APPENDIX B — CCN TABLES (cont)<br />
MAINTENANCE DISPLAY TABLES (cont)<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />
PRESDUCT<br />
Static Pressure "H2O SP<br />
Supply Fan Comm<strong>and</strong>ed % % SFAN_VFD<br />
Economzr 2 Act.Curr.Pos. % ECN2RPOS<br />
Econ Comm<strong>and</strong> Position % ECN2CPOS<br />
Static Pressure Setpoint "H2O SPSP config<br />
Static Pressure Reset SPRESET forcible<br />
STAGEGAS<br />
Heating Mode………..: ascii text strings<br />
Requested Heat Stage HT_STAGE<br />
Heating Control Point HEATCPNT<br />
Staged Gas LAT Sum dF LAT_SGAS<br />
Staged Gas LAT 1 dF LAT1SGAS<br />
Staged Gas LAT 2 dF LAT2SGAS<br />
Staged Gas LAT 3 dF LAT3SGAS<br />
Staged Gas Limit Sw.Temp dF LIMSWTMP<br />
Heat PID Timer sec HTSGTIMR<br />
Staged Gas Capacity Calc % HTSGCALC<br />
Current Running Capacity % HTSG_CAP<br />
Proportional Cap. Change HTSG_P<br />
Derivative Cap. Change HTSG_D<br />
Maximum Heat Stages HTMAXSTG<br />
Hi Limit Switch Tmp Mode LIMTMODE<br />
LAT Cutoff Mode LATCMODE<br />
Capacity Clamp Mode CAPMODE<br />
STRTHOUR<br />
Compressor A1 Run Hours hours HR_A1 config<br />
Compressor A2 Run Hours hours HR_A2 config<br />
Compressor A3 Run Hours hours HR_A3 config<br />
Compressor B1 Run Hours hours HR_B1 config<br />
Compressor B2 Run Hours hours HR_B2 config<br />
Compressor B3 Run Hours hours HR_B3 config<br />
Compressor A1 <strong>Start</strong>s CY_A1 config<br />
Compressor A2 <strong>Start</strong>s CY_A2 config<br />
Compressor A3 <strong>Start</strong>s CY_A3 config<br />
Compressor B1 <strong>Start</strong>s CY_B1 config<br />
Compressor B2 <strong>Start</strong>s CY_B2 config<br />
Compressor B3 <strong>Start</strong>s CY_B3 config<br />
SUMZ<br />
Cooling Control Point dF COOLCPNT<br />
Mixed Air Temperature dF MAT<br />
Evaporator Discharge Tmp dF EDT<br />
Return Air Temperature dF RAT forcible<br />
Outside Air Temperature dF OAT forcible<br />
Economizer Act.Curr.Pos. % ECONOPOS<br />
Economzr 2 Act.Curr.Pos. % ECON2POS<br />
Capacity Threshold Adjst Z_GAIN config<br />
Capacity Load Factor SMZ<br />
Next Stage EDT Decrease ADDRISE<br />
Next Stage EDT Increase SUBRISE<br />
Rise Per Percent Capacity RISE_PCT<br />
Cap Deadb<strong>and</strong> Subtracting Y_MINUS<br />
Cap Deadb<strong>and</strong> Adding Y_PLUS<br />
Cap Threshold Subtracting Z_MINUS<br />
Cap Threshold Adding Z_PLUS<br />
High Temp Cap Override On/Off HI_TEMP<br />
Low Temp Cap Override On/Off LOW_TEMP<br />
Pull Down Cap Override On/Off PULLDOWN<br />
Slow Change Cap Override On/Off SLO_CHNG<br />
SYSTEM<br />
Reset All Current Alarms Yes/No ALRESET config<br />
Reset Alarm History Yes/No ALHISCLR config<br />
Reset the Device Yes/No RESETDEV config<br />
Local Machine Disable Yes/No UNITSTOP config<br />
Soft Stop Request Yes/No SOFTSTOP forcible<br />
Emergency Stop Enable/Disable EMSTOP forcible<br />
CEM AN4 10K temp J5, 7-8 CEM10K1 forcible<br />
CEM AN5 10K temp J5, 9-10 CEM10K2 forcible<br />
CEM AN6 10K temp J5, 11-12 CEM10K3 forcible<br />
CEM AN1 10K temp J5, 1-2 CEM10K4 forcible<br />
CEM AN4 4-20 ma J5, 7-8 CEM4201 forcible<br />
CEM AN5 4-20 ma J5, 9-10 CEM4202 forcible<br />
CEM AN6 4-20 ma J5, 11-12 CEM4203 forcible<br />
CEM AN1 4-20 ma J5, 1-2 CEM4204 forcible<br />
190