ADAPTIVE CV STAGING SEQUENCE<br />
(Sizes 030,035)<br />
*Minimum load valve.<br />
VAV (WITH DIGITAL COMPRESSOR) STAGING<br />
SEQUENCE (Sizes 030,035)<br />
*On units with optional digital scroll compressor, compressor A1<br />
modulates from minimum to maximum capacity to provide increased<br />
stages.<br />
VAV AND ADAPTIVE CV STAGING SEQUENCE<br />
WITH MINIMUM LOAD VALVE (Size 040)<br />
*Minimum load valve.<br />
APPENDIX B — CCN TABLES (cont)<br />
TIME SCHEDULE CONFIG TABLE<br />
Allowable Entries: Day not selected = 0 Day selected = 1<br />
DAY FLAGS<br />
MTWTFSSH<br />
APPENDIX C — UNIT STAGING TABLES<br />
192<br />
OCCUPIED<br />
TIME<br />
VAV DIGITAL COMPRESSOR STAGING<br />
SEQUENCE (Size 040)<br />
*On units with optional digital scroll compressor, compressor A1<br />
modulates from minimum to maximum capacity to provide increased<br />
stages.<br />
VAV AND ADAPTIVE CV STAGING SEQUENCE<br />
WITHOUT MINIMUM LOAD VALVE (Size 040)<br />
STAGE<br />
0 1<br />
SEQUENCE<br />
2 3 4<br />
COMP Compressor Status<br />
A1 OFF OFF ON ON ON<br />
B1 OFF ON OFF ON ON<br />
B2 OFF OFF OFF OFF ON<br />
UNIT Capacity 48/50P<br />
040 0% 27% 47% 73% 100%<br />
VAV AND ADAPTIVE CV STAGING<br />
SEQUENCE (Sizes 050-075)<br />
*Minimum load valve.<br />
UNOCCUPIED<br />
TIME<br />
Period 1: 00000000 00:00 00:00<br />
Period 2: 00000000 00:00 00:00<br />
Period 3: 00000000 00:00 00:00<br />
Period 4: 00000000 00:00 00:00<br />
Period 5: 00000000 00:00 00:00<br />
Period 6: 00000000 00:00 00:00<br />
Period 7: 00000000 00:00 00:00<br />
Period 8: 00000000 00:00 00:00<br />
STAGE<br />
0 1*<br />
SEQUENCE<br />
1 2<br />
COMP Compressor Status<br />
A1 OFF ON ON ON<br />
B1 OFF OFF OFF ON<br />
UNIT Capacity 48/50P<br />
030 0% 36% 50% 100%<br />
035 0% 38% 50% 100%<br />
STAGE<br />
0<br />
SEQUENCE<br />
1 2<br />
COMP Compressor Status<br />
A1* OFF ON ON<br />
B1 OFF OFF ON<br />
UNIT Capacity 48/50P<br />
030 0% 25% to 50% 75% to 100%<br />
035 0% 25% to 50% 75% to 100%<br />
STAGE<br />
0 1*<br />
SEQUENCE<br />
1 2 3<br />
COMP Compressor Status<br />
A1 OFF ON ON ON ON<br />
B1 OFF OFF OFF ON ON<br />
B2 OFF OFF OFF OFF ON<br />
UNIT Capacity 48/50P<br />
040 0% 36% 47% 73% 100%<br />
STAGE<br />
0 1<br />
SEQUENCE<br />
2 3<br />
COMP Compressor Status<br />
A1* OFF ON ON ON<br />
B1 OFF OFF ON ON<br />
B2 OFF OFF OFF ON<br />
UNIT Capacity 48/50P<br />
040 0% 23% to 47% 50% to 73%<br />
77% to<br />
100%<br />
STAGE<br />
0 1*<br />
SEQUENCE<br />
1 2 3 4<br />
COMP Compressor Status<br />
A1 OFF ON ON ON ON ON<br />
A2 OFF OFF OFF OFF ON ON<br />
B1 OFF OFF OFF ON ON ON<br />
B2 OFF OFF OFF OFF OFF ON<br />
UNIT Capacity 48/50P<br />
050 0% 15% 23% 50% 73% 100%<br />
055 0% 17% 25% 50% 75% 100%<br />
060 0% 18% 25% 50% 75% 100%<br />
070 0% 16% 23% 46% 73% 100%<br />
075 0% 19% 25% 50% 75% 100%