APPENDIX A — LOCAL DISPLAY TABLES (cont)<br />

MODE — SERVICE TEST<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.<br />

TEST <strong>Service</strong> Test Mode ON/OFF MAN_CTRL 35,36<br />

STOP Local Machine Disable YES/NO UNITSTOP config 35,36<br />

S.STP Soft Stop Request YES/NO SOFTSTOP forcible 35,36<br />

FAN.F Supply Fan Request YES/NO SFANFORC forcible 35,36<br />

INDP TEST INDEPENDENT OUTPUTS<br />

HUM.R Humidifier Relay ON/OFF HUMR_TST 36<br />

ALRM Remote Alarm / Aux Relay ON/OFF ALRM_TST 36<br />

FANS TEST FANS<br />

F.MOD Fan Test Automatic? YES/NO FANAUTO 35,36<br />

E.POS Econo Damper Comm<strong>and</strong> Pos % ECONFANS 36<br />

S.FAN Supply Fan Relay ON/OFF SFAN_TST 36<br />

S.VFD Supply Fan VFD Speed 0-100 % SFVFDTST 36<br />

P.E.1 Power Exhaust Relay 1 ON/OFF PE1_TST 36<br />

E.VFD Exhaust Fan VFD Speed 0-100 % EFVFDTST 36<br />

P.E.2 Power Exhaust Relay 2 ON/OFF PE2_TST 36<br />

BP1.C BP 1 Comm<strong>and</strong> Position 0-100 % BLDPTST1 36<br />

BP2.C BP 2 Comm<strong>and</strong> Position 0-100 % BLDPTST2 36<br />

CDF.1 Condenser Fan Output 1 ON/OFF CDF1_TST 36<br />

CDF.2 Condenser Fan Output 2 ON/OFF CDF2_TST 36<br />

CDF.3 Condenser Fan Output 3 ON/OFF CDF3_TST 36<br />

CDF.4 Condenser Fan Output 4 ON/OFF CDF4_TST 36<br />

AC.T.C CALIBRATE TEST-ACTUATORS<br />

ECN.C Economizer Act.Cmd.Pos. 0-100 % ECONOTST 36<br />

EC.CL Economizer Calibrate Cmd YES/NO ECONOCAL 36<br />

ECN.A Econ Act. Control Angle read only ECONCANG 36<br />

EC2.C Economzr 2 Act.Cmd.Pos. 0-100 % ECON2TST 36<br />

E2.CL Economzr 2 Calibrate Cmd YES/NO ECON2CAL 36<br />

EC2.A Econ2 Act. Control Angle read only ECN2CANG 36<br />

BP1.C BP 1 Comm<strong>and</strong> Position 0-100 % BLDG1TST 36<br />

B1.CL BP 1 Actuator Cal Cmd YES/NO BLDG1CAL 36<br />

BP1.A BP Act.1 Control Angle read only BP1_CANG 36<br />

BP1.M BP 1 Actuator Max Pos. 0-100 % BP1SETMX 36<br />

BP2.C BP 2 Comm<strong>and</strong> Position 0-100 % BLDG2TST 36<br />

B2.CL BP 2 Actuator Cal Cmd YES/NO BLDG2CAL 36<br />

BP2.A BP Act.2 Control Angle read only BP2_CANG 36<br />

BP2.M BP 2 Actuator Max Pos. 0-100 % BP2SETMX 36<br />

HTC.C Ht.Coil Comm<strong>and</strong> Position 0-100 % HTCLACTC 36<br />

HT.CL Heating Coil Act. Cal.Cmd YES/NO HCOILCAL 36<br />

HTC.A Heat Coil Act.Ctl.Angle read only HTCLCANG 36<br />

HMD.C Humidifier Comm<strong>and</strong> Pos. 0-100 % HUMD_TST 36<br />

HM.CL Humidifier Act. Cal.Cmd YES/NO HUMIDCAL 36<br />

HMD.A Humidifier Act.Ctrl.Ang. read only HUMDCANG 36<br />

HMZR TEST HUMIDIMIZER<br />

RHV HumidiMizer 3-way Valve Off/On RHVH_TST 36,37<br />

C.EXV Condenser EXV Position 0 to 100 % CEXVHTST 36,37<br />

B.EXV Bypass EXV Position 0 to 100 % BEXVHTST 36,37<br />

C.CAL Condenser EXV Calibrate Off/On CEXV_CAL 36,37<br />

B.CAL Bypass EXV Calibrate Off/On BEXV_CAL 36,37<br />

COOL TEST COOLING<br />

E.POS Econo Damper Comm<strong>and</strong> Pos 0-100 % ECONCOOL 36,37<br />

SP.SP Static Pressure Setpoint 0-5 "H2O SPSP_TST 36,37<br />

CL.ST Requested Cool Stage 0-n CLST_TST 36,37<br />

MLV Minimum Load Valve Relay ON/OFF MLV_TST 36<br />

A1 Compressor A1 Relay ON/OFF CMPA1TST 36<br />

A1.CP Compressor A1 Capacity 20-100 A1CAPTST 36<br />

A1.B1 Two Circuit <strong>Start</strong> A1,B1 ON/OFF CMPABTST 36<br />

A2 Compressor A2 Relay ON/OFF CMPA2TST 36<br />

A3 Compressor A3 Relay ON/OFF CMPA3TST 36<br />

B1 Compressor B1 Relay ON/OFF CMPB1TST 36<br />

B2 Compressor B2 Relay ON/OFF CMPB2TST 36<br />

B3 Compressor B3 Relay ON/OFF CMPB3TST 36<br />

RHV HumidiMizer 3-way Valve Off/On RHVH_TST 36-38<br />

C.EXV Condenser EXV Position 0 to 100 % CEXVHTST 36-38<br />

B.EXV Bypass EXV Position 0 to 100 % BEXVHTST 36-38<br />

HEAT TEST HEATING<br />

HT.ST Requested Heat Stage 0-n HTST_TST 36,38<br />

HT.1 Heat Relay 1 ON/OFF HS1_TST 36,38<br />

HT.2 Heat Relay 2 ON/OFF HS2_TST 36,38<br />

HT.3 Relay 3 W1 Gas Valve 2 ON/OFF HS3_TST 36,38<br />

HT.4 Relay 4 W2 Gas Valve 2 ON/OFF HS4_TST 36,38<br />

HT.5 Relay 5 W1 Gas Valve 3 ON/OFF HS5_TST 36,38<br />

HT.6 Relay 6 W2 Gas Valve 3 ON/OFF HS6_TST 36,38<br />

H.I.R Heat Interlock Relay ON/OFF HIR_TST 36,38<br />

HTC.C Ht.Coil Comm<strong>and</strong> Position 0-100 % HTCLHEAT 36,38<br />

167