06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

This alarm will disable mechanical cooling <strong>and</strong> will require<br />

a manual reset. This alarm may be disabled once the reverse rotation<br />

check has been verified by setting Configuration<br />

COOLRR.VF = Yes.<br />

It is important to note that in <strong>Service</strong> Test mode, reverse rotation<br />

is checked on every compressor start.<br />

A150 (Unit is in Emergency Stop) — If the CCN point name<br />

“EMSTOP” in the System table is set to emergency stop, the<br />

unit will shut down immediately <strong>and</strong> broadcast an alarm back<br />

to the CCN indicating that the unit is down. This alarm will<br />

clear when the variable is set back to “enable”.<br />

A152 (Unit Down Due to Failure) — This alarm occurs<br />

whenever both cooling circuits are unavailable to cool. Mechanical<br />

cooling is impossible due to a failure in the system explained<br />

through other current alarms.<br />

Possible problems are:<br />

• plenum pressure switch trips on a return fan tracking unit<br />

• the supply fan status alarms have been instructed to shut<br />

down the unit<br />

• both circuits incapable of cooling due to multiple alerts of<br />

compressors <strong>and</strong>/or pressure alerts<br />

• a hardware failure of the main board's analog to digital converter<br />

or EEPROM chip<br />

• a critical storage failure in EEPROM has rendered the unit<br />

inoperable<br />

• the unit is configured for inlet guide vanes <strong>and</strong> the actuator<br />

