 (No Discrete Input) — This is used to indicate<br />
that no discrete input will be used <strong>and</strong> the st<strong>and</strong>ard IAQ<br />
sensor input will be used.<br />
• IQ.I.C = 1 (IAQ Discrete Input) — This will indicate<br />
that the IAQ level (high or low) will be indicated by<br />
the discrete input. When the IAQ level is low, the<br />
economizer minimum position will be Configuration<br />
IAQDCV.CIAQ.M.<br />
• IQ.I.C = 2 (IAQ Discrete Input with Minimum Position<br />
Override. This will indicate that the IAQ level (high or<br />
low) will be indicated by the discrete input <strong>and</strong> the economizer<br />
minimum position will be the IAQ override position,<br />
IQ.P.O (when high).<br />
It is also necessary to configure how the fan operates when<br />
using the IAQ discrete input.<br />
76<br />
ECONOMIZER<br />
MINIMUM<br />
DAMPER<br />
POSITION<br />
MINIMUM<br />
IAQ<br />
DAMPER<br />
POSITION<br />
INCREASING VENTILATION<br />
VENTILATION FOR PEOPLE<br />
VENTILATION FOR SOURCES<br />
100<br />
500<br />
AQ<br />
DIFFERENTIAL<br />
LOW (DAQ.L)<br />
700<br />
1000<br />
AQ<br />
DIFFERENTIAL<br />
HIGH (DAQ.H)<br />
Fig. 13 — IAQ Control<br />
INSIDE/OUTSIDE CO 2 DIFFERENTIAL<br />
INSIDE CO 2 CONCENTRATION<br />
NOTE: Calculating the IAQ.M <strong>and</strong> EC.MN damper position based<br />
on differential IAQ measurement.<br />
Based on the configuration parameter IAQREACT, the reaction to<br />
damper positioning based on differential air quality ppm can be<br />
adjusted.<br />
IAQREACT = 1 to 5 (more responsive)<br />
IAQREACT = 0 (linear)<br />
IAQREACT = –1 to –5 (less responsive)<br />
Fig. 14 — IAQ Response Curve<br />
IAQ Discrete Fan Config (ConfigurationIAQAQ.CF<br />
IQ.I.F) — This is used to configure the operation of the<br />
fan during an IAQ dem<strong>and</strong> condition. It has the following<br />
configurations:<br />
• IQ.I.F = 0 (No Fan <strong>Start</strong>) — IAQ dem<strong>and</strong> will never<br />
override normal indoor fan operation during occupied or<br />
unoccupied period <strong>and</strong> turn it on.