APPENDIX A — LOCAL DISPLAY TABLES (cont)<br />

MODE — CONFIGURATION (cont)<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.<br />

D.LV.T COOL/HEAT SETPT. OFFSETS<br />

L.H.ON Dmd Level Lo Heat On -1 - 2 ^F DMDLHON 1.5 32,47<br />

H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F DMDHHON 0.5 47<br />

L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2.0 ^F DMDLHOFF 1 32,47<br />

L.C.ON Dmd Level Lo Cool On -1 - 2 ^F DMDLCON 1.5 47<br />

H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F DMDHCON 0.5 47<br />

L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2.0 ^F DMDLCOFF 1 47<br />

C.T.LV Cool Trend Dem<strong>and</strong> Level 0.1 - 5.0 ^F CTRENDLV 0.1 47<br />

H.T.LV Heat Trend Dem<strong>and</strong> Level 0.1 - 5.0 ^F HTRENDLV 0.1 47<br />

C.T.TM Cool Trend Time 30 - 600 sec CTRENDTM 120 47<br />

H.T.TM Heat Trend Time 30 - 600 sec HTRENDTM 120 47<br />

DMD.L DEMAND LIMIT CONFIG.<br />

DM.L.S Dem<strong>and</strong> Limit Select 0 - 3 (multi-text strings) DMD_CTRL 0 38,39,43,53,<br />

57<br />

D.L.20 Dem<strong>and</strong> Limit at 20 ma 0 - 100 % DMT20MA 100 34,57<br />

SH.NM Loadshed Group Number 0 - 99 SHED_NUM 0 57<br />

SH.DL Loadshed Dem<strong>and</strong> Delta 0 - 60 % SHED_DEL 0 57<br />

SH.TM Maximum Loadshed Time 0 - 120 min SHED_TIM 60 57<br />

D.L.S1 Dem<strong>and</strong> Limit Sw.1 Setpt. 0 - 100 % DLSWSP1 80 38,57<br />

D.L.S2 Dem<strong>and</strong> Limit Sw.2 Setpt. 0 - 100 % DLSWSP2 50 39,57<br />

IAQ INDOOR AIR QUALITY CFG.<br />

DCV.C DCV ECONOMIZER SETPOINTS<br />

DCV.CEC.MN Economizer Min.Position 0 - 100 % ECONOMIN 5 35,39,77<br />

DCV.CIAQ.M IAQ Dem<strong>and</strong> Vent Min.Pos. 0 - 100 % IAQMINP 0 35,39,76,77,<br />

114<br />

DCV.CO.C.MX Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000 35,39,77<br />

DCV.CO.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM OACFMMIN 0 35,39,77<br />

DCV.CO.C.DB Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM OACFM_DB 400 35,39,77,78<br />

AQ.CF AIR QUALITY CONFIGS<br />

AQ.CFIQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) IAQANCFG 0 39,40,76,77<br />

AQ.CFIQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) IAQANFAN 0 39,77<br />

AQ.CFIQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) IAQINCFG 0 39,43,77<br />

AQ.CFIQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) IAQINFAN 0 39,76,77<br />

AQ.CFOQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) OAQANCFG 0 39,43,77<br />

AQ.SP AIR QUALITY SETPOINTS<br />

AQ.SPIQ.O.P IAQ Econo Override Pos. 0 - 100 % IAQOVPOS 100 39,77<br />

AQ.SPIQ.O.C IAQ Override Flow 0 - 31000 CFM IAQOVCFM 10000 77<br />

AQ.SPDAQ.L Diff.Air Quality LoLimit 0 - 1000 DAQ_LOW 100 77,78<br />

AQ.SPDAQ.H Diff. Air Quality HiLimit 100 - 2000 DAQ_HIGH 700 77,78<br />

AQ.SPD.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 DAQFNOFF 200 39,76,77<br />

