Fig. 48 — Pulley Alignment<br />

Fig. 49 — Condenser-Fan Adjustment<br />

(All Units Except Size 035)<br />

AIR PRESSURE TRANSDUCER FIELD ADJUST-<br />

MENT — All transducers have been factory calibrated <strong>and</strong><br />

should not require field adjustment. If field adjustment is<br />

necessary, follow the instructions below. To re-calibrate a<br />

transducer:<br />

1. Shut the unit power off.<br />

2. Take the wiring <strong>and</strong> pressure tubing off the transducer.<br />

Take the transducer out of the unit.<br />

3. Connect a 24-vdc power supply to transducer terminals<br />

EXC(+) <strong>and</strong> COM(–). See Fig. 51.<br />

4. Using a digital multimeter measure the current between<br />

terminals EXC(+) <strong>and</strong> OUT.<br />

142<br />

5. With both pressure ports open to atmosphere adjust the<br />

Zero (Z) screw potentiometer on the transducer <strong>and</strong> read<br />

the multimeter until the desired current output at 0 in. wg<br />

pressure is obtained (see Fig. 51).<br />

6. Reinstall the transducer in the unit.<br />

7. Restore power to the unit.<br />

FAN ORIFICE<br />

Cleaning — Inspect unit at the beginning of each heating<br />

<strong>and</strong> cooling season <strong>and</strong> during each season as operating conditions<br />

may require.<br />

MICROCHANNEL HEAT EXCHANGER (MCHX) CON-<br />

DENSER COIL MAINTENANCE AND CLEANING<br />

RECOMMENDATIONS<br />

CAUTION<br />

PLASTIC FAN<br />

PROPELLER<br />

CLEARANCE OF 0.25 INCHES<br />

(6.4 MM) FOR STANDARD<br />

CONDENSER FANS<br />

FAN DECK<br />

SURFACE<br />

Fig. 50 — Condenser Fan Position (Size 035 Units)<br />

TRANSDUCER<br />

PART<br />

NUMBER<br />

INPUT<br />

RANGE<br />

(in. wg)<br />

OUTPUT<br />

RANGE<br />

OUTPUT<br />

AT 0 IN. WG<br />

HK05ZG019 0-5 4-20 mA 4 mA<br />

HK05ZG020 0-1 4-20 mA 4 mA<br />

HK05ZG021 0-15 4-20 mA 4 mA<br />

HK05ZG022 –0.25-0.25 4-20 mA 12 mA<br />

PRESSURE PORTS<br />

Fig. 51 — Transducer Details<br />

USAGE<br />

Supply Duct/<br />

Air Foil<br />

Fan Cfm<br />

Forward<br />

Curved<br />

Fan Cfm<br />

Return/<br />

Exhaust<br />

Fan Cfm<br />

Building<br />

Pressure<br />

HIGH<br />

LOW<br />

COM OUT EXC<br />

Do not apply any chemical cleaners to MCHX condenser<br />

coils. These cleaners can accelerate corrosion <strong>and</strong> damage<br />

the coil.<br />