SUPPLY FAN VFD CONFIGURATION — The sub-menu<br />
that contains these configurations is located at the local display<br />
under ConfigurationS.VFD.<br />
VFD1 Nominal Motor Volts (N.VLT) — This configuration<br />
defines the nominal motor voltage. This value must equal the<br />
value on the motor rating plate. This value sets the maximum<br />
drive output voltage supplied to the motor.<br />
NOTE: The VFD cannot supply the motor with a greater voltage<br />
than the voltage supplied to the input of the VFD. Power to<br />
the VFD must be cycled in order for a change to this configuration<br />
to take effect.<br />
VFD1 Nominal Motor Amps (N.AMP) — This configuration<br />
defines the nominal motor current. This value must equal<br />
the value defined in the Supply Fan Motor Limitations Table<br />
26 or Table 27. Power to the VFD must be cycled in order for a<br />
change to this configuration to take effect.<br />
VFD1 Nominal Motor Freq (N.FRQ) — This configuration<br />
defines the nominal motor frequency. This value must equal<br />
the value on the motor rating plate. This value sets the frequency<br />
at which the output voltage equals the Nominal Motor Volts<br />
(N.VLT). Power to the VFD must be cycled in order for a<br />
change to this configuration to take effect.<br />
VFD1 Nominal Motor RPM (N.RPM) — This configuration<br />
defines the nominal motor speed. This value must equal<br />
the value on the motor rating plate. Power to the VFD must be<br />
cycled in order for a change to this configuration to take effect.<br />
VFD1 Nominal Motor HPwr (N.PWR) — This configuration<br />
defines the nominal motor power. This value must equal<br />
the value on the motor rating plate. Power to the VFD must be<br />
cycled in order for a change to this configuration to take effect.<br />
VFD1 Motor Direction (M.DIR) — This configuration sets<br />
the direction of motor rotation. Motor direction change occurs<br />
immediately upon a change to this configuration. Power to the<br />
VFD need NOT be cycled for a change to this configuration to<br />
take effect.<br />
VFD1 Acceleration Time (ACCL) — This configuration sets<br />
the acceleration time from zero to maximum output frequency.<br />
Power to the VFD must be cycled in order for a change to this<br />
configuration to take effect.<br />
VFD1 Deceleration Time (DECL) — This configuration sets<br />
the deceleration time from maximum output frequency to zero.<br />
Power to the VFD must be cycled in order for a change to this<br />
configuration to take effect.<br />
VFD1 Switching Frequency (SW.FQ) — This configuration<br />
sets the switching frequency for the drive. Power to the VFD<br />
*This default is model number dependent.<br />
Table 65 — Display Configuration<br />
Table 66 — Supply Fan VFD Configuration<br />
87<br />
must be cycled in order for a change to this configuration to<br />
take effect.<br />
VFD1 Type (TYPE) — This configuration sets the type of<br />
VFD communication. This configuration should not be<br />
changed without first consulting a Carrier service engineering<br />
representative.<br />
EXHAUST FAN VFD CONFIGURATION — The submenu<br />
that contains these configurations is located at the local<br />
display under ConfigurationE.VFD.<br />
VFD2 Nominal Motor Volts (N.VLT) — This configuration<br />
defines the nominal motor voltage. This value must equal the<br />
value on the motor rating plate. This value sets the maximum<br />
drive output voltage supplied to the motor.<br />
NOTE: The VFD cannot supply the motor with a greater voltage<br />
than the voltage supplied to the input of the VFD. Power to<br />
the VFD must be cycled in order for a change to this configuration<br />
to take effect.<br />
VFD2 Nominal Motor Amps (N.AMP) — This configuration<br />
defines the nominal motor current. This value must equal<br />
the value defined in the High-Capacity Power Exhaust Systems<br />
Motor Limitations Table 28. Power to the VFD must be cycled<br />
in order for a change to this configuration to take effect.<br />
VFD2 Nominal Motor Freq (N.FRQ) — This configuration<br />
defines the nominal motor frequency. This value must equal<br />
the value on the motor rating plate. This value sets the frequency<br />
at which the output voltage equals the Nominal Motor Volts<br />
(N.VLT). Power to the VFD must be cycled in order for a<br />
change to this configuration to take effect.<br />
VFD2 Nominal Motor RPM (N.RPM) — This configuration<br />
defines the nominal motor speed. This value must equal<br />
the value on the motor rating plate. Power to the VFD must be<br />
cycled in order for a change to this configuration to take effect.<br />
VFD2 Nominal Motor HPwr (N.PWR) — This configuration<br />
defines the nominal motor power. This value must equal<br />
the value on the motor rating plate. Power to the VFD must be<br />
cycled in order for a change to this configuration to take effect.<br />
VFD2 Motor Direction (M.DIR) — This configuration sets<br />
the direction of motor rotation. Motor direction change occurs<br />
immediately upon a change to this configuration. Power to the<br />
VFD need NOT be cycled for a change to this configuration to<br />
take effect.<br />
VFD2 Acceleration Time (ACCL) — This configuration sets<br />
the acceleration time from zero to maximum output frequency.<br />
Power to the VFD must be cycled in order for a change to this<br />
configuration to take effect.<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
TEST Test Display LEDs ON/OFF TEST Off<br />
METR Metric Display ON/OFF DISPUNIT Off<br />
LANG Language Selection 0-1(multi-text strings) LANGUAGE 0<br />
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable<br />
PASS <strong>Service</strong> Password 0000-9999 PASSWORD 1111<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
S.VFD SUPPLY FAN VFD CONFIG<br />
N.VLT VFD1 Nominal Motor Volts 0 to 999 Volts VFD1NVLT 460*<br />
N.AMP VFD1 Nominal Motor Amps 0 to 999 Amps VFD1NAMP 55.0*<br />
N.FRQ VFD1 Nominal Motor Freq 10 to 500 Hz VFD1NFRQ 60<br />
N.RPM VFD1 Nominal Motor RPM 50 to 30000 RPM VFD1NRPM 1750<br />
N.PWR VFD1 Nominal Motor HPwr 0 to 500 HP VFD1NPWR 40*<br />
M.DIR VFD1 Motor Direction 0=FWD, 1=REV VFD1MDIR 0<br />
ACCL VFD1 Acceleration Time 0 to 1800 sec VFD1ACCL 30<br />
DECL VFD1 Deceleration Time 0 to 1800 sec VFD1DECL 30<br />
SW.FQ VFD1 Switching Frequency 0=1kHz, 1=4kHz, 2=8kHz, 3=12kHz VFD1SWFQ 2<br />
TYPE VFD1 Type 0=LEN, 1=ANALOG VFD1TYPE 0