Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
This alarm will disable mechanical cooling <strong>and</strong> will require<br />
a manual reset. This alarm may be disabled once the reverse rotation<br />
check has been verified by setting Configuration<br />
COOLRR.VF = Yes.<br />
It is important to note that in <strong>Service</strong> Test mode, reverse rotation<br />
is checked on every compressor start.<br />
A150 (Unit is in Emergency Stop) — If the CCN point name<br />
“EMSTOP” in the System table is set to emergency stop, the<br />
unit will shut down immediately <strong>and</strong> broadcast an alarm back<br />
to the CCN indicating that the unit is down. This alarm will<br />
clear when the variable is set back to “enable”.<br />
A152 (Unit Down Due to Failure) — This alarm occurs<br />
whenever both cooling circuits are unavailable to cool. Mechanical<br />
cooling is impossible due to a failure in the system explained<br />
through other current alarms.<br />
Possible problems are:<br />
• plenum pressure switch trips on a return fan tracking unit<br />
• the supply fan status alarms have been instructed to shut<br />
down the unit<br />
• both circuits incapable of cooling due to multiple alerts of<br />
compressors <strong>and</strong>/or pressure alerts<br />
• a hardware failure of the main board's analog to digital converter<br />
or EEPROM chip<br />
• a critical storage failure in EEPROM has rendered the unit<br />
inoperable<br />
• the unit is configured for inlet guide vanes <strong>and</strong> the actuator<br />
controlling the vanes is in fault.<br />
Reset is automatic.<br />
T153 (Real Time Clock Hardware Failure) — The RTC<br />
clock chip on the MBB is not responding. Recovery is automatic<br />
but typically board replacement may be necessary.<br />
A154 (Serial EEPROM Hardware Failure) — The unit will<br />
be completely shut down. The serial EEPROM chip on the<br />
MBB which stores the unit's configurations is not responding.<br />
Recovery is automatic but typically board replacement is<br />
necessary.<br />
T155 (Serial EEPROM Storage Failure Error) — Configuration<br />
data in the serial EEPROM chip can not be verified which<br />
may mean MBB replacement. It is possible a re-initialization<br />
of the database or particular storage area(s) may clean up this<br />
problem. Reset is automatic.<br />
A156 (Critical Serial EEPROM Storage Fail Error) — The<br />
unit is completely shut down. Critical configuration data in the<br />
serial EEPROM chip can not be verified which may mean<br />
MBB replacement. Recovery is automatic but typically board<br />
replacement is necessary.<br />
NOTE: The machine will shut down. This may happen after<br />
downloading via the CCN if the device code was corrupted.<br />
Try downloading again or use the LEN connection to<br />
download.<br />
A157 (A/D Hardware Failure) — The unit will be completely<br />
shut down. The analog to digital conversion chip on the MBB<br />
has failed. Recovery is automatic but typically board replacement<br />
is necessary.<br />
A169 (Expansion Valve Control Board Comm Failure) —<br />
Cooling is disabled until communication with the EXV control<br />
board is re-established. Recovery is automatic. Reason for failure<br />
may be due to incorrect wiring, power loss to the control<br />
board, or damage to the RS-485 drivers on the LEN bus.<br />
T170 (Compressor Expansion Board Comm Failure) —<br />
Compressors A3 <strong>and</strong> B3 are disabled until communication<br />
with the CEB control board is re-established. Recovery is automatic.<br />
Reason for failure may be due to incorrect wiring, power<br />
loss to the control board, or damage to the RS-485 drivers on<br />
the LEN bus.<br />
A171 (Staged Gas Control Board Comm Failure) — Staged<br />
Gas Heating is disabled until communication with the staged<br />
113<br />
gas control board is re-established. Recovery is automatic.<br />
Reason for failure may be due to incorrect wiring, power loss<br />
to the staged gas control board, or damage to the RS-485 drivers<br />
