06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Table 57 — Indoor Air Quality Configuration<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

DCV.C DCV ECONOMIZER SETPOINTS<br />

EC.MN Economizer Min.Position 0 - 100 % ECONOMIN 5<br />

IAQ.M IAQ Dem<strong>and</strong> Vent Min.Pos. 0 - 100 % IAQMINP 0<br />

O.C.MX Economizer Min.Flow 0 - 20000 CFM OACFMMAX 2000<br />

O.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM OACFMMIN 0<br />

O.C.DB Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM OACFM_DB 400<br />

AQ.CF AIR QUALITY CONFIGS<br />

IQ.A.C IAQ Analog Sensor Config 0 - 4 IAQANCFG 0<br />

IQ.A.F IAQ 4-20 ma Fan Config 0 - 2 IAQANFAN 0<br />

IQ.I.C IAQ Discrete Input Config 0 - 2 IAQINCFG 0<br />

IQ.I.F IAQ Disc.In. Fan Config 0 - 2 IAQINFAN 0<br />

OQ.A.C OAQ 4-20ma Sensor Config 0 - 2 OAQANCFG 0<br />

AQ.SP AIR QUALITY SETPOINTS<br />

IQ.O.P IAQ Econo Override Pos. 0 - 100 % IAQOVPOS 100<br />

IQ.O.C IAQ Override Flow 0 - 31000 CFM IAQOVCFM 10000<br />

DAQ.L Diff.Air Quality LoLimit 0 - 1000 DAQ_LOW 100<br />

DAQ.H Diff. Air Quality HiLimit 100 - 2000 DAQ_HIGH 700<br />

D.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 DAQFNOFF 200<br />

D.F.ON DAQ PPM Fan On Setpoint 0 - 2000 DAQFNON 400<br />

IAQ.R Diff. AQ Responsiveness -5 - 5 IAQREACT 0<br />

OAQ.L OAQ Lockout Value 0 - 2000 OAQLOCK 0<br />

OAQ.U User Determined OAQ 0 - 5000 OAQ_USER 400<br />

AQ.S.R AIR QUALITY SENSOR RANGE<br />

IQ.R.L IAQ Low Reference 0 - 5000 IAQREFL 0<br />

IQ.R.H IAQ High Reference 0 - 5000 IAQREFH 2000<br />

OQ.R.L OAQ Low Reference 0 - 5000 OAQREFL 0<br />

OQ.R.H OAQ High Reference 0 - 5000 OAQREFH 2000<br />

IAQ.P IAQ PRE-OCCUPIED PURGE<br />

IQ.PG IAQ Purge Yes/No IAQPURGE No<br />

IQ.P.T IAQ Purge Duration 5 - 60 min IAQPTIME 15<br />

IQ.P.L IAQ Purge LoTemp Min Pos 0 - 100 % IAQPLTMP 10<br />

IQ.P.H IAQ Purge HiTemp Min Pos 0 - 100 % IAQPHTMP 35<br />

IQ.L.O IAQ Purge OAT Lockout 35 - 70 dF IAQPNTLO 50<br />

• IQ.I.F = 1 (Fan On If Occupied) — IAQ dem<strong>and</strong> will<br />

override normal indoor fan operation <strong>and</strong> turn it on (if<br />

off) only during the occupied period (CV operation with<br />

automatic fan).<br />

• IQ.I.F = 2 (Fan On Occupied/Unoccupied) — IAQ<br />

dem<strong>and</strong> will always override normal indoor fan operation<br />

<strong>and</strong> turn it on (if off) during both the occupied <strong>and</strong><br />

