position. Recovery is automatic. Reason for error is either a<br />

faulty sensor, wiring error, or damaged input on the MBB control<br />

board.<br />

T221 (Outdoor Air Quality Sensor Failure) — If the outdoor<br />

air quality sensor (InputsAIR.QOAQ) fails, OAQ<br />

defaults to 400 ppm <strong>and</strong> dem<strong>and</strong> control ventilation will<br />

continue. Recovery is automatic. Reason for error is either a<br />

faulty sensor, wiring error, or damaged input on the CEM<br />

control board.<br />

T229 (Economizer Min Pos Override Input Failure) — If<br />

the economizer minimum position override input fails, the<br />

economizer will operate as if it were not configured for<br />

override. Recovery is automatic. Reason for error is either a<br />

faulty sensor, wiring error, or damaged input on the MBB control<br />

board. This error only occurs when the unit is configured<br />

for minimum position override <strong>and</strong> a 4 to 20 mA signal is not<br />

present.<br />

T245 (Outside Air Cfm Sensor Failure) — If the outside air cfm<br />

sensor (InputsCFMO.CFM) fails, the economizer will default<br />

to discrete positioning of the economizer (Configuration<br />

IAQDCV.CIAQ.M, ConfigurationEconEC.MN).<br />

Recovery is automatic. Reason for error is either a faulty sensor,<br />

wiring error, or damaged input on the CEM control board.<br />

T246 (Supply Air Cfm Sensor Failure) — If the supply air<br />

cfm sensor (InputsCFMS.CFM) fails, fan tracking is not<br />

possible <strong>and</strong> the system will shut down. Recovery is automatic.<br />

Reason for error is either a faulty sensor, wiring error, or damaged<br />

input on the EXB control board.<br />

T247 (Return Air Cfm Sensor Failure) — If the return air<br />

cfm sensor (InputsCFMR.CFM) fails, fan tracking is not<br />

possible <strong>and</strong> the system will shut down. Recovery is automatic.<br />

Reason for error is either a faulty sensor, wiring error, or damaged<br />

input on the EXB control board.<br />

T300 (Space Temperature Below Limit) — If the space temperature<br />

is below the configurable SPT Low Alert Limits (occupied<br />

[ConfigurationALLMSP.L.O] for 5 minutes or<br />

unoccupied [ConfigurationALLMSP.L.U] for 10 minutes),<br />

then an alert will be broadcast. The alert will automatically<br />

reset.<br />

T301 (Space Temperature Above Limit) — If the space temperature<br />

is above the configurable SPT High Alert Limits<br />

(occupied [ConfigurationALLMSP.H.O] for 5 minutes or<br />

unoccupied [ConfigurationALLMSP.H.U] for 10 minutes),<br />

then an alert will be broadcast. The alert will automatically<br />

reset.<br />

T302 (Supply Temperature Below Limit) — If the supply-air<br />

temperature measured by the supply temperature sensor is below<br />

the configurable SAT LO Alert Limit/Occ (Configuration<br />

ALLMSA.L.O) for 5 minutes or the Low Supply air temperature<br />

alert limit unoccupied mode (ConfigurationALLM<br />

SA.L.U) for 10 minutes, then an alert will be broadcast.<br />

T303 (Supply Temperature Above Limit) — If the supply<br />

temperature is above the configurable SAT HI Alert Limit Occ<br />

(ConfigurationALLMSAH.O) for 5 minutes or the SAT<br />

HI Alert Limit/Unocc (ConfigurationALLMSA.H.U) for<br />

10 minutes, then an alert will be broadcast. The alert will automatically<br />

reset.<br />

T304 (Return Air Temperature Below Limit) — If the return<br />

air temperature measured by the RAT sensor is below the<br />

configurable RAT LO Alert Limit/Occ (Configuration<br />

ALLMRA.L.O) for 5 minutes or RAT HI Alert Limit/Occ<br />

(ConfigurationALLMRA.L.U) for 10 minutes, then an<br />

alert will be broadcast.<br />

T305 (Return Air Temperature Above Limit) — If the return<br />

air temperature is below the RAT HI Alert Limit/Occ (ConfigurationALLMRA.H.O)<br />

