Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TIME<br />
EWT<br />
LWT<br />
SETP<br />
Run Status<br />
<strong>Service</strong> Test<br />
Temperatures<br />
Pressures<br />
Setpoints<br />
Inputs<br />
Outputs<br />
Configuration<br />
Time Clock<br />
Operating Modes<br />
Alarms<br />
CARRIER COMFORT NETWORK ® INTERFACE —<br />
The 48/50P Series units can be connected to the CCN if<br />
desired. See Fig. 36. The communication bus wiring is a<br />
shielded, 3-conductor cable with drain wire <strong>and</strong> is field supplied<br />
<strong>and</strong> installed. See the Installation Instructions for wiring<br />
information.<br />
The system elements are connected to the communication<br />
bus in a daisy chain arrangement. The positive pin of each<br />
system element communication connector must be wired to the<br />
positive pins of the system elements on either side of it. This is<br />
also required for the negative <strong>and</strong> signal ground pins of each<br />
system element. Wiring connections for CCN should be made<br />
at the COMM board. See Fig. 20. Consult the CCN Contractor’s<br />
Manual for further information.<br />
NOTE: Conductors <strong>and</strong> drain wire must be 20-AWG<br />
(American Wire Gage) minimum str<strong>and</strong>ed, tinned copper.<br />
Individual conductors must be insulated with PVC, PVC/<br />
nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester<br />
100% foil shield <strong>and</strong> an outer jacket of PVC, PVC/nylon,<br />
chrome vinyl, or Teflon with a minimum operating temperature<br />
range of –20 C to 60 C is required.<br />
It is important when connecting to a CCN communication<br />
bus that a color-coding scheme be used for the entire network<br />
to simplify the installation. It is recommended that red be used<br />
for the signal positive, black for the signal negative <strong>and</strong> white<br />
for the signal ground. Use a similar scheme for cables containing<br />
different colored wires.<br />
At each system element, the shields of its communication<br />
bus cables must be tied together. If the communication bus is<br />
entirely within one building, the resulting continuous shield<br />
must be connected to a ground at one point only. If the communication<br />
bus cable exits from one building <strong>and</strong> enters another,<br />
the shields must be connected to grounds at the lightning<br />
suppressor in each building where the cable enters or exits the<br />
building (one point per building only). To connect the unit to<br />
the network:<br />
1. Turn off power to the control box.<br />
2. Cut the CCN wire <strong>and</strong> strip the ends of the red (+), white<br />
(ground), <strong>and</strong> black (–) conductors. (Substitute appropriate<br />
colors for different colored cables.)<br />
3. Connect the red wire to (+) terminal on the COMM<br />
board, the white wire to COM terminal on the COMM<br />
board, <strong>and</strong> the black wire to the (–) terminal on the<br />
COMM board.<br />
4. The RJ14 CCN connector on the COMM board can also<br />
be used, but is only intended for temporary connection<br />
(for example, a laptop computer running <strong>Service</strong> Tool).<br />
ENTER<br />
Co m f o r t Link<br />
E S C<br />
N A V I G A T O R<br />
1 2 . 5 8<br />
5 4 . 6 F<br />
4 4 .1 F<br />
4 4 . 0 F<br />
M O D E Alarm Status<br />
Fig. 35 — Accessory Navigator Display<br />
137<br />
5. Restore power to unit.<br />
IMPORTANT: A shorted CCN bus cable will prevent<br />
some routines from running <strong>and</strong> may prevent the unit<br />
from starting. If abnormal conditions occur, unplug the<br />
connector. If conditions return to normal, check the<br />
CCN connector <strong>and</strong> cable. Run new cable if necessary.<br />
A short in one section of the bus can cause problems<br />
with all system elements on the bus.<br />
SERVICE<br />
<strong>Service</strong> Access — All unit components can be reached<br />
through clearly labeled hinged access doors. These doors are<br />
not equipped with tiebacks, so if heavy duty servicing is needed,<br />
either remove them or prop them open to prevent accidental<br />
closure.<br />
Each door is held closed with 3 latches. The latches are<br />
secured to the unit with a single 1/ 4-in. –20 x 1/ 2-in. long bolt.<br />
See Fig. 37.<br />
To open, loosen the latch bolt using a 7 / 16-in. wrench. Pivot<br />
the latch so it is not in contact with the door. Open the door. To<br />
shut, reverse the above procedure.<br />
NOTE: Disassembly of the top cover may be required under<br />
special service circumstances. It is very important that the orientation<br />
<strong>and</strong> position of the top cover be marked on the unit<br />
prior to disassembly. This will allow proper replacement of the<br />
top cover onto the unit <strong>and</strong> prevent rainwater from leaking into<br />
the unit.<br />
IMPORTANT: After servicing is completed, make sure<br />
door is closed <strong>and</strong> relatched properly, <strong>and</strong> that the<br />
latches are tight. Failure to do this can result in water<br />
leakage into the indoor-air section of the unit.<br />
COMPRESSORS<br />
Sizes 030,035 — Access to the compressors is below the unitcontrol<br />
box.<br />
Sizes 040-060 — Access to the compressors is through the<br />
doors on the condenser end of the unit. This door also provides<br />
access to the discharge service valves, filter driers, the crankcase<br />
heaters, <strong>and</strong> the high-pressure <strong>and</strong> low-pressure switches.<br />
Circuit A is always the compressor on the left when facing<br />
main control box.<br />
Sizes 070-100 — Each compressor is readily accessible from<br />
sides of unit.<br />
LIQUID SERVICE VALVES, SUCTION SERVICE<br />
VALVES, AND SIGHT GLASSES<br />
Sizes 030-060 — Access to these components is through the<br />
access panel on the right side of the unit. See Fig. 38. There is<br />
also a Schrader port in each suction line that is accessible<br />
through this same panel.<br />
Sizes 070-100 — Access to these components is from the side<br />
of the unit.<br />
SUPPLY-FAN MOTORS, PULLEYS, AND BELTS — Access<br />
to these components is through the 2 doors labeled FAN<br />
SECTION on each side of the unit.<br />
POWER EXHAUST MOTORS, PULLEYS, AND BELTS —<br />
Access to these components is through the door below the side<br />
economizer hoods on both sides of the unit. See Fig. 39.<br />
RETURN AIR FILTERS — Access to these filters is through<br />
the door marked FILTER SECTION.<br />
UNIT CONTROL BOX — Access to this component is<br />
through the doors marked ELECTRICAL SECTION on the<br />
condenser end of the unit.<br />
GAS HEAT SECTION (48P Only) — Access to the gas heat<br />
section is through the door labeled HEAT SECTION on the