• D.V.CF = 1 — Reheat follows a dehumidification heat<br />
set point (D.V.HT).<br />
Vent Reheat RAT Offset (D.V.RA) — Set point offset used<br />
only during the vent mode. The air will be reheated to returnair<br />
temperature less this offset.<br />
Vent Reheat Set Point (D.V.HT) — Set point used only during<br />
the vent mode. The air will be reheated to this set point.<br />
Dehumidify Cool Set Point (D.C.SP) — This is the dehumidification<br />
cooling set point.<br />
Dehumidity RH Set Point (D.RH.S) — This is the dehumidification<br />
relative humidity trip point.<br />
OPERATION — Dehumidification <strong>and</strong> reheat can only occur<br />
if the unit is equipped with either staged gas or hydronic heat.<br />
Dehumidification without reheat can be done on any unit but<br />
ConfigurationDEHUD.SEL must be set to 2.<br />
If the machine’s control type is a TSTAT type (ConfigurationUNITC.TYP=3)<br />
<strong>and</strong> the discrete input selection for<br />
the sensor is not configured (D.SEN not equal to 3), dehumidification<br />
will be disabled.<br />
If the machine’s control type is a TSTAT type (ConfigurationUNITC.TYP=3)<br />
<strong>and</strong> the economizer is able to provide<br />
cooling, a dehumidification mode may be called out, but<br />
the control will not request mechanical cooling.<br />
NOTE: Configuring ConfigurationDEHUD.SEN to 1,2<br />
or 3 will enable the CEM board along with the sensor selected<br />
for control.<br />
NOTE: If ConfigurationDEHUD.SEL = 1 or 2, then<br />
either staged gas or hot water valve control will be automatically<br />
enabled (ConfigurationHEATHT.CF will be set to<br />
either 3 or 4).<br />
If a tempering, unoccupied or “mechanical cooling locked<br />
out” HVAC mode is present, dehumidification will be disabled.<br />
An HVAC: Off, Vent or Cool mode must be in effect to launch<br />
either a Reheat or Dehumidification mode.<br />
If an associated sensor responsible for dehumidification<br />
fails, dehumidification will not be attempted (SPRH, RARH).<br />
Initiating a Reheat or Dehumidification Mode — To call out<br />
a Reheat mode in the Vent or the Off HVAC mode, or to call<br />
out a Dehumidification mode in a Cool HVAC mode, one of<br />
the following conditions must be true:<br />
• The space is occupied <strong>and</strong> the humidity is greater than<br />
the relative humidity trip point (D.RH.S).<br />
• The space is occupied <strong>and</strong> the discrete humidity input is<br />
closed.<br />
Dehumidification <strong>and</strong> Reheat Control — If a dehumidification<br />
mode is initiated, the rooftop will attempt to lower<br />
humidity as follows:<br />
• Economizer Cooling — The economizer, if allowed to<br />
perform free cooling, will have its control point (Run<br />
StatusVIEWEC.C.P) set to ConfigurationDEHU<br />
D.C.SP. If ConfigurationDEHUD.EC.D is disabled,<br />
the economizer will always be disabled during<br />
dehumidification.<br />
• Cooling — For all cooling control types: A High Cool<br />
HVAC mode will be requested internally to the control to<br />
Table 60 — Dehumidification Configuration<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
DEHU DEHUMIDIFICATION CONFIG.<br />
D.SEL Dehumidification Config 0-4 DHSELECT 0<br />
D.SEN Dehumidification Sensor 1-3 DHSENSOR 1<br />
D.EC.D Econ disable in DH mode? Yes/No DHECDISA Yes<br />
D.V.CF Vent Reheat Setpt Select 0-1 DHVHTCFG 0<br />
D.V.RA Vent Reheat RAT offset 0-8 deltaF DHVRAOFF 0<br />
D.V.HT Vent Reheat Setpoint 55-95 dF DHVHT_SP 70<br />
D.C.SP Dehumidify Cool Setpoint 40-55 dF DHCOOLSP 45<br />
D.RH.S Dehumidify RH Setpoint 10-90 % DHRELHSP 55<br />
HZ.RT Humidi-Mizer Adjust Rate 5-120 sec HMZRRATE 30<br />
HZ.PG Humidi-Mizer Prop. Gain 0-10 HMZR_PG 0.8<br />
80<br />
•<br />
maintain diagnostics, although the end user will see a<br />
Dehumidification mode at the display. In addition, for<br />
multi-stage cooling units the cooling control point will<br />
be set to ConfigurationDEHUD.C.SP (no SASP<br />
reset is applied).<br />
Reheat When Cooling Dem<strong>and</strong> is Present — For reheat<br />
control during dehumidification: If reheat follows an<br />
offset subtracted from return-air temperature (ConfigurationDEHUD.SEL<br />
= 2), then no heating will be<br />
initiated <strong>and</strong> the alarm relay will be energized. If<br />
ConfigurationDEHUD.SEL = 1 <strong>and</strong> ConfigurationHEATHT.CF<br />
= staged gas or hot water valve,<br />
then the selected heating control type will operate in the<br />
low heat/modulating mode.<br />
• The heating control point will be whatever the actual<br />
cooling set point would have been (without any supply<br />
air reset applied).<br />
• Reheat During Vent Mode — If configured (ConfigurationDEHUD.V.CF<br />
= 0), the heating control point<br />
will be equal to RAT - D.V.RA. If configured (ConfigurationDEHUD.V.CF=1),<br />
the heating control point<br />
will be equal to the D.V.HT set point.<br />
Ending Dehumidification <strong>and</strong> Reheat Control — When either<br />
the humidity sensor fall 5% below the set point (ConfigurationDEHUD.RH.S)<br />
or the discrete input reads<br />
“LOW”, the Dehumidification mode will end.<br />
Humidi-MiZer ® Adaptive Dehumidification<br />
System — Units with the factory-equipped Humidi-MiZer<br />
option are capable of providing multiple modes of improved<br />
dehumidification as a variation of the normal cooling cycle.<br />
The design of the Humidi-MiZer system allows for two humidity<br />
control modes of operation of the rooftop unit, utilizing a<br />
common subcooling/reheat dehumidification coil located<br />
downstream of the st<strong>and</strong>ard evaporator coil. This allows the<br />
rooftop unit to operate in both a Dehumidification (Subcooling)<br />
mode <strong>and</strong> a hot gas Reheat Mode for maximum system<br />
flexibility. The Humidi-MiZer package is factory installed <strong>and</strong><br />
will operate whenever there is a dehumidification requirement<br />
present. The Humidi-MiZer system is initiated based on input<br />
from a factory installed return air humidity sensor to the large<br />
rooftop unit controller. Additionally, the unit controller may receive<br />
an input from a space humidity sensor, a discrete input<br />
from a mechanical humidistat, or third-party controller. Dehumidification<br />
<strong>and</strong> reheat control are allowed during Cooling <strong>and</strong><br />
Vent modes in the occupied period.<br />
SET UP THE SYSTEM — The settings for Humidi-MiZer<br />
system can be found at the local display at ConfigurationDEHU.<br />
See Table 60.<br />
Dehumidification Configuration (D.SEL) — The dehumidification<br />
configuration for Humidi-MiZer is D.SEL = 4 (DH –<br />
HUMDZR).<br />
Dehumidification Sensor (D.SEN) — The sensor can be configured<br />
for the following settings:<br />
• D.SEN = 1 — Initiated by return air relative humidity<br />
sensor.<br />
• D.SEN = 2— Initiated by space relative humidity sensor.<br />
• D.SEN = 3 — Initiated by discrete input.