for 5 minutes or RAT HI Alert<br />

Limit/Occ (ConfigurationALLMRA.H.U) for 10 minutes,<br />

then an alert will be broadcast. The alert will automatically reset.<br />

114<br />

T308 (Return Air Relative Humidity Below Limit) — If the<br />

unit is configured to use a return air relative humidity sensor<br />

through the Return Air RH Sensor (ConfigurationUNIT<br />

SENSRRH.S) setting, <strong>and</strong> the measured level is below the<br />

configurable RH Low Alert Limit (ConfigurationALLM<br />

R.RH.L) for 5 minutes, then the alert will occur. The unit will<br />

continue to run <strong>and</strong> the alert will automatically reset.<br />

T309 (Return Air Relative Humidity Above Limit) — If the<br />

unit is configured to use a return air relative humidity sensor<br />

through the Return Air RH Sensor (ConfigurationUNIT<br />

SENSRRH.S) setting, <strong>and</strong> the measured level is above the<br />

configurable RH High Alert Limit (ConfigurationALLM<br />

R.RH.H) for 5 minutes, then the alert will occur. Unit will continue<br />

to run <strong>and</strong> the alert will automatically reset.<br />

T310 (Supply Duct Pressure Below Limit) — If the unit is a<br />

VAV unit with a supply duct pressure sensor <strong>and</strong> the measured<br />

supply duct static pressure (PressuresAIR.PSP) is below<br />

the configurable SP Low Alert Limit (ConfigurationALLM<br />

SP.L) for 5 minutes, then the alert will occur. The unit will<br />

continue to run <strong>and</strong> the alert will automatically reset.<br />

T311 (Supply Duct Pressure Above Limit) — If the unit is a<br />

VAV unit with a supply duct pressure sensor <strong>and</strong> the measured<br />

supply duct static pressure (PressuresAIR.PSP) is above<br />

the configurable SP Low Alert Limit (ConfigurationALLM<br />

SP.H) for 5 minutes, then the alert will occur. The unit will<br />

continue to run <strong>and</strong> the alert will automatically reset.<br />

T312 (Building Static Pressure Below Limit) — If the unit<br />

is configured to use modulating power exhaust then a<br />

building static pressure limit can be configured using the BP<br />

Low Alert Limit (ConfigurationALLMBP.L). If the measured<br />

pressure (PressuresAIR.PBP) is below the limit for<br />

5 minutes then the alert will occur.<br />

T313 (Building Static Pressure Above Limit) — If the unit<br />

is configured to use modulating power exhaust then a<br />

building static pressure limit can be configured using the BP HI<br />

Alert Limit (ConfigurationALLMBP.H). If the measured<br />

pressure (PressuresAIR.PBP) is above the limit for<br />

5 minutes, then the alert will occur.<br />

T314 (IAQ Above Limit) — If the unit is configured to use a<br />

CO 2 sensor <strong>and</strong> the level (InputsAIR.QIAQ) is above the<br />

configurable IAQ High Alert Limit (ConfigurationALLM<br />

IAQ.H) for 5 minutes then the alert will occur. The unit will<br />

continue to run <strong>and</strong> the alert will automatically reset.<br />

T316 (OAT Below Limit) — If the outside-air temperature<br />

measured by the OAT thermistor (TemperaturesAIR.T<br />

OAT) is below the configurable OAT Low Alert Limit (ConfigurationALLMOAT.L)<br />

for 5 minutes then the alert will<br />

be broadcast.<br />

T317 (OAT Above Limit — If the outside-air temperature<br />

measured by the OAT thermistor (TemperaturesAIR.T<br />

OAT) is above the configurable OAT High Alert Limit<br />

(ConfigurationALLMOAT.H) for 5 minutes then the alert<br />

will be broadcast.<br />

A400 (Hydronic Freezestat Trip) — If the freezestat for the<br />

hydronic coil trips, the unit goes into emergency mode <strong>and</strong><br />

does not allow cooling or heating. The economizer goes to 0%<br />

open. Supply fan operation is enabled. Recovery is automatic<br />

when the switch goes off.<br />

A404 (Fire Shut Down Emergency Mode [fire-smoke]) —<br />

If the fire shutdown input is energized (fire shutdown is in effect),<br />

or if two fire smoke modes are incorrectly energized at<br />

the same time, a Fire Shutdown mode will occur. This is an<br />

emergency mode requiring the complete shutdown of the unit.<br />

Recovery is automatic when the inputs are no longer on.<br />

A405 (Evacuation Emergency Mode) — If the evacuation input<br />

on the CEM is energized, an evacuation mode occurs<br />

which flags an alarm. This mode attempts to lower the pressure<br />

of the space to prevent smoke from moving into another space.