Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
STAGE<br />
Table 49 — IGC LED Indicators<br />
NOTES:<br />
1. There is a 3-second pause between error code displays.<br />
2. If more than one error code exists, all applicable error codes will<br />
be displayed in numerical sequence.<br />
3. Error codes on the IGC will be lost if power to the unit is<br />
interrupted.<br />
The IGC boards only control the first stage of gas heat on<br />
each gas valve. The second stages are controlled directly from<br />
the MBB board. The IGC board has a minimum on-time of 1<br />
minute.<br />
In modes such as <strong>Service</strong> Test where long minimum on<br />
times are not enforced, the 1-minute timer on the IGC will still<br />
be followed <strong>and</strong> the gas will remain on for a minimum of 1<br />
minute.<br />
RELOCATE SAT FOR HEATING-LINKAGE APPLICA-<br />
TIONS — If ConfigurationHEATLAT.M is set to YES,<br />
the supply air temperature thermistor (TemperaturesAIR.T<br />
SAT) must be relocated downstream of the installed heating<br />
device. This only applies to two-stage gas or electric heating<br />
types (ConfigurationHEAT HT.CF=1 or 2).<br />
Determine a location in the supply duct that will provide a<br />
fairly uniform airflow. Typically this would be a minimum of<br />
5 equivalent duct diameters downstream of the unit. Also, care<br />
should be taken to avoid placing the thermistor within a direct<br />
line-of-sight of the heating element to avoid radiant effects.<br />
Run a new two-wire conductor cable from the control box<br />
through the low voltage conduit into the space inside the building<br />
<strong>and</strong> route the cable to the new sensor location.<br />
Installing a New Sensor — Procure a duct-mount temperature<br />
sensor (Carrier P/N 33ZCSENPAT or equivalent 10-kilo-ohm<br />
at 25C NTC [negative temperature coefficient] sensor). Install<br />
the sensor through the side wall of the duct <strong>and</strong> secure.<br />
Re-Using the Factory SAT Sensor — The factory sensor is<br />
attached to the left-h<strong>and</strong> side of the supply fan housing.<br />
Table 48 — Staged Gas Heat Control Steps (HT.ST = 3)<br />
RELAY OUTPUT<br />
Heat 1 Heat 2 Heat 3 Heat 4 Heat 5 Heat 6<br />
MBB-RLY8 MBB-RLY7 SCB-RLY1 SCB-RLY2 SCB-RLY3 SCB-RLY4<br />
IGC1 MGV1 IGC2 MGV2 IGC3 MGV3<br />
63<br />
CAPACITY<br />
%<br />
0 OFF OFF OFF OFF OFF OFF 0<br />
1 ON OFF OFF OFF OFF OFF 25<br />
2 ON ON OFF OFF OFF OFF 33<br />
3 ON OFF ON OFF OFF OFF 50<br />
4 ON ON ON OFF OFF OFF 58<br />
5 ON ON ON ON OFF OFF 67<br />
6 ON OFF ON OFF ON OFF 75<br />
7 ON OFF ON ON ON OFF 83<br />
8 ON ON ON ON ON OFF 92<br />
9 ON ON ON ON ON ON 100<br />
ERROR CODE LED INDICATION<br />
Normal <strong>Operation</strong> On<br />
Hardware Failure Off<br />
Fan On/Off Delay Modified 1 Flash<br />
Limit Switch Fault 2 Flashes<br />
Fame Sense Fault 3 Flashes<br />
Five Consecutive Limit Switch Faults 4 Flashes<br />
Ignition Lockout Fault 5 Flashes<br />
Ignition Switch Fault 6 Flashes<br />
Rollout Switch Fault 7 Flashes<br />
Internal Control Fault 8 Flashes<br />
Software Lockout 9 Flashes<br />
Disconnect the sensor from the factory harness. Fabricate a<br />
mounting method to insert the sensor through the duct wall <strong>and</strong><br />
secure in place.<br />
Attach the new conductor cable to the sensor leads <strong>and</strong> terminate<br />
in an appropriate junction box. Connect the opposite<br />
end inside the unit control box at the factory leads from MBB<br />
J8 terminals 11 <strong>and</strong> 12 (PNK) leads. Secure the unattached<br />
PNK leads from the factory harness to ensure no accidental<br />
contact with other terminals inside the control box.<br />
TEMPERING MODE — In a vent or cooling mode, the<br />
economizer at minimum position may send extremely cold<br />
outside air down the ductwork of the building. Therefore it<br />
may be necessary to bring heat on to counter-effect this low<br />
supply-air temperature. This is referred to as the tempering<br />
mode.<br />
Setting up the System — The relevant set points for tempering<br />
are located at the local display under Setpoints:<br />
ITEM EXPANSION RANGE UNITS<br />
T.PRG<br />
T.CL<br />
T.V.OC<br />
T.V.UN<br />
Tempering<br />
Purge SASP<br />
Tempering in<br />
Cool Offset<br />
Tempering Vent<br />
Occ SASP<br />
Tempering Vent<br />
Unocc. SASP<br />
CCN<br />
POINT<br />
DEFAULT<br />
–20-80 dF TEMPPURG 50<br />
5-75 ^F TEMPCOOL 5<br />
–20-80 dF TEMPVOCC 65<br />
–20-80 dF TEMPVUNC 50<br />
<strong>Operation</strong> — First, the unit must be in a vent mode, a low cool,<br />
or a high cool HVAC mode to be considered for a tempering<br />
mode. Secondly, the tempering mode is only allowed when the<br />
rooftop is configured for staged gas or hydronic heating (ConfigurationHEATHT.CF=3<br />
or 4). Also, if OAT is above<br />
the chosen tempering set point, tempering will not be allowed.<br />
Additionally, tempering mode is locked out if any stages of<br />
mechanical cooling are present.<br />
If the control is configured for staged gas or hydronic heating<br />
<strong>and</strong> the control is in a vent, low cool, or high cool HVAC<br />
mode, <strong>and</strong> the rooftop control is in a situation where the economizer<br />
must maintain a minimum position/minimum cfm, then<br />
the evaporator discharge temperature (EDT) will be monitored.<br />
If the EDT falls below a particular trip point then tempering<br />
mode may be called out:<br />
HVAC mode = “Tempering Vent”<br />
HVAC mode = “Tempering LoCool”<br />
HVAC mode = “Tempering HiCool”<br />
The decision making/selection process for the tempering<br />
trip set point is as follows:<br />
If an HVAC cool mode is in effect, then the tempering cool<br />
point is SASP – T.CL.