LEGEND<br />

IAQ — Indoor Air Quality<br />

VAV — Variable Air Volume<br />

Table 99 — Field Terminal Connections<br />

BOARD<br />

NO.<br />

TERMINAL<br />

NUMBER<br />

DESCRIPTION TYPE<br />

TB-1 - POWER CONNECTION OR DISCONNECT (in Main Control Box)<br />

11 L1 power supply 208-230/460/575/380/-3-60, 400-3-50<br />

TB1 12 L2 power supply 208-230/460/575/380/-3-60, 400-3-50<br />

13 L3 power supply 208-230/460/575/380/-3-60, 400-3-50<br />

NEUTRAL (in Main Control Box)<br />

Neutral 1 Neutral Power<br />

TB201 - FIELD CONNECTIONS (in Main Control Box)<br />

1 Smoke Detector Alarm Input external contact (maximum 24 vac, 3 A)<br />

2 Smoke Detector Alarm Input external contact (maximum 24 vac, 3 A)<br />

3 Remote Occupied/Economizer Enable 24 vac out 24 VAC Output<br />

4 Remote Occupied/Economizer Enable 24 vac in 24 VAC Input<br />

5 Outdoor Enthalpy Switch 24 VAC out 24 VAC Output<br />

6 Outdoor Enthalpy Switch 24 VAC in 24 VAC Input<br />

7<br />

Indoor Air IAQ Remote Sensor/Remote<br />

Pot/Remote 4-20 mA<br />

Thermistor input or externally powered 4 to 20 mA when used with<br />

180 ohm resistor<br />

8<br />

Indoor Air IAQ Remote Sensor/Remote<br />

Pot/Remote 4-20 mA<br />

Thermistor input or externally powered 4 to 20 mA when used with<br />

180 ohm resistor<br />

9 VAV Heater Interlock Relay Contact (maximum 24 vac, 3 A)<br />

10 VAV Heater Interlock Relay Contact (maximum 24 vac, 3 A)<br />

R 24 VAC Power 24 VAC Output<br />

Y1 Thermostat Y1 (1st stage cool) 24 VAC Input<br />

Y2 Thermostat Y2 (2nd stage cool) 24 VAC Input<br />

W1 Thermostat W1 (1st stage heat) 24 VAC Input<br />

TB201 W2 Thermostat W2 (2nd stage heat) 24 VAC Input<br />

G Thermostat G (Fan) 24 VAC Input<br />

C 24 VAC Common 24 VAC Output<br />

X Alarm Output (NO) 24 VAC Output<br />

FS1 Fire Shut Down external contact (maximum 24 vac, 3 A)<br />

FS2 Fire Shut Down external contact (maximum 24 vac, 3 A)<br />

T55-1 Space Sensor TH Thermistor Input<br />

T55-2 Space Sensor COM Thermistor Input<br />

T55-3 Space Sensor Offset Switch Thermistor Input<br />

HUM1 Humidifier Output Contact (maximum 24 vac, 3 A)<br />

HUM2 Humidifier Output Contact (maximum 24 vac, 3 A)<br />

(+) CCN + Communication<br />

(COM) CCN Common Communication<br />

(-) CCN - Communication<br />

SHIELD Ground Ground<br />

LEN Local Equipment Network Communication<br />

CCN Carrier Comfort Network Communication<br />

TB202 - FIELD CONNECTIONS CEM (in Main Control Box)<br />

1 Not Used —<br />

2 Not Used —<br />

3 Space Humidity 4-20 mA (-) 4 - 20 mA signal<br />

4 Space Humidity 4-20 mA (+) 4 - 20 mA loop power<br />

5 Ground Ground<br />

6 Outdoor Air IAQ 4-20 mA (-) 4 - 20 mA signal<br />

7 Outdoor Air IAQ 4-20 mA (+) 4 - 20 mA loop power<br />

8 Supply Air Reset 4-20 mA (-) 4 - 20 mA signal<br />

9 Supply Air Reset 4-20 mA (+) 4 - 20 mA loop power<br />

10 Dem<strong>and</strong> Limit 4-20 mA (-) 4 - 20 mA signal<br />

11 Dem<strong>and</strong> Limit 4-20 mA (+) 4 - 20 mA loop power<br />

12 IAQ Switch 24 VAC in external contact (maximum 24 vac, 3 A)<br />

TB202 13 IAQ Switch 24 VAC out external contact (maximum 24 vac, 3 A)<br />

14 Fire Smoke Purge 24 VAC in external contact (maximum 24 vac, 3 A)<br />

15 Fire Smoke Purge 24 VAC out external contact (maximum 24 vac, 3 A)<br />

16 Fire Evacuation 24 VAC in external contact (maximum 24 vac, 3 A)<br />

17 Fire Evacuation 24 VAC out external contact (maximum 24 vac, 3 A)<br />

18 Fire Pressurization 24 VAC in external contact (maximum 24 vac, 3 A)<br />

19 Fire Pressurization 24 VAC out external contact (maximum 24 vac, 3 A)<br />

20 Dem<strong>and</strong> Limit Loadshed 24 VAC in external contact (maximum 24 vac, 3 A)<br />

21 Dem<strong>and</strong> Limit Loadshed 24 VAC out external contact (maximum 24 vac, 3 A)<br />

22 Dem<strong>and</strong> Limit Redline 24 VAC in external contact (maximum 24 vac, 3 A)<br />

23 Dem<strong>and</strong> Limit Redline 24 VAC out external contact (maximum 24 vac, 3 A)<br />

24 Humidistat external contact (maximum 24 vac, 3 A)<br />

25 Humidistat external contact (maximum 24 vac, 3 A)<br />