Fig. 48 — Pulley Alignment<br />
Fig. 49 — Condenser-Fan Adjustment<br />
(All Units Except Size 035)<br />
AIR PRESSURE TRANSDUCER FIELD ADJUST-<br />
MENT — All transducers have been factory calibrated <strong>and</strong><br />
should not require field adjustment. If field adjustment is<br />
necessary, follow the instructions below. To re-calibrate a<br />
transducer:<br />
1. Shut the unit power off.<br />
2. Take the wiring <strong>and</strong> pressure tubing off the transducer.<br />
Take the transducer out of the unit.<br />
3. Connect a 24-vdc power supply to transducer terminals<br />
EXC(+) <strong>and</strong> COM(–). See Fig. 51.<br />
4. Using a digital multimeter measure the current between<br />
terminals EXC(+) <strong>and</strong> OUT.<br />
142<br />
5. With both pressure ports open to atmosphere adjust the<br />
Zero (Z) screw potentiometer on the transducer <strong>and</strong> read<br />
the multimeter until the desired current output at 0 in. wg<br />
pressure is obtained (see Fig. 51).<br />
6. Reinstall the transducer in the unit.<br />
7. Restore power to the unit.<br />
FAN ORIFICE<br />
Cleaning — Inspect unit at the beginning of each heating<br />
<strong>and</strong> cooling season <strong>and</strong> during each season as operating conditions<br />
may require.<br />
MICROCHANNEL HEAT EXCHANGER (MCHX) CON-<br />
DENSER COIL MAINTENANCE AND CLEANING<br />
RECOMMENDATIONS<br />
CAUTION<br />
PLASTIC FAN<br />
PROPELLER<br />
CLEARANCE OF 0.25 INCHES<br />
(6.4 MM) FOR STANDARD<br />
CONDENSER FANS<br />
FAN DECK<br />
SURFACE<br />
Fig. 50 — Condenser Fan Position (Size 035 Units)<br />
TRANSDUCER<br />
PART<br />
NUMBER<br />
INPUT<br />
RANGE<br />
(in. wg)<br />
OUTPUT<br />
RANGE<br />
OUTPUT<br />
AT 0 IN. WG<br />
HK05ZG019 0-5 4-20 mA 4 mA<br />
HK05ZG020 0-1 4-20 mA 4 mA<br />
HK05ZG021 0-15 4-20 mA 4 mA<br />
HK05ZG022 –0.25-0.25 4-20 mA 12 mA<br />
PRESSURE PORTS<br />
Fig. 51 — Transducer Details<br />
USAGE<br />
Supply Duct/<br />
Air Foil<br />
Fan Cfm<br />
Forward<br />
Curved<br />
Fan Cfm<br />
Return/<br />
Exhaust<br />
Fan Cfm<br />
Building<br />
Pressure<br />
HIGH<br />
LOW<br />
COM OUT EXC<br />
Do not apply any chemical cleaners to MCHX condenser<br />
coils. These cleaners can accelerate corrosion <strong>and</strong> damage<br />
the coil.<br />