AIRFLOW<br />

(cfm)<br />

Table 14 — Fan Performance — 50P2,P3055 Units with Discharge Plenum <strong>and</strong> 50P4,P5055 Units<br />

LEGEND<br />

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)<br />

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6<br />

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp<br />

10,000 217 1.21 258 1.71 296 2.29 334 2.97 371 3.76 407 4.63 440 5.56 471 6.51<br />

12,500 248 2.01 286 2.63 319 3.26 349 3.95 380 4.71 410 5.58 440 6.52 469 7.54<br />

15,000 281 3.13 317 3.90 347 4.64 374 5.38 400 6.18 425 7.03 450 7.95 476 8.95<br />

17,500 315 4.64 348 5.55 378 6.43 403 7.29 426 8.16 449 9.05 471 10.00 493 10.99<br />

20,000 351 6.64 381 7.64 409 8.68 433 9.68 456 10.66 477 11.64 497 12.65 516 13.68<br />

22,500 389 9.20 414 10.25 440 11.43 464 12.59 486 13.71 506 14.81 525 15.91 543 17.03<br />

25,000 427 12.39 449 13.48 473 14.75 496 16.06 517 17.34 537 18.59 555 19.82 573 21.04<br />

AIRFLOW<br />

(cfm)<br />

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)<br />

1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2<br />

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp<br />

10,000 500 7.48 527 8.46 552 9.45 576 10.44 598 11.42 619 12.41 639 13.41 659 14.41<br />

12,500 498 8.63 525 9.76 552 10.93 577 12.12 601 13.32 624 14.54 646 15.76 667 16.99<br />

15,000 501 10.03 526 11.17 550 12.38 575 13.65 598 14.97 621 16.32 644 17.71 666 19.11<br />

17,500 514 12.05 536 13.17 557 14.35 579 15.60 600 16.91 621 18.28 643 19.70 663 21.18<br />

20,000 535 14.76 554 15.88 573 17.06 592 18.29 611 19.58 630 20.91 649 22.31 668 23.77<br />

22,500 561 18.17 579 19.34 596 20.54 613 21.78 629 23.06 646 24.40 663 25.78 680 27.20<br />

25,000 590 22.27 606 23.51 622 24.78 637 26.07 653 27.39 668 28.75 683 30.13 699 31.56<br />

AIRFLOW<br />

(cfm)<br />

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)<br />

3.4 3.6 3.8 4.0<br />

Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp<br />

10,000 677 15.40 695 16.40 712 17.40 728 18.41<br />

12,500 687 18.22 706 19.45 725 20.69 742 21.92<br />

15,000 687 20.54 707 21.98 727 23.43 746 24.89<br />

17,500 684 22.69 704 24.24 724 25.83 743 27.43<br />

20,000 686 25.27 705 26.84 723 28.44 742 30.09<br />

22,500 697 28.68 713 30.21 730 31.79 747 33.42<br />

25,000 714 33.04 729 34.55 — — — —<br />

50P3,P5 units only.<br />

Bhp — Brake Horsepower<br />

NOTES:<br />

1. Fan performance is based on wet coils <strong>and</strong> clean 2-in. filters.<br />

19<br />

2. See Component Pressure Drop data table before using Fan Performance<br />

tables.<br />

3. Conversion — Bhp to kW:<br />

Kilowatts =<br />

Bhp x .746<br />

Motor efficiency<br />

See Physical Data table for motor efficiency.