06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Configuring the Economizer to Communicate Via Actuator<br />

Serial Number — Every actuator used in the P Series control<br />

system has its own unique serial number. The rooftop control<br />

uses this serial number to communicate with the actuator.<br />

These serial numbers are programmed at the factory <strong>and</strong><br />

should not need changing. Should field replacement of an actuator<br />

become necessary, it will be required to configure the serial<br />

numbers of the new actuator. Four individual numbers make<br />

up this serial number <strong>and</strong> these can be programmed to match<br />

the serial number of the actuator in its Economizer Actuator<br />

Configs group, ACT.C (SN1.1, SN1.2, SN1.3, SN1.4, SN2.1,<br />

SN2.2, SN2.3, SN2.4).<br />

NOTE: The serial numbers for all actuators can be found<br />

inside the control doors of the unit as well as on the actuator<br />

itself. If an actuator is replaced in the field, it is a good idea to<br />

remove the additional peel-off serial number sticker on the<br />

actuator <strong>and</strong> cover up the old one inside the control doors.<br />

Control Angle Alarm Configuration — The economizer actuator<br />

determines its end stops through a calibration at the<br />

factory. Field-installed actuators may be calibrated in the<br />

<strong>Service</strong> Test mode. When an actuator learns its end stops<br />

through calibration, it also determines its control angle. The<br />

actuator will resolve this control angle <strong>and</strong> express its operation<br />

in a percent (%) of this learned range.<br />

If the economizer has not learned a sufficient control angle<br />

during calibration, the economizer damper will be unable<br />

to control ventilation <strong>and</strong> free cooling. For this reason the<br />

economizer actuator used in the P Series control system has a<br />

configurable control angle alarm low limit (Configuration<br />

ECONACT.CC.A.L1 or C.A.L2). If the control angle<br />

learned through calibration is less than C.A.L1 or C.A.L2, an<br />

alert will occur <strong>and</strong> the actuator will not function.<br />

NOTE: This configuration does not typically need adjustment.<br />

It is configurable for the small number of jobs which may<br />

require a custom solution or workaround.<br />

UNOCCUPIED ECONOMIZER FREE COOLING — This<br />

Free Cooling function is used to start the supply fan <strong>and</strong> use<br />

the economizer to bring in outside air when the outside<br />

temperature is cool enough to pre-cool the space. This is done<br />

to delay the need for mechanical cooling when the system<br />

enters the occupied period. This function requires the use of a<br />

space temperature sensor.<br />

When configured, the economizer will modulate during an<br />

unoccupied period <strong>and</strong> attempt to maintain space temperature<br />

