CONTROLS SET POINT AND CONFIGURATION LOG (cont)<br />
ITEM EXPANSION RANGE DEFAULT SETTING<br />
UNIT (cont)<br />
DS.AD Dig Scroll Adjust Delay 15 - 60 sec 20<br />
DS.RP Dig Scroll Reduce Delta 0 - 100% 6<br />
DS.RD Dig Scroll Reduce Delay 15 - 60 sec 30<br />
DS.RO Dig Scroll Reduction OAT 70 - 120 dF 95<br />
DS.MO Dig Scroll Max Only OAT 70 - 120 dF 105<br />
MLV Min Load Valve Enable Enable/Disable Disable<br />
H.SST Hi SST Alert Delay Time 5 - 30 min 10<br />
RR.VF Rev Rotation Verified ? Yes/No No<br />
CS.HP Use CSBs for HPS detect? Yes/No Yes<br />
EDT.R EVAP.DISCHRGE TEMP RESET<br />
RS.CF EDT Reset Configuration 0 - 3 (multi-text strings) 2<br />
RTIO Reset Ratio 0 - 10 3<br />
LIMT Reset Limit 0 - 20 ^F 10<br />
RES.S EDT 4-20 ma Reset Input Enable/Disable Disable<br />
HEAT HEATING CONFIGURATION<br />
HT.CF Heating Control Type 0 - 4 0<br />
HT.SP Heating Supply Air Setpt 80 - 120 dF 85<br />
OC.EN Occupied Heating Enabled Yes/No No<br />
LAT.M MBB Sensor Heat Relocate Yes/No No<br />
SG.CF STAGED GAS CONFIGS<br />
SG.CFHT.ST Staged Gas Heat Type 0 - 4 0<br />
SG.CFCAP.M Max Cap Change per Cycle 5 - 45 45<br />
SG.CFM.R.DB S.Gas DB min.dF/PID Rate 0 - 5 0.5<br />
SG.CFS.G.DB St.Gas Temp. Dead B<strong>and</strong> 0 - 5 ^F 2<br />
SG.CFRISE Heat Rise dF/sec Clamp 0.05 - 0.2 0.06<br />
SG.CFLAT.L LAT Limit Config 0 - 20 ^F 10<br />
SG.CFLIM.M Limit Switch Monitoring? Yes/No Yes<br />
SG.CFSW.H.T Limit Switch High Temp 110 - 180 dF 170<br />
SG.CFSW.L.T Limit Switch Low Temp 100 - 170 dF 160<br />
SG.CFHT.P Heat Control Prop. Gain 0 - 1.5 1<br />
SG.CFHT.D Heat Control Derv. Gain 0 - 1.5 1<br />
SG.CFHT.TM Heat PID Rate Config 60 - 300 sec 90<br />
HH.CF HYDRONIC HEAT CONFIGS<br />
HH.CFHW.P Hydronic Ctl.Prop. Gain 0 - 1.5 1<br />
HH.CFHW.I Hydronic Ctl.Integ. Gain 0 - 1.5 1<br />
HH.CFHW.D Hydronic Ctl.Derv. Gain 0 - 1.5 1<br />
HH.CFHW.TM Hydronic PID Rate Config 15 - 300 sec 90<br />
HH.CFACT.C HYDR.HEAT ACTUATOR CFGS.<br />
HH.CFACTCSN.1 Hydronic Ht.Serial Num.1 0 - 9999 0<br />
HH.CFACTCSN.2 Hydronic Ht.Serial Num.2 0 - 6 0<br />
HH.CFACTCSN.3 Hydronic Ht.Serial Num.3 0 - 9999 0<br />
HH.CFACTCSN.4 Hydronic Ht.Serial Num.4 0 - 254 0<br />
HH.CFACTCC.A.LM Hydr.Ht.Ctl.Ang.Lo Limit 0-90 85<br />
SP SUPPLY STATIC PRESS.CFG.<br />
SP.CF Static Pressure Config Enable/Disable Disable<br />
SP.S Static Pressure Sensor Enable/Disable Disable<br />
SP.LO Static Press. Low Range -10 - 0 0<br />
SP.HI Static Press. High Range 0 - 10 5<br />
SP.SP Static Pressure Setpoint 0 - 5 1.5<br />
SP.MN VFD Minimum Speed 0 - 100 20<br />
SP.MX VFD Maximum Speed 0 - 100 100<br />
SP.FS VFD Fire Speed Over. 0 - 100 100<br />
SP.RS Stat. Pres. Reset Config 0 - 4 (multi-text strings) 0<br />
SP.RT SP Reset Ratio 0.00 - 2.00 0.20<br />
SP.LM SP Reset Limit 0.00 - 2.00 0.75<br />
SP.EC SP Reset Econo Position 0 - 100% 5<br />
S.PID STAT.PRESS.PID CONFIGS<br />
S.PIDSP.TM Stat.Pres.PID Run Rate 5 - 120 15<br />
S.PIDSP.P Static Press. Prop. Gain 0 - 5 0.5<br />
S.PIDSP.I Static Pressure Intg. Gain 0 - 2 0.5<br />
S.PIDSP.D Static Pressure Derv. Gain 0 - 5 0.3<br />
CL-2<br />
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -<br />