CONTROLS SET POINT AND CONFIGURATION LOG (cont)<br />

ITEM EXPANSION RANGE DEFAULT SETTING<br />

BP (cont)<br />

FAN.T FAN TRACKING CONFIG<br />

FAN.TFT.CF Fan Track Learn Enable Yes/No No<br />

FAN.TFT.TM Fan Track Learn Rate 5-60 min 15<br />

FAN.TFT.ST Fan Track Initial DCFM -20000 - 20000 CFM 2000<br />

FAN.TFT.MX Fan Track Max Clamp 0 - 20000 CFM 4000<br />

FAN.TFT.AD Fan Track Max Correction 0 -20000 CFM 1000<br />

FAN.TFT.OF Fan Track Internl EEPROM -20000 - 20000 CFM 0<br />

FAN.TFT.RM Fan Track Internal RAM -20000 - 20000 CFM 0<br />

FAN.TFT.RS Fan Track Reset Internal Yes/No No<br />

FAN.TSCF.C Supply Air CFM Config 1 - 2 (multi-text strings) 1<br />

B.PID BLDG.PRESS.PID CONFIGS<br />

B.PIDBP.TM Bldg.Pres.PID Run Rate 5 - 120 sec 10<br />

B.PIDBP.P Bldg.Press. Prop. Gain 0 - 5 0.5<br />

B.PIDBP.I Bldg.Press. Integ. Gain 0 - 2 0.5<br />

B.PIDBP.D Bldg.Press. Deriv. Gain 0 - 5 0.3<br />

ACT.C BLDG.PRES. ACTUATOR CFGS<br />

ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS<br />

ACT.CBP.1SN.1 BP 1 Serial Number 1 0 - 9999 0<br />

ACT.CBP.1SN.2 BP 1 Serial Number 2 0 - 6 0<br />

ACT.CBP.1SN.3 BP 1 Serial Number 3 0 - 9999 0<br />

ACT.CBP.1SN.4 BP 1 Serial Number 4 0 - 254 0<br />

ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0-90 35<br />

ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS<br />

ACT.CBP.2SN.1 BP 2 Serial Number 1 0 - 9999 0<br />

ACT.CBP.2SN.2 BP 2 Serial Number 2 0 - 6 0<br />

ACT.CBP.2SN.3 BP 2 Serial Number 3 0 - 9999 0<br />

ACT.CBP.2SN.4 BP 2 Serial Number 4 0 - 254 0<br />

ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0-90 35<br />

D.LV.T COOL/HEAT SETPT. OFFSETS<br />

L.H.ON Dmd Level Lo Heat On 0 - 2 ^F 1.5<br />

H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F 0.5<br />

L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2.0 ^F 1.0<br />

L.C.ON Dmd Level Lo Cool On 0 - 2 ^F 1.5<br />

H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F 0.5<br />

L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2.0 ^F 1.0<br />

C.T.LV Cool Trend Dem<strong>and</strong> Level 0.1 - 5.0 ^F 0.1<br />

H.T.LV Heat Trend Dem<strong>and</strong> Level 0.1 - 5.0 ^F 0.1<br />

C.T.TM Cool Trend Time 30 - 600 sec 120<br />

H.T.TM Heat Trend Time 30 - 600 sec 120<br />

DMD.L DEMAND LIMIT CONFIG.<br />

DM.L.S Dem<strong>and</strong> Limit Select 0 - 3 (multi-text strings) 0<br />

D.L.20 Dem<strong>and</strong> Limit at 20 ma 0 - 100% 100<br />

SH.NM Loadshed Group Number 0 - 99 0<br />

SH.DL Loadshed Dem<strong>and</strong> Delta 0 - 60% 0<br />

SH.TM Maximum Loadshed Time 0 - 120 min 60<br />

D.L.S1 Dem<strong>and</strong> Limit Sw.1 Setpt. 0 - 100% 80<br />

D.L.S2 Dem<strong>and</strong> Limit Sw.2 Setpt. 0 - 100% 50<br />

IAQ INDOOR AIR QUALITY CFG.<br />

DCV.C DCV ECONOMIZER SETPOINTS<br />

DCV.CEC.MN Economizer Min.Position 0 - 100% 5<br />

DCV.CIAQ.M IAQ Dem<strong>and</strong> Vent Min.Pos. 0 - 100% 0<br />

DCV.CO.C.MX Economizer Min.Flow 0 - 20000 CFM 2000<br />

DCV.CO.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM 0<br />

DCV.CO.C.DB Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM 400<br />

AQ.CF AIR QUALITY CONFIGS<br />

AQ.CFIQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) 0<br />

AQ.CFIQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) 0<br />

AQ.CFIQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) 0<br />

AQ.CFIQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) 0<br />

AQ.CFOQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) 0<br />

CL-4<br />

- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -<br />