to the occupied cooling set point. Once the need for cooling has<br />

been satisfied during this cycle, the fan will be stopped.<br />

Configuring the economizer for Unoccupied Economizer<br />

Free Cooling is done in the UEFC group. There are three<br />

configuration options, FC.CF, FC.TM <strong>and</strong> FC.LO.<br />

Unoccupied Economizer Free Cooling Configuration<br />

(FC.CF) — This option is used to configure the type of unoccupied<br />

economizer free cooling control that is desired.<br />

0 = disable unoccupied economizer free cooling<br />

1 = perform unocc. economizer free cooling as available during<br />

the entire unoccupied period.<br />

2 = perform unocc. economizer free cooling as available,<br />

FC.TM minutes before the next occupied period.<br />

Unoccupied Economizer Free Cooling Time Configuration<br />

(FC.TM) — This option is a configurable time period, prior to<br />

the next occupied period, that the control will allow unoccupied<br />

economizer free cooling to operate. This option is only<br />

applicable when FC.CF = 2.<br />

Unoccupied Economizer Free Cooling Outside Lockout<br />

Temperature (FC.LO) — This configuration option allows<br />

the user to select an outside-air temperature below which unoccupied<br />

free cooling is not allowed. This is further explained in<br />

the logic section.<br />

70<br />

Unoccupied Economizer Free Cooling Logic — The following<br />

qualifications that must be true for unoccupied free cooling<br />

to operate:<br />

• Unit configured for an economizer<br />

• Space temperature sensor enabled <strong>and</strong> sensor reading<br />

within limits<br />

• Unit in the unoccupied mode<br />

• FC.CF set to 1 or FC.CF set to 2 <strong>and</strong> control is within<br />

FC.TM minutes of the next occupied period<br />

• Not in the Temperature Compensated <strong>Start</strong> mode<br />

• Not in a cooling mode<br />

• Not in a heating mode<br />

• Not in a tempering mode<br />

• Outside-air temperature sensor reading within limits<br />

• Economizer would be allowed to cool if the fan were<br />

requested <strong>and</strong> in a cool mode<br />

• OAT > FC.LO (1.0° F hysteresis applied)<br />

• Unit not in a fire smoke mode<br />

• No fan failure when configured to for unit to shut down<br />

on a fan failure<br />

If all of the above conditions are satisfied:<br />

Unoccupied Economizer Free Cooling will start when both of<br />

the following conditions are true:<br />

{SPT > (OCSP + 2)} AND {SPT > (OAT + 8)}<br />

The Unoccupied Economizer Free Cooling Mode will stop<br />

when either of the following conditions are true:<br />

{SPT < OCSP} OR {SPT < (OAT + 3)} where SPT = Space<br />

Temperature <strong>and</strong> OCSP = Occupied Cooling Set Point.<br />

When the Unoccupied Economizer Free Cooling mode is<br />

active, the supply fan is turned on <strong>and</strong> the economizer damper<br />

modulated to control to the supply air set point (Setpoints<br />

SASP) plus any supply air reset that may be applied (Inputs<br />

RSETSA.S.R).<br />

OUTDOOR AIR CFM CONTROL — If an outdoor air cfm<br />

flow station has been installed, the economizer is able to<br />

provide minimum ventilation based on cfm, instead of<br />

damper position. The outdoor air cfm reading can be found in<br />

InputsCFMO.CFM. During cfm control, the economizer<br />

must guarantee a certain amount of cfm at any time for ventilation<br />

purposes. If the outdoor air cfm measured is less than the<br />

current calculated cfm minimum position, then the economizer<br />

will attempt to open until the outdoor air cfm is greater than or<br />

equal to this cfm minimum position. The following options are<br />

used to program outside air cfm control.<br />

Outdoor Air Cfm Sensor Enable (OCF.S) — If this option is<br />

enabled, the outdoor air cfm sensor will be read <strong>and</strong> outside air<br />

cfm control will be enabled.<br />

Economizer Minimum Flow Rate (O.C.MX) — This option<br />

replaces the Economizer Minimum Position (Configuration<br />

ECONEC.MN) when the outdoor air cfm sensor is<br />

enabled.<br />

IAQ Dem<strong>and</strong> Vent Minimum Flow Rate (O.C.MN) — This<br />

option replaces the IAQ Dem<strong>and</strong> Ventilation Minimum<br />

Position (ConfigurationIAQDCV.CIAQ.M) when the<br />

outdoor air cfm sensor is enabled.<br />

Economizer Minimum Flow Deadb<strong>and</strong> (O.C.DB) — This<br />

option defines the deadb<strong>and</strong> of the cfm control logic.<br />

The configurable deadb<strong>and</strong> is added to the economizer’s<br />

minimum cfm position <strong>and</strong> creates a range (ECMINCFM to<br />

ECMINCFM ± OACFM_DB) where the economizer will not<br />

attempt to adjust to maintain the minimum cfm position.<br />

Increasing this deadb<strong>and</strong> value may help to slow down excessive<br />

economizer movement when attempting to control to a<br />

minimum position at the expense of bringing in more ventilation<br />

air than desired.<br />

ECONOMIZER OPERATION CONFIGURATION — The<br />

configuration items in the E.CFG menu group affect how

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!