APPENDIX A — LOCAL DISPLAY TABLES (cont)<br />

MODE — CONFIGURATION (cont)<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.<br />

SP SUPPLY STATIC PRESS.CFG.<br />

SP.CF Static Pressure Config Enable/Disable STATICFG Disable 64-66<br />

SP.S Static Pressure Sensor Enable/Disable SPSENS Disable 64,65<br />

SP.LO Static Press. Low Range -10 - 0 SP_LOW 0 64,65<br />

SP.HI Static Press. High Range 0 - 10 SP_HIGH 5 64,65<br />

SP.SP Static Pressure Setpoint 0 - 5 SPSP 1.5 32,64,65<br />

SP.MN VFD Minimum Speed 0 - 100 STATPMIN 20 38,64,65<br />

SP.MX VFD Maximum Speed 0 - 100 STATPMAX 100 38,64,65<br />

SP.FS VFD Fire Speed Over. 0 - 100 STATPFSO 100 64,65,75<br />

SP.RS Stat. Pres. Reset Config 0 - 4 (multi-text strings) SPRSTCFG 0 38,43,65<br />

SP.RT SP Reset Ratio 0.00 - 2.00 SPRRATIO 0.20 65<br />

SP.LM SP Reset Limit 0.00 - 2.00 SPRLIMIT 0.75 65<br />

SP.EC SP Reset Econo. Position 0 - 100 % ECONOSPR 5 65<br />

S.PID STAT.PRESS.PID CONFIGS<br />

S.PIDSP.TM Stat.Pres.PID Run Rate 5 - 120 SPIDRATE 15 65<br />

S.PIDSP.P Static Press. Prop. Gain 0 - 5 STATP_PG 0.5 65<br />

S.PIDSP.I Static Pressure Intg. Gain 0 - 2 STATP_IG 0.5 65<br />

S.PIDSP.D Static Pressure Derv. Gain 0 - 5 STATP_DG 0.3 65<br />

ECON ECONOMIZER CONFIGURATION<br />

EC.EN Economizer Installed? Yes/No ECON_ENA Yes 33,67,68<br />

EC2.E Econ.Act.2 Installed? Yes/No ECON_TWO No 33,67,68<br />

EC.MN Economizer Min.Position 0 - 100 % ECONOMIN 5 33,67,68,70,<br />

114<br />

EC.MX Economizer Max.Position 0 - 100 % ECONOMAX 98 33,57,67,68<br />

E.TRM Economzr Trim For SumZ ? Yes/No ECONTRIM Yes 33,52,67,68<br />

E.SEL Econ ChangeOver Select 0 - 3 (multi-text strings) ECON_SEL 0 33,40,67,68<br />

OA.E.C OA Enthalpy ChgOvr Selct 1 - 5 (multi-text strings) OAEC_SEL 4 33,68<br />

OA.EN Outdr.Enth Compare Value 18 - 28 OAEN_CFG 24 33,67,68<br />

OAT.L High OAT Lockout Temp -40 - 120 dF OAT_LOCK 60 33,67,68<br />

O.DEW OA Dewpoint Temp Limit 50 - 62 dF OADEWCFG 55 33,68,69<br />

ORH.S Outside Air RH Sensor Enable/Disable OARHSENS Disable 33,43,68<br />

CFM.C OUTDOOR AIR CFM CONTROL<br />

CFM.COCF.S Outdoor Air CFM Sensor Enable/Disable OCFMSENS Disable 33,43,68-70,<br />

78<br />

CFM.CO.C.MX Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000 33,68-70,78<br />

CFM.CO.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM OACFMMIN 0 68-70,78<br />

CFM.CO.C.DB Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM OACFM_DB 400 33,68-70,78<br />

E.CFG ECON.OPERATION CONFIGS<br />

E.CFGE.P.GN Economizer Prop.Gain 0.7 - 3.0 EC_PGAIN 1 68<br />

E.CFGE.RNG Economizer Range Adjust 0.5 - 5 ^F EC_RANGE 2.5 68<br />

E.CFGE.SPD Economizer Speed Adjust 0.1 - 10 EC_SPEED 0.75 68<br />

E.CFGE.DBD Economizer Deadb<strong>and</strong> 0.1 - 2 ^F EC_DBAND 0.5 68<br />

UEFC UNOCC.ECON.FREE COOLING<br />

UEFCFC.CF Unoc Econ Free Cool Cfg 0-2 (multi-text strings) UEFC_CFG 0 70<br />

UEFCFC.TM Unoc Econ Free Cool Time 0 - 720 min UEFCTIME 120 70<br />

UEFCFC.L.O Un.Ec.Free Cool OAT Lock 40 - 70 dF UEFCNTLO 50 70<br />

ACT.C ECON.ACTUATOR CONFIGS<br />

ACTCSN.1.1 Econ Serial Number 1 0 - 9999 ECON_SN1 0 68,70<br />

ACTCSN.1.2 Econ Serial Number 2 0 - 6 ECON_SN2 0 68,70<br />

ACTCSN.1.3 Econ Serial Number 3 0 - 9999 ECON_SN3 0 68,70<br />

ACTCSN.1.4 Econ Serial Number 4 0 - 254 ECON_SN4 0 68,70<br />

ACTCC.A.L1 Econ Ctrl Angle Lo Limit 0 - 90 ECONCALM 85 68,70<br />

ACTCSN.2.1 Econ 2 Serial Number 1 0 - 9999 ECN2_SN1 0 68,70<br />

ACTCSN.2.2 Econ 2 Serial Number 2 0 - 6 ECN2_SN2 0 68,70<br />

ACTCSN.2.3 Econ 2 Serial Number 3 0 - 9999 ECN2_SN3 0 68,70<br />

ACTCSN.2.4 Econ 2 Serial Number 4 0 - 254 ECN2_SN4 0 68,70<br />

ACTCC.A.L2 Ecn2 Ctrl Angle Lo Limit 0 - 90 ECN2CALM 85 68,70<br />

BP BUILDING PRESS. CONFIGS<br />

BP.CF Building Press. Config 0 - 5 (multi-text strings) BLDG_CFG 0 33,34,71-73<br />

