High SST Alert Delay Time (H.SST) — This option allows<br />
the low saturated suction temperature alert timing delay to be<br />
adjusted.<br />
Reverse Rotation Verified? (RR.VF) — This configuration is<br />
used to enable or disable the compressor reverse rotation detection<br />
algorithm. This algorithm performs a check for correct<br />
compressor rotation upon power up of the unit. The method for<br />
detecting correct rotation is based on the assumption that there<br />
will be a drop in suction pressure upon a compressor start if it is<br />
rotating in the correct direction.<br />
A test is made once, on power up, for suction pressure<br />
change on the first compressor of the first circuit to start.<br />
Reverse rotation is determined by measuring suction pressure<br />
at 3 points in time:<br />
• 5 seconds prior to compressor start.<br />
Table 33 — Setpoints<br />
Table 34 — Supply Air Reset Configuration<br />
Table 35 — Cooling Configuration<br />
47<br />
• At the instant the compressor starts.<br />
• 5 seconds after the compressor starts.<br />
The rate of suction pressure change from 5 seconds prior to<br />
compressor start to compressor start (rate prior) is compared to<br />
the rate of suction pressure change from compressor start to 5<br />
seconds after compressor start (rate after).<br />
If (rate after) is less than (rate prior minus 1.25), alarm A140<br />
is generated. This alarm will disable mechanical cooling <strong>and</strong><br />
will require a manual reset.<br />
It is important to note that in <strong>Service</strong> Test mode reverse rotation<br />
is checked on every compressor start.<br />
Once it has been verified that power to the unit <strong>and</strong> compressors<br />
has been applied correctly <strong>and</strong> the compressors start<br />
up normally, this configuration can be set to YES to disable the<br />
reverse rotation check.<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
OHSP Occupied Heat Setpoint 40-99 dF OHSP 68<br />
OCSP Occupied Cool Setpoint 40-99 dF OCSP 75<br />
UHSP Unoccupied Heat Setpoint 40-99 dF UHSP 55<br />
UCSP Unoccupied Cool Setpoint 40-110 dF UCSP 90<br />
GAP Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5<br />
V.C.ON VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5<br />
V.C.OF VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2<br />
SASP Supply Air Setpoint 45-75 dF SASP 55<br />
SA.HI Supply Air Setpoint Hi 45-75 dF SASP_HI 55<br />
SA.LO Supply Air Setpoint Lo 45-75 dF SASP_LO 60<br />
SA.HT Heating Supply Air Setpt 90-145 dF SASPHEAT 85<br />
T.PRG Tempering Purge SASP –20-80 dF TEMPPURG 50<br />
T.CL Tempering in Cool SASP 5-75 dF TEMPCOOL 5<br />
T.V.OC Tempering Vent Occ SASP –20-80 dF TEMPVOCC 65<br />
T.V.UN Tempering Vent Unocc. SASP –20-80 dF TEMPVUNC 50<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
EDT.R EVAP.DISCHRGE TEMP RESET<br />
RS.CF EDT Reset Configuration 0 - 3 EDRSTCFG 2<br />
RTIO Reset Ratio 0 - 10 RTIO 3<br />
LIMT Reset Limit 0 - 20 deltaF LIMT 10<br />
RES.S EDT 4-20 ma Reset Input Enable/Disable EDTRSENS Disable<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
COOL COOLING CONFIGURATION<br />
A1.EN Enable Compressor A1 Enable/Disable CMPA1ENA Enable<br />
A2.EN Enable Compressor A2 Enable/Disable CMPA2ENA Enable<br />
A3.EN Enable Compressor A3 Enable/Disable CMPA3ENA Enable<br />
B1.EN Enable Compressor B1 Enable/Disable CMPB1ENA Enable<br />
B2.EN Enable Compressor B2 Enable/Disable CMPB2ENA Enable<br />
B3.EN Enable Compressor B3 Enable/Disable CMPB3ENA Enable<br />
CS.A1 CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable<br />
CS.A2 CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable<br />
CS.A3 CSB A3 Feedback Alarm Enable/Disable CSB_A3EN Enable<br />
CS.B1 CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable<br />
CS.B2 CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable<br />
CS.B3 CSB B3 Feedback Alarm Enable/Disable CSB_B3EN Enable<br />
Z.GN Capacity Threshold Adjst 0.1 - 10.0 Z_GAIN 1<br />
MC.LO Compressor Lockout Temp –25 - 55 dF OATLCOMP 40<br />
LLAG Lead/Lag <strong>Operation</strong> ? Yes/No LLENABLE No<br />
M.M. Motor Master Control ? Yes/No MOTRMAST No<br />
SCT.H Maximum Condenser Temp 100 - 150 dF SCT_MAX 115<br />
SCT.L Minimum Condenser Temp 40 - 90 dF SCT_MIN 72<br />
DG.A1 A1 is Digital Scroll Yes/No DIGCMPA1 No<br />
MC.A1 A1 Min Digital Capacity 10 - 100 % MINCAPA1 50<br />
DS.AP Dig Scroll Adjust Delta 0 -100 % DSADJPCT 100<br />
DS.AD Dig Scroll Adjust Delay 15 - 60 sec DSADJDLY 20<br />
DS.RP Dig Scroll Reduce Delta 0 -100 % DSREDPCT 6<br />
DS.RD Dig Scroll Reduce Delay 15 - 60 sec DSREDDLY 30<br />
DS.RO Dig Scroll Reduction OAT 70-120 dF DSREDOAT 95<br />
DS.MO Dig Scroll Max Only OAT 70-120 dF DSMAXOAT 105<br />
MLV Min Load Valve Enable Enable/Disable MLV_ENAB Disable<br />
H.SST Hi SST Alert Delay Time 5 - 30 min HSSTTIME 10<br />
RR.VF Rev Rotation Verified? Yes/No REVR_VER No<br />
CS.HP Use CSBs for HPS Detect? Yes/No CSBHPDET Yes