SUPPLY FAN VFD CONFIGURATION — The sub-menu<br />

that contains these configurations is located at the local display<br />

under ConfigurationS.VFD.<br />

VFD1 Nominal Motor Volts (N.VLT) — This configuration<br />

defines the nominal motor voltage. This value must equal the<br />

value on the motor rating plate. This value sets the maximum<br />

drive output voltage supplied to the motor.<br />

NOTE: The VFD cannot supply the motor with a greater voltage<br />

than the voltage supplied to the input of the VFD. Power to<br />

the VFD must be cycled in order for a change to this configuration<br />

to take effect.<br />

VFD1 Nominal Motor Amps (N.AMP) — This configuration<br />

defines the nominal motor current. This value must equal<br />

the value defined in the Supply Fan Motor Limitations Table<br />

26 or Table 27. Power to the VFD must be cycled in order for a<br />

change to this configuration to take effect.<br />

VFD1 Nominal Motor Freq (N.FRQ) — This configuration<br />

defines the nominal motor frequency. This value must equal<br />

the value on the motor rating plate. This value sets the frequency<br />

at which the output voltage equals the Nominal Motor Volts<br />

(N.VLT). Power to the VFD must be cycled in order for a<br />

change to this configuration to take effect.<br />

VFD1 Nominal Motor RPM (N.RPM) — This configuration<br />

defines the nominal motor speed. This value must equal<br />

the value on the motor rating plate. Power to the VFD must be<br />

cycled in order for a change to this configuration to take effect.<br />

VFD1 Nominal Motor HPwr (N.PWR) — This configuration<br />

defines the nominal motor power. This value must equal<br />

the value on the motor rating plate. Power to the VFD must be<br />

cycled in order for a change to this configuration to take effect.<br />

VFD1 Motor Direction (M.DIR) — This configuration sets<br />

the direction of motor rotation. Motor direction change occurs<br />

immediately upon a change to this configuration. Power to the<br />

VFD need NOT be cycled for a change to this configuration to<br />

take effect.<br />

VFD1 Acceleration Time (ACCL) — This configuration sets<br />

the acceleration time from zero to maximum output frequency.<br />

Power to the VFD must be cycled in order for a change to this<br />

configuration to take effect.<br />

VFD1 Deceleration Time (DECL) — This configuration sets<br />

the deceleration time from maximum output frequency to zero.<br />

Power to the VFD must be cycled in order for a change to this<br />

configuration to take effect.<br />

VFD1 Switching Frequency (SW.FQ) — This configuration<br />

sets the switching frequency for the drive. Power to the VFD<br />

*This default is model number dependent.<br />

Table 65 — Display Configuration<br />

Table 66 — Supply Fan VFD Configuration<br />

87<br />

must be cycled in order for a change to this configuration to<br />

take effect.<br />

VFD1 Type (TYPE) — This configuration sets the type of<br />

VFD communication. This configuration should not be<br />

changed without first consulting a Carrier service engineering<br />

representative.<br />

EXHAUST FAN VFD CONFIGURATION — The submenu<br />

that contains these configurations is located at the local<br />

display under ConfigurationE.VFD.<br />

VFD2 Nominal Motor Volts (N.VLT) — This configuration<br />

defines the nominal motor voltage. This value must equal the<br />

value on the motor rating plate. This value sets the maximum<br />

drive output voltage supplied to the motor.<br />

NOTE: The VFD cannot supply the motor with a greater voltage<br />

than the voltage supplied to the input of the VFD. Power to<br />

the VFD must be cycled in order for a change to this configuration<br />

to take effect.<br />

VFD2 Nominal Motor Amps (N.AMP) — This configuration<br />

defines the nominal motor current. This value must equal<br />

the value defined in the High-Capacity Power Exhaust Systems<br />

Motor Limitations Table 28. Power to the VFD must be cycled<br />

in order for a change to this configuration to take effect.<br />

VFD2 Nominal Motor Freq (N.FRQ) — This configuration<br />

defines the nominal motor frequency. This value must equal<br />

the value on the motor rating plate. This value sets the frequency<br />

at which the output voltage equals the Nominal Motor Volts<br />

(N.VLT). Power to the VFD must be cycled in order for a<br />

change to this configuration to take effect.<br />

VFD2 Nominal Motor RPM (N.RPM) — This configuration<br />

defines the nominal motor speed. This value must equal<br />

the value on the motor rating plate. Power to the VFD must be<br />

cycled in order for a change to this configuration to take effect.<br />

VFD2 Nominal Motor HPwr (N.PWR) — This configuration<br />

defines the nominal motor power. This value must equal<br />

the value on the motor rating plate. Power to the VFD must be<br />

cycled in order for a change to this configuration to take effect.<br />

VFD2 Motor Direction (M.DIR) — This configuration sets<br />

the direction of motor rotation. Motor direction change occurs<br />

immediately upon a change to this configuration. Power to the<br />

VFD need NOT be cycled for a change to this configuration to<br />

take effect.<br />

VFD2 Acceleration Time (ACCL) — This configuration sets<br />

the acceleration time from zero to maximum output frequency.<br />

Power to the VFD must be cycled in order for a change to this<br />

configuration to take effect.<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

TEST Test Display LEDs ON/OFF TEST Off<br />

METR Metric Display ON/OFF DISPUNIT Off<br />

LANG Language Selection 0-1(multi-text strings) LANGUAGE 0<br />

PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable<br />

PASS <strong>Service</strong> Password 0000-9999 PASSWORD 1111<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

S.VFD SUPPLY FAN VFD CONFIG<br />

N.VLT VFD1 Nominal Motor Volts 0 to 999 Volts VFD1NVLT 460*<br />

N.AMP VFD1 Nominal Motor Amps 0 to 999 Amps VFD1NAMP 55.0*<br />

N.FRQ VFD1 Nominal Motor Freq 10 to 500 Hz VFD1NFRQ 60<br />

N.RPM VFD1 Nominal Motor RPM 50 to 30000 RPM VFD1NRPM 1750<br />

N.PWR VFD1 Nominal Motor HPwr 0 to 500 HP VFD1NPWR 40*<br />

M.DIR VFD1 Motor Direction 0=FWD, 1=REV VFD1MDIR 0<br />

ACCL VFD1 Acceleration Time 0 to 1800 sec VFD1ACCL 30<br />

DECL VFD1 Deceleration Time 0 to 1800 sec VFD1DECL 30<br />

SW.FQ VFD1 Switching Frequency 0=1kHz, 1=4kHz, 2=8kHz, 3=12kHz VFD1SWFQ 2<br />

TYPE VFD1 Type 0=LEN, 1=ANALOG VFD1TYPE 0