APPENDIX B — CCN TABLES (cont)<br />
STATUS DISPLAY TABLES (cont)<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />
MODETRIP<br />
Unoccup. Cool Mode <strong>Start</strong> UCCLSTRT<br />
Unoccup. Cool Mode End UCCL_END<br />
Occupied Cool Mode <strong>Start</strong> OCCLSTRT<br />
Occupied Cool Mode End OCCL_END<br />
Ctl.Temp RAT,SPT or Zone CTRLTEMP<br />
Occupied Heat Mode End OCHT_END<br />
Occupied Heat Mode <strong>Start</strong> OCHTSTRT<br />
Unoccup. Heat Mode End UCHT_END<br />
Unoccup. Heat Mode <strong>Start</strong> UCHTSTRT<br />
HVAC Mode…………..: ascii text strings string<br />
TEMPCTRL<br />
Evaporator Discharge Tmp dF EDT<br />
Leaving Air Temperature dF LAT<br />
Mixed Air Temperature dF MAT<br />
Controlling Return Temp dF RETURN_T forcible<br />
Controlling Space Temp dF SPACE_T forcible<br />
TEMPS<br />
Air Temp Lvg Supply Fan dF SAT<br />
Return Air Temperature dF RAT forcible<br />
Outside Air Temperature dF OAT forcible<br />
Space Temperature dF SPT forcible<br />
Space Temperature Offset ^F SPTO forcible<br />
Staged Gas LAT Sum dF LAT_SGAS<br />
Staged Gas LAT 1 dF LAT1SGAS<br />
Staged Gas LAT 2 dF LAT2SGAS<br />
Staged Gas LAT 3 dF LAT23SGAS<br />
Staged Gas Limit Sw.Temp dF LIMSWTMP<br />
Air Temp Lvg Evap Coil dF CCT<br />
Cir A Sat.Condensing Tmp dF SCTA<br />
Cir B Sat.Condensing Tmp dF SCTB<br />
Cir A Sat.Suction Temp. dF SSTA<br />
Cir B Sat.Suction Temp. dF SSTB<br />
TSTAT<br />
Control Mode………..: ascii text strings<br />
Thermostat Y1 Input On/Off Y1 forcible<br />
Thermostat Y2 Input On/Off Y2 forcible<br />
Thermostat W1 Input On/Off W1 forcible<br />
Thermostat W2 Input On/Off W2 forcible<br />
Thermostat G Input On/Off G forcible<br />
UINPUTS<br />
Filter Status Input Dirty/Clean FLTS forcible<br />
Fan request from IGC On/Off IGCFAN<br />
Fire Shutdown Input Alarm/Normal FSD forcible<br />
Thermostat G Input On/Off G forcible<br />
Thermostat W2 Input On/Off W2 forcible<br />
Thermostat W1 Input On/Off W1 forcible<br />
Thermostat Y2 Input On/Off Y2 forcible<br />
Thermostat Y1 Input On/Off Y1 forcible<br />
Remote Input State On/Off RMTIN forcible<br />
Enth. Switch Read High ? Yes/No ENTH forcible<br />
Supply Fan Status Switch On/Off SFS forcible<br />
Circ A High Press.Switch On/Off CIRCAHPS<br />
Circ B High Press.Switch On/Off CIRCBHPS<br />
Freeze Status Switch Alarm/Normal FRZ forcible<br />
Plenum Press.Safety Sw. High/Low PPS forcible<br />
Dem<strong>and</strong> Limit Switch 1 On/Off DMD_SW1 forcible<br />
Dem<strong>and</strong> Limit Switch 2 On/Off DMD_SW2 forcible<br />
Pressurization Input Alarm/Normal PRES forcible<br />
Evacuation Input Alarm/Normal EVAC forcible<br />
Smoke Purge Input Alarm/Normal PURG forcible<br />
IAQ - Discrete Input High/Low IAQIN forcible<br />
Dehumidify Switch Input On/Off DHDISCIN forcible<br />
178