SETTING UP THE SYSTEM — The IAQ configuration options<br />

are under the Local Display Mode ConfigurationIAQ.<br />

See Table 57.<br />

IAQ Analog Sensor Config (ConfigurationIAQ<br />

AQ.CFIQ.A.C) — This is used to configure the type of<br />

IAQ position control. It has the following options:<br />

• IQ.A.C = 0 (No analog input). If there is no other minimum<br />

position control, the economizer minimum position<br />

will be ConfigurationIAQEC.MN <strong>and</strong> there will be<br />

no IAQ control.<br />

• IQ.A.C = 1 (IAQ analog input). An indoor air (space or<br />

return air) CO 2 sensor is installed. If an outdoor air CO 2<br />

sensor is also installed, or OAQ is broadcast on the CCN,<br />

or if a default OAQ value is used, then the unit can perform<br />

IAQ control.<br />

• IQ.A.C = 2 (IAQ analog input with minimum position<br />

override) — If the differential between IAQ <strong>and</strong> OAQ<br />

is above ConfigurationIAQAQ.SPDAQ.H, the<br />

economizer minimum position will be the IAQ override<br />

position (ConfigurationIAQAQ.SPIQ.O.P).<br />

• IQ.A.C = 3 (4 to 20 mA minimum position) — With a 4<br />

to 20 mA signal connected to TB201 terminal 7 <strong>and</strong> 8,<br />

the economizer minimum position will be scaled linearly<br />

from 0% (4 mA) to EC.MN (20 mA).<br />

• IQ.A.C = 4 (10K potentiometer minimum position) — With<br />

a 10K linear potentiometer connected to TB201 terminal 7<br />

<strong>and</strong> 8, the economizer minimum position will be scaled linearly<br />

from 0% (0 kilo-ohms) to EC.MN (10 kilo-ohms).<br />

IAQ Analog Fan Config (ConfigurationIAQAQ.CF<br />

IQ.A.F) — This configuration is used to configure the control<br />

of the indoor fan. If this option is used then the IAQ sensor<br />

must be in the space <strong>and</strong> not in the return duct. It has the following<br />

configurations:<br />

• IQ.A.F = 0 (No Fan <strong>Start</strong>) — IAQ dem<strong>and</strong> will never<br />

override normal indoor fan operation during occupied or<br />

unoccupied period <strong>and</strong> turn it on.<br />

• IQ.A.F = 1 (Fan On If Occupied) — IAQ dem<strong>and</strong> will<br />

override normal indoor fan operation <strong>and</strong> turn it on (if<br />

off) only during the occupied period (CV operation with<br />

automatic fan).<br />

• IQ.A.F = 2 (Fan On Occupied/Unoccupied) — IAQ<br />

dem<strong>and</strong> will always override normal indoor fan operation<br />

<strong>and</strong> turn it on (if off) during both the occupied <strong>and</strong> unoccupied<br />

period. For IQ.A.F = 1 or 2, the fan will be turned on as<br />

described above when DAQ is above the DAQ Fan On Set<br />

Point (ConfigurationIAQAQ.SPD.F.ON). The fan<br />

will be turned off when DAQ is below the DAQ Fan Off Set<br />

Point (ConfigurationIAQAQ.SPD.F.OF). The control<br />

can also be set up to respond to a discrete IAQ input.<br />

The discrete input is connected to TB202 terminal 12 <strong>and</strong><br />

13.<br />

IAQ Discrete Input Config (ConfigurationIAQAQ.CF<br />

IQ.I.C) — This configuration is used to set the type of IAQ<br />

sensor. The following are the options:<br />

• IQ.I.C = 0 (No Discrete Input) — This is used to indicate<br />

that no discrete input will be used <strong>and</strong> the st<strong>and</strong>ard IAQ<br />

sensor input will be used.<br />

• IQ.I.C = 1 (IAQ Discrete Input) — This will indicate<br />

that the IAQ level (high or low) will be indicated by<br />

the discrete input. When the IAQ level is low, the<br />

economizer minimum position will be Configuration<br />

IAQDCV.CIAQ.M.<br />

• IQ.I.C = 2 (IAQ Discrete Input with Minimum Position<br />

Override. This will indicate that the IAQ level (high or<br />

low) will be indicated by the discrete input <strong>and</strong> the economizer<br />

minimum position will be the IAQ override position,<br />

IQ.P.O (when high).<br />

It is also necessary to configure how the fan operates when<br />

using the IAQ discrete input.<br />

76<br />

ECONOMIZER<br />

MINIMUM<br />

DAMPER<br />

POSITION<br />

MINIMUM<br />

IAQ<br />

DAMPER<br />

POSITION<br />

INCREASING VENTILATION<br />

VENTILATION FOR PEOPLE<br />

VENTILATION FOR SOURCES<br />

100<br />

500<br />

AQ<br />

DIFFERENTIAL<br />

LOW (DAQ.L)<br />

700<br />

1000<br />

AQ<br />

DIFFERENTIAL<br />

HIGH (DAQ.H)<br />

Fig. 13 — IAQ Control<br />

INSIDE/OUTSIDE CO 2 DIFFERENTIAL<br />

INSIDE CO 2 CONCENTRATION<br />

NOTE: Calculating the IAQ.M <strong>and</strong> EC.MN damper position based<br />

on differential IAQ measurement.<br />

Based on the configuration parameter IAQREACT, the reaction to<br />

damper positioning based on differential air quality ppm can be<br />

adjusted.<br />

IAQREACT = 1 to 5 (more responsive)<br />

IAQREACT = 0 (linear)<br />

IAQREACT = –1 to –5 (less responsive)<br />

Fig. 14 — IAQ Response Curve<br />

IAQ Discrete Fan Config (ConfigurationIAQAQ.CF<br />

IQ.I.F) — This is used to configure the operation of the<br />

fan during an IAQ dem<strong>and</strong> condition. It has the following<br />

configurations:<br />

• IQ.I.F = 0 (No Fan <strong>Start</strong>) — IAQ dem<strong>and</strong> will never<br />

override normal indoor fan operation during occupied or<br />

unoccupied period <strong>and</strong> turn it on.