06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Routine cleaning of coil surfaces is essential to maintain<br />

proper operation of the unit. Elimination of contamination <strong>and</strong><br />

removal of harmful residues will greatly increase the life of the<br />

coil <strong>and</strong> extend the life of the unit. The following steps should<br />

be taken to clean MCHX condenser coils:<br />

1. Remove any foreign objects or debris attached to the core<br />

face or trapped within the mounting frame <strong>and</strong> brackets.<br />

2. Put on personal protective equipment including safety<br />

glasses <strong>and</strong>/or face shield, waterproof clothing <strong>and</strong><br />

gloves. It is recommended to use full coverage clothing.<br />

3. <strong>Start</strong> high pressure water sprayer <strong>and</strong> purge any soap or<br />

industrial cleaners from sprayer before cleaning condenser<br />

coils. Only clean potable water is authorized for cleaning<br />

condenser coils.<br />

4. Clean condenser face by spraying the core steady <strong>and</strong><br />

uniformly from top to bottom while directing the spray<br />

straight toward the core. Do not exceed 900 psig or<br />

30 degree angle. The nozzle must be at least 12 in. from<br />

the core face. Reduce pressure <strong>and</strong> use caution to prevent<br />

damage to air centers.<br />

CAUTION<br />

Excessive water pressure will fracture the braze between<br />

air centers <strong>and</strong> refrigerant tubes.<br />

CONDENSATE DRAIN — Check <strong>and</strong> clean each year at<br />

start of cooling season. In winter, keep drains <strong>and</strong> traps dry.<br />

FILTERS — Clean or replace at start of each heating <strong>and</strong> cooling<br />

season, or more often if operating conditions require. Refer<br />

to Installation Instructions for type <strong>and</strong> size.<br />

1. Remove economizer outdoor-air filters from the hoods by<br />

removing the filter retainers.<br />

2. Clean filters with steam or hot water <strong>and</strong> mild detergent.<br />

3. Reinstall filters in hoods after cleaning. Never replace<br />

cleanable filters with throwaway filters.<br />

OUTDOOR-AIR INLET SCREENS — Clean screens with<br />

steam or hot water <strong>and</strong> a mild detergent. Do not use disposable<br />

filters in place of screens.<br />

Lubrication<br />

FAN SHAFT BEARINGS — Lubricate fan shaft bearings at<br />

least once a year with suitable bearing grease. Extended grease<br />

lines are provided on pulley side of blower. Typical lubricants<br />

are given below:<br />

MANUFACTURER LUBRICANT<br />

Texaco Regal AFB-2*<br />

Mobil Mobilplex EP No. 1<br />

Sunoco Prestige 42<br />

Texaco Multifak 2<br />

*Preferred lubricant because it contains rust <strong>and</strong> oxidation inhibitors.<br />

FAN MOTOR BEARINGS — The condenser-fan <strong>and</strong><br />

evaporator-fan motors have sealed bearings so no field lubrication<br />

is required.<br />

DOOR HINGES — All door hinges should be lubricated at<br />

least once a year.<br />

Refrigerant Feed Components — Each refrigerant<br />

circuit (2 per unit) has all the necessary refrigerant controls.<br />

Thermostatic Expansion Valve (TXV) — On sizes<br />

030 <strong>and</strong> 035, each circuit has one TXV. On sizes 040-100, each<br />

circuit has 2 TXVs on which superheat may be adjusted if necessary.<br />

Adjustment is not normally required or recommended.<br />

The TXV is set to maintain 10 to 13 F superheat leaving the<br />

evaporator coil. It controls the flow of refrigerant to the evaporator<br />

coils.<br />

143<br />

Refrigeration Circuits<br />

LEAK TESTING — Units are shipped with a full operating<br />

charge of R-410A (see unit nameplate). If there is no pressure<br />

in the system, introduce enough nitrogen to search for the leak.<br />

Repair the leak using good refrigeration practices. After leaks<br />

are repaired, system must be evacuated <strong>and</strong> dehydrated<br />

using methods described in GTAC II, Module 4, System<br />

Dehydration.<br />

REFRIGERANT CHARGE — Amount of refrigerant charge<br />

is listed on unit nameplate. Refer to Carrier GTAC II; Module<br />

5; Charging, Recovery, Recycling, <strong>and</strong> Reclamation section for<br />

charging methods <strong>and</strong> procedures.<br />

Unit panels must be in place when unit is operating during<br />

charging procedure.<br />

NOTE: Do not use recycled refrigerant as it may contain<br />

contaminants.<br />

NO CHARGE — Use st<strong>and</strong>ard evacuating techniques. After<br />

evacuating system, weigh in the specified amount of refrigerant<br />

from the unit nameplate.<br />

LOW CHARGE COOLING — Due to the compact, all aluminum<br />

design, microchannel heat exchangers will reduce<br />

refrigerant charge <strong>and</strong> overall operating weight. As a result,<br />

charging procedures for MCHX units require more accurate<br />

measurement techniques. Charge should be added in small<br />

increments. Using cooling charging charts provided (Fig. 52-<br />

89), add or remove refrigerant until conditions of the chart are<br />

met. As conditions get close to the point on the chart, add or<br />

remove charge in 1 / 4 lb increments until complete. Ensure that<br />

all fans are on <strong>and</strong> all compressors are running when using<br />

charging charts.<br />

To Use the Cooling Charging Chart — Use the outdoor air<br />

temperature, saturated suction temperature <strong>and</strong> saturated condensing<br />

temperature (available on the ComfortLink display),<br />

<strong>and</strong> find the intersection point on the cooling charging chart. If<br />

intersection point is above the line, carefully recover some of<br />

the refrigerant. If intersection point is below the line, carefully<br />

add refrigerant.<br />

NOTE: Indoor-air cfm must be within normal operating range<br />

of unit.<br />

In order to determine which charging chart to use, the technician<br />

can verify the evaporator configuration of the unit (High<br />

Cap or Std Cap) by counting the number of rows on the installed<br />

evaporator. Use Table 103 to identify the correct unit<br />

configuration for refrigerant charging.<br />

Units With Humidi-MiZer® Adaptive Dehumidification<br />

System<br />

NOTE: All circuits must be running in normal cooling<br />

mode. Indoor airflow must be within specified air quantity<br />

limits for cooling. All outdoor fans must be on <strong>and</strong> running at<br />

normal speed.<br />

Table 103 — Unit Capacity Type<br />

UNIT SIZE NUMBER OF ROWS ON EVAPORATOR<br />

48/50P<br />

High Capacity Std Capacity<br />

030 4 3<br />

035 N/A 4<br />

040 6 3<br />

050 6 4<br />

055 6 4<br />

060 6 4<br />

070 6 4<br />

075 6 4<br />

090 6 4<br />

100 6 4

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!