unoccupied period.<br />

Economizer Min Position (ConfigurationIAQDCV.C<br />

EC.MN) — This is the fully occupied minimum economizer<br />

position.<br />

IAQ Dem<strong>and</strong> Vent Min Pos. (ConfigurationIAQ<br />

DCV.CIAQ.M) — This configuration will be used to set the<br />

minimum damper position in the occupied period when there<br />

is no IAQ dem<strong>and</strong>.<br />

IAQ Econo Override Pos (ConfigurationIAQAQ.SP<br />

IQ.O.P) — This configuration is the position that the economizer<br />

goes to when override is in effect.<br />

OAQ 4-20 mA Sensor Config (ConfigurationIAQ<br />

AQ.CFOQ.A.C) — This is used to configure the type of<br />

outdoor sensor that will be used for OAQ levels. It has the following<br />

configuration options:<br />

• OQ.A.C = 0 (No Sensor) — No sensor will be used <strong>and</strong><br />

the internal software reference setting will be used.<br />

• OQ.A.C = 1 (OAQ Sensor with DAQ) — An outdoor<br />

CO 2 sensor will be used.<br />

• OQ.A.C = 2 (4 to 20 mA Sensor without DAQ).<br />

OAQ Lockout Value (ConfigurationIAQAQ.SP<br />

OAQ.L) — This is the maximum OAQ level above which dem<strong>and</strong><br />

ventilation will be disabled.<br />

Diff. Air Quality Lo Limit (ConfigurationIAQAQ.SP<br />

DAQ.L) — This is the differential CO 2 level at which IAQ<br />

control of the dampers will be initiated.<br />

Diff. Air Quality Hi Limit (ConfigurationIAQAQ.SP<br />

DAQ.H) — This is the differential CO 2 level at which IAQ<br />

control of the dampers will be at maximum <strong>and</strong> the dampers<br />

will be at the Configuration IAQDCV.CEC.MN.<br />

77<br />

DAQ ppm Fan On Set Point (Configuration<br />

IAQAQ.SPD.F.ON) — This is the CO 2 level at which<br />

the indoor fan will be turned on.<br />

DAQ ppm Fan Off Set Point (ConfigurationIAQ<br />

AQ.SPD.F.OF) — This is the CO 2 level at which the<br />

indoor fan will be turned off.<br />

IAQ Low Reference (ConfigurationIAQAQ.S.R<br />

IQ.R.L) — This is the reference that will be used with a to<br />

non-Carrier IAQ sensor that may have a different characteristic<br />

curve. It represents the CO 2 level at 4 mA.<br />

IAQ High Reference (ConfigurationIAQAQ.SR<br />

IQ.R.H) — This is the reference that will be used with a<br />

non-Carrier IAQ sensor that may have a different characteristic<br />

curve. It represents the CO 2 level at 4 mA.<br />

OAQ Low Reference (ConfigurationIAQAQ.S.R<br />

OQ.R.L) — This is the reference that will be used with a<br />

non-Carrier OAQ sensor that may have a different characteristic<br />

curve. It represents the CO 2 level at 4 mA.<br />

OAQ High Reference (ConfigurationIAQAQ.S.R<br />

OQ.R.H) — This is the reference that will be used with a non-<br />

Carrier OAQ sensor that may have a different characteristic<br />

curve. It represents the CO 2 level at 4 mA.<br />

Diff. IAQ Responsiveness (ConfigurationIAQAQ.SP<br />

IAQ.R) — This is the configuration that is used to select the<br />

IAQ response curves as shown in Fig. 14.<br />

PRE-OCCUPANCY PURGE — The control has the option<br />

for a pre-occupancy purge to refresh the air in the space prior to<br />

occupancy.<br />

This feature is enabled by setting ConfigurationIAQ<br />

IAQ.PIQ.PG to Yes.<br />

The IAQ Purge will operate under the following conditions:<br />

• IQ.PG is enabled<br />

• the unit is in the unoccupied state<br />

• Current Time is valid<br />

• Next Occupied Time is valid<br />

• time is within two hours of the next occupied period<br />

• time is within the purge duration (Configuration<br />

IAQIAQ.PIQ.P.T)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!