BP.S Building Pressure Sensor Enable/Disable BPSENS Disable 72,73<br />

BP.R Bldg. Press. (+/-) Range 0.10 - 0.25 "H2O BP_RANGE 0.25 72,73<br />

BP.SP Building Pressure Setp. -0.25 - 0.25 "H2O BPSP 0.05 34,72,73<br />

BP.SO BP Setpoint Offset 0 - 0.5 "H2O BPSO 0.05 34,72,73<br />

BP.P1 Power Exhaust On Setp.1 0 - 100 % PES1 25 72,73<br />

BP.P2 Power Exhaust On Setp.2 0 - 100 % PES2 75 72,73<br />

B.V.A VFD/ACTUATOR CONFIG<br />

B.V.ABP.FS VFD/Act. Fire Speed/Pos. 0 - 100 % BLDGPFSO 100 34,72,73,75<br />

B.V.ABP.MN VFD/Act. Min.Speed/Pos. 0 - 50 % BLDGPMIN 0 34,72,73<br />

B.V.ABP.MX VFD Maximum Speed 50 - 100 % BLDGPMAX 100 34,72,73<br />

B.V.ABP.1M BP 1 Actuator Max Pos. 85 - 100 % BP1SETMX 100 34,72,73<br />

B.V.ABP.2M BP 2 Actuator Max Pos. 85 - 100 % BP2SETMX 100 34,72,73<br />

B.V.ABP.CL BP Hi Cap VFD Clamp Val. 5 - 25 % BLDGCLMP 10 34,72,73<br />

FAN.T FAN TRACKING CONFIG<br />

FAN.TFT.CF Fan Track Learn Enable Yes/No DCFM_CFG No 34,72,73<br />

FAN.TFT.TM Fan Track Learn Rate 5-60 min DCFMRATE 15 34,72,73<br />

FAN.TFT.ST Fan Track Initial DCFM -20000 - 20000 CFM DCFMSTRT 2000 34,72,73<br />

FAN.TFT.MX Fan Track Max Clamp 0 - 20000 CFM DCFM_MAX 4000 34,72,73<br />

FAN.TFT.AD Fan Track Max Correction 0 -20000 CFM DCFM_ADJ 1000 34,72,73<br />

FAN.TFT.OF Fan Track Internl EEPROM -20000 - 20000 CFM DCFM_OFF 0 34,72,73<br />

FAN.TFT.RM Fan Track Internal RAM -20000 - 20000 CFM DCFM_RAM 0 34,72,73<br />

FAN.TFT.RS Fan Track Reset Internal Yes/No DCFMRSET No 34,72,73<br />

FAN.TSCF.C Supply Air CFM Config 1 - 2 (multi-text strings) SCFM_CFG 1 34,72,73<br />

B.PID BLDG.PRESS.PID CONFIGS<br />

B.PIDBP.TM Bldg.Pres.PID Run Rate 5 - 120 sec BPIDRATE 10 72,73<br />

B.PIDBP.P Bldg.Press. Prop. Gain 0 - 5 BLDGP_PG 0.5 72,73<br />

B.PIDBP.I Bldg.Press. Integ. Gain 0 - 2 BLDGP_IG 0.5 72,73<br />

B.PIDBP.D Bldg.Press. Deriv. Gain 0 - 5 BLDGP_DG 0.3 72,73<br />

ACT.C BLDG.PRES. ACTUATOR CFGS<br />

ACT.CBP.1 BLDG.PRES. ACT.1 CONFIGS<br />

ACT.CBP.1SN.1 BP 1 Serial Number 1 0 - 9999 BP_1_SN1 0 73,74<br />

ACT.CBP.1SN.2 BP 1 Serial Number 2 0 - 6 BP_1_SN2 0 73,74<br />

ACT.CBP.1SN.3 BP 1 Serial Number 3 0 - 9999 BP_1_SN3 0 73,74<br />

ACT.CBP.1SN.4 BP 1 Serial Number 4 0 - 254 BP_1_SN4 0 73,74<br />

ACT.CBP.1C.A.LM BP1 Cntrl Angle Lo Limit 0-90 BP1_CALM 35 73,74<br />

ACT.CBP.2 BLDG.PRES. ACT.2 CONFIGS<br />

ACT.CBP.2SN.1 BP 2 Serial Number 1 0 - 9999 BP_2_SN1 0 73,74<br />

ACT.CBP.2SN.2 BP 2 Serial Number 2 0 - 6 BP_2_SN2 0 73,74<br />

ACT.CBP.2SN.3 BP 2 Serial Number 3 0 - 9999 BP_2_SN3 0 73,74<br />

ACT.CBP.2SN.4 BP 2 Serial Number 4 0 - 254 BP_2_SN4 0 73,74<br />

ACT.CBP.2C.A.LM BP2 Cntrl Angle Lo Limit 0-90 BP2_CALM 35 73,74<br />