on the LEN bus.<br />
T172 (Control Expansion Module Comm Failure) — Any<br />
function associated with a sensor configured for use that resides<br />
on the controls expansion module will be disabled until<br />
communication is re-established. Recovery is automatic. Reason<br />
for failure may be due to incorrect wiring, power loss to the<br />
control expansion module, or damage to the RS-485 drivers on<br />
the LEN bus.<br />
A173 (RXB Board Communication Failure) — As the RXB<br />
board is integral to all P Series units, the error will cause a system<br />
shutdown until communication is re-established. Recovery<br />
is automatic. Reason for failure may be due to incorrect wiring,<br />
power loss to the RXB board, or damage to the RS-485 drivers<br />
on the LEN bus.<br />
A174 (EXB Board Communication Failure) — The EXB<br />
board is responsible for building pressure control. Building<br />
Pressure control configurations that require this board will<br />
cause a complete system shut down when communication failure<br />
occurs. Recovery is automatic. Reason for failure may be<br />
due to incorrect wiring, power loss to the EXB board, or damage<br />
to the RS-485 drivers on the LEN bus.<br />
A175 (Supply Fan VFD Communication Failure) — The<br />
supply fan is disabled until communication with the supply fan<br />
VFD is re-established. Recovery is automatic. Reason for failure<br />
may be due to incorrect wiring, power loss to the VFD, or<br />
damage to the RS-485 drivers on the LEN bus.<br />
T176 (Exhaust Fan VFD Communication Failure) — The<br />
exhaust fan is disabled until communication with the exhaust<br />
fan VFD is re-established. Recovery is automatic. Reason for<br />
failure may be due to incorrect wiring, power loss to the VFD,<br />
or damage to the RS-485 drivers on the LEN bus.<br />
T177 (4-20 mA Dem<strong>and</strong> Limit Failure) — If this transducer<br />
fails, <strong>and</strong> the unit is configured to perform dem<strong>and</strong> limiting<br />
with this transducer, no capacity limiting will be performed <strong>and</strong><br />
an alert will be generated. Recovery is automatic. Reason for<br />
error is either a faulty sensor, wiring error, or damaged input on<br />
the CEM control board.<br />
T178 (4-20 mA Static Pressure Reset Fail) — If this transducer<br />
fails, <strong>and</strong> the unit is configured to perform static pressure<br />
reset with this transducer, no static pressure reset will be performed<br />
<strong>and</strong> an alert will be generated. Recovery is automatic.<br />
Reason for error is either a faulty sensor, wiring error, or damaged<br />
input on the CEM control board.<br />
A200 (Linkage Timeout Error — Comm Failure) — If linkage<br />
is established via the CCN with ComfortID terminals, a<br />
5-minute timeout on loss of communication will be monitored.<br />
If 5 minutes expires since the last communication from a VAV<br />
Linkage Master, the unit will remove the link <strong>and</strong> flag the alert.<br />
When the rooftop loses its link, the temperature <strong>and</strong> set points<br />
are derived locally. Recovery is automatic on re-establishment<br />
of communications. Reason for failure may be wiring error, too<br />
much bus activity, or damaged RS-485 drivers.<br />
T210 (Building Pressure Transducer Failure) — If the building<br />
pressure transducer (PressuresAIR.PBP) fails, building<br />
pressure control fails also. Recovery is automatic. Reason<br />
for error is either a faulty sensor, wiring error, or damaged input<br />
on the RXB control board.<br />
T211 (Static Pressure Transducer Failure) — If the static<br />
pressure transducer (PressuresAIR.PSP) fails, static pressure<br />
control fails also. Recovery is automatic. Reason for error<br />
is either a faulty sensor, wiring error, or damaged input on the<br />
RXB control board.<br />
T220 (Indoor Air Quality Sensor Failure) — If the indoor air<br />
quality sensor (InputsAIR.QIAQ) fails, dem<strong>and</strong> control<br />
ventilation is not possible. The control defaults to the max vent