controlling the vanes is in fault.<br />

Reset is automatic.<br />

T153 (Real Time Clock Hardware Failure) — The RTC<br />

clock chip on the MBB is not responding. Recovery is automatic<br />

but typically board replacement may be necessary.<br />

A154 (Serial EEPROM Hardware Failure) — The unit will<br />

be completely shut down. The serial EEPROM chip on the<br />

MBB which stores the unit's configurations is not responding.<br />

Recovery is automatic but typically board replacement is<br />

necessary.<br />

T155 (Serial EEPROM Storage Failure Error) — Configuration<br />

data in the serial EEPROM chip can not be verified which<br />

may mean MBB replacement. It is possible a re-initialization<br />

of the database or particular storage area(s) may clean up this<br />

problem. Reset is automatic.<br />

A156 (Critical Serial EEPROM Storage Fail Error) — The<br />

unit is completely shut down. Critical configuration data in the<br />

serial EEPROM chip can not be verified which may mean<br />

MBB replacement. Recovery is automatic but typically board<br />

replacement is necessary.<br />

NOTE: The machine will shut down. This may happen after<br />

downloading via the CCN if the device code was corrupted.<br />

Try downloading again or use the LEN connection to<br />

download.<br />

A157 (A/D Hardware Failure) — The unit will be completely<br />

shut down. The analog to digital conversion chip on the MBB<br />

has failed. Recovery is automatic but typically board replacement<br />

is necessary.<br />

A169 (Expansion Valve Control Board Comm Failure) —<br />

Cooling is disabled until communication with the EXV control<br />

board is re-established. Recovery is automatic. Reason for failure<br />

may be due to incorrect wiring, power loss to the control<br />

board, or damage to the RS-485 drivers on the LEN bus.<br />

T170 (Compressor Expansion Board Comm Failure) —<br />

Compressors A3 <strong>and</strong> B3 are disabled until communication<br />

with the CEB control board is re-established. Recovery is automatic.<br />

Reason for failure may be due to incorrect wiring, power<br />

loss to the control board, or damage to the RS-485 drivers on<br />

the LEN bus.<br />

A171 (Staged Gas Control Board Comm Failure) — Staged<br />

Gas Heating is disabled until communication with the staged<br />

113<br />

gas control board is re-established. Recovery is automatic.<br />

Reason for failure may be due to incorrect wiring, power loss<br />

to the staged gas control board, or damage to the RS-485 drivers<br />

on the LEN bus.<br />

T172 (Control Expansion Module Comm Failure) — Any<br />

function associated with a sensor configured for use that resides<br />

on the controls expansion module will be disabled until<br />

communication is re-established. Recovery is automatic. Reason<br />

for failure may be due to incorrect wiring, power loss to the<br />

control expansion module, or damage to the RS-485 drivers on<br />

the LEN bus.<br />

A173 (RXB Board Communication Failure) — As the RXB<br />

board is integral to all P Series units, the error will cause a system<br />

shutdown until communication is re-established. Recovery<br />

is automatic. Reason for failure may be due to incorrect wiring,<br />

power loss to the RXB board, or damage to the RS-485 drivers<br />

on the LEN bus.<br />

A174 (EXB Board Communication Failure) — The EXB<br />

board is responsible for building pressure control. Building<br />

Pressure control configurations that require this board will<br />

cause a complete system shut down when communication failure<br />

occurs. Recovery is automatic. Reason for failure may be<br />

due to incorrect wiring, power loss to the EXB board, or damage<br />

to the RS-485 drivers on the LEN bus.<br />

A175 (Supply Fan VFD Communication Failure) — The<br />

supply fan is disabled until communication with the supply fan<br />

VFD is re-established. Recovery is automatic. Reason for failure<br />

may be due to incorrect wiring, power loss to the VFD, or<br />

damage to the RS-485 drivers on the LEN bus.<br />

T176 (Exhaust Fan VFD Communication Failure) — The<br />

exhaust fan is disabled until communication with the exhaust<br />

fan VFD is re-established. Recovery is automatic. Reason for<br />

failure may be due to incorrect wiring, power loss to the VFD,<br />

or damage to the RS-485 drivers on the LEN bus.<br />

T177 (4-20 mA Dem<strong>and</strong> Limit Failure) — If this transducer<br />

fails, <strong>and</strong> the unit is configured to perform dem<strong>and</strong> limiting<br />

with this transducer, no capacity limiting will be performed <strong>and</strong><br />

an alert will be generated. Recovery is automatic. Reason for<br />

error is either a faulty sensor, wiring error, or damaged input on<br />

the CEM control board.<br />

T178 (4-20 mA Static Pressure Reset Fail) — If this transducer<br />

fails, <strong>and</strong> the unit is configured to perform static pressure<br />

reset with this transducer, no static pressure reset will be performed<br />

<strong>and</strong> an alert will be generated. Recovery is automatic.<br />

Reason for error is either a faulty sensor, wiring error, or damaged<br />

input on the CEM control board.<br />

A200 (Linkage Timeout Error — Comm Failure) — If linkage<br />

is established via the CCN with ComfortID terminals, a<br />

5-minute timeout on loss of communication will be monitored.<br />

If 5 minutes expires since the last communication from a VAV<br />

Linkage Master, the unit will remove the link <strong>and</strong> flag the alert.<br />

When the rooftop loses its link, the temperature <strong>and</strong> set points<br />

are derived locally. Recovery is automatic on re-establishment<br />

of communications. Reason for failure may be wiring error, too<br />

much bus activity, or damaged RS-485 drivers.<br />

T210 (Building Pressure Transducer Failure) — If the building<br />

pressure transducer (PressuresAIR.PBP) fails, building<br />

pressure control fails also. Recovery is automatic. Reason<br />

for error is either a faulty sensor, wiring error, or damaged input<br />

on the RXB control board.<br />

T211 (Static Pressure Transducer Failure) — If the static<br />

pressure transducer (PressuresAIR.PSP) fails, static pressure<br />

control fails also. Recovery is automatic. Reason for error<br />

is either a faulty sensor, wiring error, or damaged input on the<br />

RXB control board.<br />

T220 (Indoor Air Quality Sensor Failure) — If the indoor air<br />

quality sensor (InputsAIR.QIAQ) fails, dem<strong>and</strong> control<br />

ventilation is not possible. The control defaults to the max vent

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!