CONTROLS SET POINT AND CONFIGURATION LOG (cont)<br />

ITEM EXPANSION RANGE DEFAULT SETTING<br />

S.VFD SUPPLY FAN VFD CONFIG<br />

N.VLT VFD1 Nominal Motor Volts 0 - 999 VOLTS 460<br />

N.AMP VFD1 Nominal Motor Amps 0 - 999 AMPS 55<br />

N.FRQ VFD1 Nominal Motor Freq 10 - 500 60<br />

N.RPM VFD1 Nominal Motor RPM 50 - 30000 1750<br />

N.PWR VFD1 Nominal Motor HPwr 0 - 500 40<br />

M.DIR VFD1 Motor Direction 0 - 1 (multi-text strings) 0<br />

ACCL VFD1 Acceleration Time 0 - 1800 sec 30<br />

DECL VFD1 Deceleration Time 0 - 1800 sec 30<br />

SW.FQ VFD1 Switching Frequency 0 - 3 (multi-text strings) 2<br />

TYPE VFD1 Type 0 - 1 (multi-text strings) 0<br />

E.VFD EXHAUST FAN VFD CONFIG<br />

N.VLT VFD2 Nominal Motor Volts 0 - 999 VOLTS 460<br />

N.AMP VFD2 Nominal Motor Amps 0 - 999 AMPS 55<br />

N.FRQ VFD2 Nominal Motor Freq 10 - 500 60<br />

N.RPM VFD2 Nominal Motor RPM 50 - 30000 1750<br />

N.PWR VFD2 Nominal Motor HPwr 0 - 500 40<br />

M.DIR VFD2 Motor Direction 0 - 1 (multi-text strings) 0<br />

ACCL VFD2 Acceleration Time 0 - 1800 sec 30<br />

DECL VFD2 Deceleration Time 0 - 1800 sec 30<br />

SW.FQ VFD2 Switching Frequency 0 - 3 (multi-text strings) 2<br />

TYPE VFD2 Type 0 - 1 (multi-text strings) 0<br />