EDT Low Alert Limit/Occ (SA.L.O) — If the space temperature<br />
is below the configurable occupied evaporator discharge<br />
temperature (EDT) Low Alert Limit (SA.L.O), then Alert 302<br />
will be generated <strong>and</strong> cooling operation will be stopped but<br />
heating operation will continue. The alert will automatically<br />
reset.<br />
EDT High Alert Limit/Occ (SA.H.O) — If the space temperature<br />
is above the configurable occupied EDT High Alert Limit<br />
(SA.H.O), then Alert 303 will be generated <strong>and</strong> heating operation<br />
will be stopped but cooling operation will continue. The<br />
alert will automatically reset.<br />
EDT Low Alert Limit/Unocc (SA.L.U) — If the space temperature<br />
is below the configurable unoccupied EDT Low Alert<br />
Limit (SA.L.U), then Alert 302 will be generated <strong>and</strong> cooling<br />
operation will be stopped but heating operation will continue.<br />
The alert will automatically reset.<br />
EDT High Alert Limit/Unocc (SA.H.U) — If the space temperature<br />
is above the configurable unoccupied EDT High Alert<br />
Limit (SA.H.U), then Alert 303 will be generated <strong>and</strong> heating<br />
operation will be stopped but cooling operation will continue.<br />
The alert will automatically reset.<br />
RAT Low Alert Limit/Occ (RA.L.O) — If the return-air temperature<br />
is below the configurable occupied RAT Low Alert<br />
Limit (RA.L.O), then Alert 304 will be generated <strong>and</strong> internal<br />
routines will be modified. Unit operation will continue but<br />
VAV heating operation will be disabled. The alert will automatically<br />
reset.<br />
RAT High Alert Limit/Occ (RA.H.O) — If the return-air<br />
temperature is above the configurable occupied RAT High<br />
Alert Limit (RA.H.O), then Alert 305 will be generated <strong>and</strong><br />
operation will continue. The alert will automatically reset.<br />
RAT Low Alert Limit/Unocc (RA.L.U) — If the return-air<br />
temperature is below the configurable unoccupied RAT Low<br />
Alert Limit (RA.L.U), then Alert 304 will be generated. Unit<br />
operation will continue but VAV heating operation will be disabled.<br />
The alert will automatically reset.<br />
RAT High Alert Limit/Unocc (RA.H.U) — If the return-air<br />
temperature is above the configurable unoccupied RAT High<br />
Alert Limit (RA.H.U), then Alert 305 will be generated. <strong>Operation</strong><br />
will continue. The alert will automatically reset.<br />
OAT Low Alert Limit (OAT.L) — If the outside-air temperature<br />
measured by the OAT thermistor is below the configurable<br />
OAT Low Alert Limit (OAT.L) then alert T316 will be<br />
generated.<br />
OAT High Alert Limit (OAT.H) — If the outside-air temperature<br />
measured by the OAT thermistor is above the configurable<br />
OAT High Alert Limit (OAT.H) then alert T317 will be<br />
generated.<br />
Table 61 — CCN Configuration<br />
84<br />
RARH Low Alert Limit (R.RH.L) — If the unit is configured<br />
to use a return air relative humidity sensor (ConfigurationUNITSENSRRH.S),<br />
<strong>and</strong> the measured level is<br />
below the configurable RH Low Alert Limit (R.RH.L), then<br />
Alert 308 will occur. The unit will continue to run <strong>and</strong> the alert<br />
will automatically reset.<br />
RARH High Alert Limit (R.RH.H) — If the unit is configured<br />
to use a return air relative humidity sensor (ConfigurationUNITSENSRRH.S),<br />
<strong>and</strong> the measured level is<br />
above the configurable RARH High Alert Limit (R.RH.H),<br />
then Alert 309 will occur. The unit will continue to run <strong>and</strong> the<br />
alert will automatically reset.<br />
OARH Low Alert Limit (O.RH.L) — If the unit is configured<br />
to use an outdoor air relative humidity sensor (ConfigurationECONORH.S)<br />
<strong>and</strong> the measured level is below the<br />
configurable OARH Low Alert Limit (O.RH.L), then economizer<br />
operation will be disabled. The unit will continue to run<br />
<strong>and</strong> the alert will automatically reset.<br />
OARH High Alert Limit (O.RH.H) — If the unit is configured<br />
to use a return air relative humidity sensor (ConfigurationECONORH.S)<br />
<strong>and</strong> the measured level is above the<br />
configurable OARH High Alert Limit (O.RH.H), then economizer<br />
operation will be disabled. The unit will continue to run<br />
<strong>and</strong> the alert will automatically reset.<br />
Supply Duct Pressure Low Alert Limit (SP.L) — If the unit<br />
is a VAV unit with a supply duct pressure sensor <strong>and</strong> the measured<br />
supply duct static pressure is below the configurable SP<br />
Low Alert Limit (DP.L), then Alert 310 will occur. The unit<br />
will continue to run <strong>and</strong> the alert will automatically reset.<br />
Supply Duct Pressure High Alert Limit (SP.H) — If the unit<br />
is a VAV unit with a supply duct pressure sensor <strong>and</strong> the measured<br />
supply duct static pressure is above the configurable SP<br />
High Alert Limit (SP.H), then Alert 311 will occur. The unit<br />
will continue to run <strong>and</strong> the alert will automatically reset.<br />
Building Pressure Low Alert Limit (BP.L) — If the unit is<br />
configured to use modulating power exhaust then a building<br />
static pressure limit can be configured using the BP Low Alert<br />
Limit (BP.L). If the measured pressure is below the limit then<br />
Alert 312 will occur.<br />
Building Pressure High Alert Limit (BP.H) — If the unit is<br />
configured to use modulating power exhaust then a building<br />
static pressure limit can be configured using the BP Hi Alert<br />
Limit (BP.H). If the measured pressure is above the limit, then<br />
Alert 313 will occur.<br />
Indoor Air Quality High Alert Limit (IAQ.H) — If the unit<br />
is configured to use a CO 2 sensor <strong>and</strong> the level is above the<br />
configurable IAQ High Alert Limit (IAQ.H) then the alert will<br />
occur. The unit will continue to run <strong>and</strong> the alert will automatically<br />
reset.<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
CCN CCN CONFIGURATION<br />
CCNA CCN Address 1 - 239 CCNADD 1<br />
CCNB CCN Bus Number 0 - 239 CCNBUS 0<br />
BAUD CCN Baud Rate 1 - 5 CCNBAUDD 3<br />
BROD CCN BROADCST DEFINITIONS<br />
TM.DT CCN Time/Date Broadcast ON/OFF CCNBC On<br />
OAT.B CCN OAT Broadcast ON/OFF OATBC Off<br />
ORH.B CCN OARH Broadcast ON/OFF OARHBC Off<br />
OAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off<br />
G.S.B Global Schedule Broadcst ON/OFF GSBC Off<br />
B.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off<br />
SC.OV CCN SCHEDULES-OVERRIDES<br />
SCH.N Schedule Number 0 - 99 SCHEDNUM 1<br />
HOL.T Accept Global Holidays? YES/NO HOLIDAYT No<br />
O.T.L. Override Time Limit 0 - 4 HRS OTL 1<br />
OV.EX Timed Override Hours 0 - 4 HRS OVR_EXT 0<br />
SPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes<br />
T58.O T58 Override Enabled ? YES/NO T58_OVER Yes<br />
GL.OV Global Sched. Override ? YES/NO GLBLOVER No