High SST Alert Delay Time (H.SST) — This option allows<br />

the low saturated suction temperature alert timing delay to be<br />

adjusted.<br />

Reverse Rotation Verified? (RR.VF) — This configuration is<br />

used to enable or disable the compressor reverse rotation detection<br />

algorithm. This algorithm performs a check for correct<br />

compressor rotation upon power up of the unit. The method for<br />

detecting correct rotation is based on the assumption that there<br />

will be a drop in suction pressure upon a compressor start if it is<br />

rotating in the correct direction.<br />

A test is made once, on power up, for suction pressure<br />

change on the first compressor of the first circuit to start.<br />

Reverse rotation is determined by measuring suction pressure<br />

at 3 points in time:<br />

• 5 seconds prior to compressor start.<br />

Table 33 — Setpoints<br />

Table 34 — Supply Air Reset Configuration<br />

Table 35 — Cooling Configuration<br />

47<br />

• At the instant the compressor starts.<br />

• 5 seconds after the compressor starts.<br />

The rate of suction pressure change from 5 seconds prior to<br />

compressor start to compressor start (rate prior) is compared to<br />

the rate of suction pressure change from compressor start to 5<br />

seconds after compressor start (rate after).<br />

If (rate after) is less than (rate prior minus 1.25), alarm A140<br />

is generated. This alarm will disable mechanical cooling <strong>and</strong><br />

will require a manual reset.<br />

It is important to note that in <strong>Service</strong> Test mode reverse rotation<br />

is checked on every compressor start.<br />

Once it has been verified that power to the unit <strong>and</strong> compressors<br />

has been applied correctly <strong>and</strong> the compressors start<br />

up normally, this configuration can be set to YES to disable the<br />

reverse rotation check.<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

OHSP Occupied Heat Setpoint 40-99 dF OHSP 68<br />

OCSP Occupied Cool Setpoint 40-99 dF OCSP 75<br />

UHSP Unoccupied Heat Setpoint 40-99 dF UHSP 55<br />

UCSP Unoccupied Cool Setpoint 40-110 dF UCSP 90<br />

GAP Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5<br />

V.C.ON VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5<br />

V.C.OF VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2<br />

SASP Supply Air Setpoint 45-75 dF SASP 55<br />

SA.HI Supply Air Setpoint Hi 45-75 dF SASP_HI 55<br />

SA.LO Supply Air Setpoint Lo 45-75 dF SASP_LO 60<br />

SA.HT Heating Supply Air Setpt 90-145 dF SASPHEAT 85<br />

T.PRG Tempering Purge SASP –20-80 dF TEMPPURG 50<br />

T.CL Tempering in Cool SASP 5-75 dF TEMPCOOL 5<br />

T.V.OC Tempering Vent Occ SASP –20-80 dF TEMPVOCC 65<br />

T.V.UN Tempering Vent Unocc. SASP –20-80 dF TEMPVUNC 50<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

EDT.R EVAP.DISCHRGE TEMP RESET<br />

RS.CF EDT Reset Configuration 0 - 3 EDRSTCFG 2<br />

RTIO Reset Ratio 0 - 10 RTIO 3<br />

LIMT Reset Limit 0 - 20 deltaF LIMT 10<br />

RES.S EDT 4-20 ma Reset Input Enable/Disable EDTRSENS Disable<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

COOL COOLING CONFIGURATION<br />

A1.EN Enable Compressor A1 Enable/Disable CMPA1ENA Enable<br />

A2.EN Enable Compressor A2 Enable/Disable CMPA2ENA Enable<br />

A3.EN Enable Compressor A3 Enable/Disable CMPA3ENA Enable<br />

B1.EN Enable Compressor B1 Enable/Disable CMPB1ENA Enable<br />

B2.EN Enable Compressor B2 Enable/Disable CMPB2ENA Enable<br />

B3.EN Enable Compressor B3 Enable/Disable CMPB3ENA Enable<br />

CS.A1 CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Enable<br />

CS.A2 CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Enable<br />

CS.A3 CSB A3 Feedback Alarm Enable/Disable CSB_A3EN Enable<br />

CS.B1 CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Enable<br />

CS.B2 CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Enable<br />

CS.B3 CSB B3 Feedback Alarm Enable/Disable CSB_B3EN Enable<br />

Z.GN Capacity Threshold Adjst 0.1 - 10.0 Z_GAIN 1<br />

MC.LO Compressor Lockout Temp –25 - 55 dF OATLCOMP 40<br />

LLAG Lead/Lag <strong>Operation</strong> ? Yes/No LLENABLE No<br />

M.M. Motor Master Control ? Yes/No MOTRMAST No<br />

SCT.H Maximum Condenser Temp 100 - 150 dF SCT_MAX 115<br />

SCT.L Minimum Condenser Temp 40 - 90 dF SCT_MIN 72<br />

DG.A1 A1 is Digital Scroll Yes/No DIGCMPA1 No<br />

MC.A1 A1 Min Digital Capacity 10 - 100 % MINCAPA1 50<br />

DS.AP Dig Scroll Adjust Delta 0 -100 % DSADJPCT 100<br />

DS.AD Dig Scroll Adjust Delay 15 - 60 sec DSADJDLY 20<br />

DS.RP Dig Scroll Reduce Delta 0 -100 % DSREDPCT 6<br />

DS.RD Dig Scroll Reduce Delay 15 - 60 sec DSREDDLY 30<br />

DS.RO Dig Scroll Reduction OAT 70-120 dF DSREDOAT 95<br />

DS.MO Dig Scroll Max Only OAT 70-120 dF DSMAXOAT 105<br />

MLV Min Load Valve Enable Enable/Disable MLV_ENAB Disable<br />

H.SST Hi SST Alert Delay Time 5 - 30 min HSSTTIME 10<br />

RR.VF Rev Rotation Verified? Yes/No REVR_VER No<br />

CS.HP Use CSBs for HPS Detect? Yes/No CSBHPDET Yes