06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CONTROLS SET POINT AND CONFIGURATION LOG (cont)<br />

ITEM EXPANSION RANGE DEFAULT SETTING<br />

ECON ECONOMIZER CONFIGURATION<br />

EC.EN Economizer Installed? Yes/No Yes<br />

EC2.E Econ.Act.2 Installed? Yes/No No<br />

EC.MN Economizer Min.Position 0 - 100% 5<br />

EC.MX Economizer Max.Position 0 - 100% 98<br />

E.TRM Economzr Trim For SumZ ? Yes/No Yes<br />

E.SEL Econ ChangeOver Select 0 - 3 (multi-text strings) 0<br />

OA.E.C OA Enthalpy ChgOvr Selct 1 - 5 (multi-text strings) 4<br />

OA.EN Outdr.Enth Compare Value 18 - 28 24<br />

OAT.L High OAT Lockout Temp -40 - 120 dF 60<br />

O.DEW OA Dewpoint Temp Limit 50 - 62 dF 55<br />

ORH.S Outside Air RH Sensor Enable/Disable Disable<br />

CFM.C OUTDOOR AIR CFM CONTROL<br />

CFM.COCF.S Outdoor Air CFM Sensor Enable/Disable Disable<br />

CFM.CO.C.MX Economizer Min.Flow 0 - 20000 CFM 2000<br />

CFM.CO.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow 0 - 20000 CFM 0<br />

CFM.CO.C.DB Econ.Min.Flow Deadb<strong>and</strong> 200 - 1000 CFM 400<br />

E.CFG ECON.OPERATION CONFIGS<br />

E.CFGE.P.GN Economizer Prop.Gain 0.7 - 3.0 1<br />

E.CFGE.RNG Economizer Range Adjust 0.5 - 5 ^F 2.5<br />

E.CFGE.SPD Economizer Speed Adjust 0.1 - 10 0.75<br />

E.CFGE.DBD Economizer Deadb<strong>and</strong> 0.1 - 2 ^F 0.5<br />

UEFC UNOCC.ECON.FREE COOLING<br />

UEFCFC.CF Unoc Econ Free Cool Cfg 0-2 (multi-text strings) 0<br />

UEFCFC.TM Unoc Econ Free Cool Time 0 - 720 min 120<br />

UEFCFC.L.O Un.Ec.Free Cool OAT Lock 40 - 70 dF 50<br />

ACT.C ECON.ACTUATOR CONFIGS<br />

ACTCSN.1.1 Econ Serial Number 1 0 - 9999 0<br />

ACTCSN.1.2 Econ Serial Number 2 0 - 6 0<br />

ACTCSN.1.3 Econ Serial Number 3 0 - 9999 0<br />

ACTCSN.1.4 Econ Serial Number 4 0 - 254 0<br />

ACTCC.A.L1 Econ Ctrl Angle Lo Limit 0 - 90 85<br />

ACTCSN.2.1 Econ 2 Serial Number 1 0 - 9999 0<br />

ACTCSN.2.2 Econ 2 Serial Number 2 0 - 6 0<br />

ACTCSN.2.3 Econ 2 Serial Number 3 0 - 9999 0<br />

ACTCSN.2.4 Econ 2 Serial Number 4 0 - 254 0<br />

ACTCC.A.L2 Econ 2 Ctrl Angle Lo Limit 0 - 90 85<br />

BP BUILDING PRESS. CONFIGS<br />

BP.CF Building Press. Config 0 - 5 (multi-text strings) 0<br />

BP.S Building Pressure Sensor Enable/Disable Disable<br />

BP.R Bldg. Press. (+/-) Range 0.10 - 0.25 "H2O 0.25<br />

BP.SP Building Pressure Setp. -0.25 - 0.25 "H2O 0.05<br />

BP.SO BP Setpoint Offset 0 - 0.5 "H2O 0.05<br />

BP.P1 Power Exhaust On Setp.1 0 - 100% 25<br />

BP.P2 Power Exhaust On Setp.2 0 - 100% 75<br />

B.V.A VFD/ACTUATOR CONFIG<br />

B.V.ABP.FS VFD/Act. Fire Speed/Pos. 0 - 100% 100<br />

B.V.ABP.MN VFD/Act. Min.Speed/Pos. 0 - 50% 0<br />

B.V.ABP.MX VFD Maximum Speed 50 - 100% 100<br />

B.V.ABP.1M BP 1 Actuator Max Pos. 85 - 100% 100<br />

B.V.ABP.2M BP 2 Actuator Max Pos. 85 - 100% 100<br />

B.V.ABP.CL BP Hi Cap VFD Clamp Val. 5 - 25% 10<br />

CL-3

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!