APPENDIX C — UNIT STAGING TABLES (cont)<br />

VAV (WITH DIGITAL COMPRESSOR) STAGING SEQUENCE (Sizes 050-075)<br />

STAGE<br />

0 1<br />

SEQUENCE<br />

2 3 4<br />

COMP Compressor Status<br />

A1* OFF ON ON ON ON<br />

A2 OFF OFF OFF ON ON<br />

B1 OFF OFF ON ON ON<br />

B2 OFF OFF OFF OFF ON<br />

UNIT Capacity 48/50P<br />

050 0% 12% to 23% 38% to 50% 62% to 73% 88% to 100%<br />

055 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%<br />

060 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%<br />

070 0% 11% to 23% 34% to 46% 61% to 73% 89% to 100%<br />

075 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%<br />

*On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.<br />

*Minimum load valve.<br />

VAV AND ADAPTIVE CV STAGING SEQUENCE (Sizes 090-100)<br />

STAGE<br />

0 1* 1 2<br />

SEQUENCE<br />

3 4 5 6<br />

COMP Compressor Status<br />

A1 OFF ON ON ON ON ON ON ON<br />

A2 OFF OFF OFF OFF ON ON ON ON<br />

A3 OFF OFF OFF OFF OFF OFF ON ON<br />

B1 OFF OFF OFF ON ON ON ON ON<br />

B2 OFF OFF OFF OFF OFF ON ON ON<br />

B3 OFF OFF OFF OFF OFF OFF OFF ON<br />

UNIT Capacity 48/50P<br />

090 0% 12% 17% 33% 50% 67% 83% 100%<br />

100 0% 11% 15% 33% 49% 67% 82% 100%<br />

VAV (WITH DIGITAL COMPRESSOR) STAGING SEQUENCE (Sizes 090-100)<br />

STAGE<br />

0 1 2<br />

SEQUENCE<br />

3 4 5 6<br />

COMP Compressor Status<br />

A1* OFF ON ON ON ON ON ON<br />

A2 OFF OFF OFF ON ON ON ON<br />

A3 OFF OFF OFF OFF OFF ON ON<br />

B1 OFF OFF ON ON ON ON ON<br />

B2 OFF OFF OFF OFF ON ON ON<br />

B3 OFF OFF OFF OFF OFF OFF ON<br />

UNIT Capacity 48/50P<br />

090 0% 8% to 17% 25% to 33% 42% to 50% 58% to 67% 75% to 83% 92% to 100%<br />

100 0% 8% to 15% 26% to 33% 41% to 49% 59% to 67% 74% to 82% 92% to 100%<br />

*On units with optional digital scroll compressor, compressor A1 modulates from minimum to maximum capacity to provide increased stages.<br />