APPENDIX B — CCN TABLES (cont)<br />

SERVICE-CONFIG TABLES (cont)<br />

TABLE DISPLAY NAME RANGE UNITS POINT NAME DEFAULT<br />

UNIT<br />

Machine Control Type 1-6 CTRLTYPE 4<br />

Unit Size (30-100) 30-100 UNITSIZE 30<br />

Fan Mode (0=auto, 1=cont) 0-1 FAN_MODE 1<br />

Remote Switch Config 0 - 3 RMTINCFG 0<br />

CEM Module Installed Yes/No CEM_BRD No<br />

Temp.Cmp.Strt.Cool Factr 0-60 min TCSTCOOL 0<br />

Temp.Cmp.Strt.Heat Factr 0-60 min TCSTHEAT 0<br />

Fan fail shuts down unit Yes/No SFS_SHUT No<br />

Fan Stat Monitoring Type 0-2 SFS_MON 0<br />

VAV Unocc.Fan Retry time 0-720 min SAMPMINS 50<br />

50 Hertz Unit ? Yes/No UNIT_HZ No<br />

MAT Calc Config Type 0-2 MAT_SEL 1<br />

Reset MAT Table Entries? Yes/No MATRESET No<br />

MAT Outside Air Default 0 - 100 % MATOAPOS 20<br />

Altitude……..in feet: 0-60000 ALTITUDE 0<br />

MAT Outside Air Default % MATOAPOS<br />

<strong>Start</strong>up Delay Time 0 - 900 secs DELAY 0<br />

Auxiliary Relay Config 0 - 3 (multi-text strings) AUXRELAY 0<br />

Space Temp Sensor Enable/Disable SPTSENS Disable<br />

Space Temp Offset Sensor Enable/Disable SPTOSENS Disable<br />

Space Temp Offset Range 1 - 10 SPTO_RNG 5<br />

Space Air RH Sensor Enable/Disable SPRHSENS Disable<br />

Return Air RH Sensor Enable/Disable RARHSENS Disable<br />

Filter Stat.Sw.Enabled ? Enable/Disable FLTS_ENA Disable<br />

VFD_CFG<br />

VFD1 Nominal Motor Volts volts VFD1NVLT<br />

VFD1 Nominal Motor Amps amps VFD1NAMP<br />

VFD1 Nominal Motor Freq VFD1NFRQ<br />

VFD1 Nominal Motor RPM VFD1NRPM<br />

VFD1 Nominal Motor HPwr VFD1NPWR<br />

VFD1 Motor Direction VFD1MDIR<br />

VFD1 Acceleration Time sec VFD1ACCL<br />

VFD1 Deceleration Time sec VFD1DECL<br />

VFD1 Switching Frequency VFD1SWFQ<br />

VFD1 Type VFD1TYPE<br />

VFD2 Nominal Motor Volts volts VFD2NVLT<br />

VFD2 Nominal Motor Amps amps VFD2NAMP<br />

VFD2 Nominal Motor Freq VFD2NFRQ<br />

VFD2 Nominal Motor RPM VFD2NRPM<br />

VFD2 Nominal Motor HPwr VFD2NPWR<br />

VFD2 Motor Direction VFD2MDIR<br />

VFD2 Acceleration Time sec VFD2ACCL<br />

VFD2 Deceleration Time sec VFD2DECL<br />

VFD2 Switching Frequency VFD2SWFQ<br />

VFD2 Type VFD2TYPE<br />

generics<br />

Target Point Name 8 CHAR ASCII POINT_01<br />

Target Point Name 8 CHAR ASCII POINT_02<br />

Target Point Name 8 CHAR ASCII POINT_03<br />

Target Point Name 8 CHAR ASCII POINT_04<br />

Target Point Name 8 CHAR ASCII POINT_05<br />

Target Point Name 8 CHAR ASCII POINT_06<br />

Target Point Name 8 CHAR ASCII POINT_07<br />

Target Point Name 8 CHAR ASCII POINT_08<br />

Target Point Name 8 CHAR ASCII POINT_09<br />

Target Point Name 8 CHAR ASCII POINT_10<br />

Target Point Name 8 CHAR ASCII POINT_11<br />

Target Point Name 8 CHAR ASCII POINT_12<br />

Target Point Name 8 CHAR ASCII POINT_13<br />

Target Point Name 8 CHAR ASCII POINT_14<br />

Target Point Name 8 CHAR ASCII POINT_15<br />

Target Point Name 8 CHAR ASCII POINT_16<br />

Target Point Name 8 CHAR ASCII POINT_17<br />

Target Point Name 8 CHAR ASCII POINT_18<br />

Target Point Name 8 CHAR ASCII POINT_19<br />

Target Point Name 8 CHAR ASCII POINT_20<br />