AQ.SPD.F.ON DAQ PPM Fan On Setpoint 0 - 2000 DAQFNON 400 39,76,77<br />

AQ.SPIAQ.R Diff. AQ Responsiveness -5 - 5 IAQREACT 0 77<br />

AQ.SPOAQ.L OAQ Lockout Value 0 - 2000 OAQLOCK 0 77<br />

AQ.SPOAQ.U User Determined OAQ 0 - 5000 OAQ_USER 400 77<br />

AQ.S.R AIR QUALITY SENSOR RANGE<br />

AQ.S.RIQ.R.L IAQ Low Reference 0 - 5000 IAQREFL 0 39,77<br />

AQ.S.RIQ.R.H IAQ High Reference 0 - 5000 IAQREFH 2000 39,77<br />

AQ.S.ROQ.R.L OAQ Low Reference 0 - 5000 OAQREFL 0 77<br />

AQ.S.ROQ.R.H OAQ High Reference 0 - 5000 OAQREFH 2000 77<br />

IAQ.P IAQ PRE-OCCUPIED PURGE<br />

IAQ.PIQ.PG IAQ Purge Yes/No IAQPURGE No 77,78<br />

IAQ.PIQ.P.T IAQ Purge Duration 5 - 60 min IAQPTIME 15 77,78<br />

IAQ.PIQ.P.L IAQ Purge LoTemp Min Pos 0 - 100 % IAQPLTMP 10 77,78<br />

IAQ.PIQ.P.H IAQ Purge HiTemp Min Pos 0 - 100 % IAQPHTMP 35 77,78<br />

IAQ.PIQ.L.O IAQ Purge OAT Lockout 35 - 70 dF IAQPNTLO 50 77,78<br />

HUMD HUMIDITY CONFIGURATION<br />

HM.CF Humidifier Control Cfg. 0 - 4 HUMD_CFG 0 78,79<br />

HM.SP Humidifier Setpoint 0 - 100 % HUSP 40 78,79<br />

H.PID HUMIDIFIER PID CONFIGS<br />

H.PIDHM.TM Humidifier PID Run Rate 10 - 120 sec HUMDRATE 30 78,79<br />

H.PIDHM.P Humidifier Prop. Gain 0 - 5 HUMID_PG 1 78,79<br />

H.PIDHM.I Humidifier Integral Gain 0 - 5 HUMID_IG 0.3 78,79<br />

H.PIDHM.D Humidifier Deriv. Gain 0 - 5 HUMID_DG 0.3 78,79<br />

ACT.C HUMIDIFIER ACTUATOR CFGS<br />

ACTCSN.1 Humd Serial Number 1 0 - 9999 HUMD_SN1 0 79<br />

ACTCSN.2 Humd Serial Number 2 0 - 6 HUMD_SN2 0 79<br />

ACTCSN.3 Humd Serial Number 3 0 - 9999 HUMD_SN3 0 79<br />

ACTCSN.4 Humd Serial Number 4 0 - 254 HUMD_SN4 0 79<br />

ACTCC.A.LM Humd Ctrl Angle Lo Limit 0-90 HUMDCALM 85 79<br />

DEHU DEHUMIDIFICATION CONFIG.<br />

D.SEL Dehumidification Config 0-3(multi-text strings) DHSELECT 0 79-81<br />

D.SEN Dehumidification Sensor 1-3(multi-text strings) DHSENSOR 1 79-81<br />

D.EC.D Econ disable in DH mode? Yes/No DHECDISA Yes 79-81<br />

D.V.CF Vent Reheat Setpt Select 0-1(multi-text strings) DHVHTCFG 0 79-81<br />

D.V.RA Vent Reheat RAT offset 0-8 ^F DHVRAOFF 0 80,81<br />

D.V.HT Vent Reheat Setpoint 55-95 dF DHVHT_SP 70 80,81<br />

D.C.SP Dehumidify Cool Setpoint 40-55 dF DHCOOLSP 45 80,81<br />

D.RH.S Dehumidify RH Setpoint 10-90 % DHRELHSP 55 80,81<br />

HZ.RT Humidimizer Adjust Rate 5-120 HMZRRATE 30 80,81<br />

HZ.PG Humidimizer Prop. Gain 0-10 HMZR_PG 0.8 80,81<br />

CCN CCN CONFIGURATION<br />

CCNA CCN Address 1 - 239 CCNADD 1 83,84<br />

CCNB CCN Bus Number 0 - 239 CCNBUS 0 83,84<br />

BAUD CCN Baud Rate 1 - 5 (multi-text strings) CCNBAUDD 3 83,84<br />

BROD CCN BROADCST DEFINITIONS<br />

BRODTM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 83,84<br />

BRODOAT.B CCN OAT Broadcast ON/OFF OATBC Off 83,84<br />

BRODORH.B CCN OARH Broadcast ON/OFF OARHBC Off 83,84<br />

BRODOAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 83,84<br />

BRODG.S.B Global Schedule Broadcst ON/OFF GSBC Off 83,84<br />

BRODB.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 83,84<br />

SC.OV CCN SCHEDULES-OVERRIDES<br />

SC.OVSCH.N Schedule Number 0 - 99 SCHEDNUM 1 32,33,35,83,<br />

84<br />

SC.OVHOL.T Accept Global Holidays? YES/NO HOLIDAYT No 83,84<br />

SC.OVO.T.L. Override Time Limit 0 - 4 HRS OTL 1 83,84<br />

SC.OVOV.EX Timed Override Hours 0 - 4 HRS OVR_EXT 0 83,84<br />

SC.OVSPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes 83,84<br />

SC.OVT58.O T58 Override Enabled ? YES/NO T58_OVER Yes 83,84<br />

SC.OVGL.OV Global Sched. Override ? YES/NO GLBLOVER No 83,84<br />