APPENDIX B — CCN TABLES (cont)<br />

MAINTENANCE DISPLAY TABLES<br />

TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />

ALARMS01<br />

Active Alarm ascii ALARM_01<br />

------------------------ ascii<br />

Active Alarm ascii ALARM_02<br />

------------------------ ascii<br />

Active Alarm ascii ALARM_03<br />

------------------------ ascii<br />

Active Alarm ascii ALARM_04<br />

------------------------ ascii<br />

follow same format for…<br />

ALARMS02 to ALARMS05<br />

BEL_ACTU<br />

Economizer Act.Curr.Pos. 0-100 % ECONOPOS<br />

Economzr 2 Act.Curr.Pos. 0-100 % ECON2POS<br />

Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible<br />

Economzr 2 Act.Curr.Pos. 0-100 % ECN2RPOS<br />

Econ Comm<strong>and</strong> Position 0-100 % ECN2CPOS<br />

Humidifer Act.Curr.Pos. 0-100 % HUMDRPOS<br />

Humidifier Comm<strong>and</strong> Pos. 0-100 % HUMDCPOS<br />

Ht.Coil Act.Current Pos. 0-100 % HTCLRPOS<br />

Ht.Coil Comm<strong>and</strong> Position 0-100 % HTCLCPOS<br />

BP 1 Actuator Curr.Pos. 0-100 % BP1_RPOS<br />

BP 1 Comm<strong>and</strong> Position 0-100 % BP1_CPOS<br />

BP 2 Actuator Curr.Pos. 0-100 % BP2_RPOS<br />

BP 2 Comm<strong>and</strong> Position 0-100 % BP2_CPOS<br />

COMPRESR<br />

Compressor A1 Relay On/Off CMPA1<br />

Compressor A1 Capacity % CMPA1CAP<br />

Circ A High Press.Switch On/Off CIRCAHPS<br />

Compressor A1 Feedback On/Off CSB_A1<br />

Curr.Sens.Brd. A1 Status ascii CSBA1ASC<br />

CSB A1 Feedback Alarm Enable/Disable CSB_A1EN config<br />

Comp A1 Locked Out ? Yes/No CMPA1LOK<br />

Compressor A1 Strikes CMPA1STR<br />

Enable Compressor A1 Enable/Disable CMPA1ENA config<br />

Compressor A2 Relay On/Off CMPA2<br />

Compressor A2 Feedback On/Off CSB_A2<br />

Curr.Sens.Brd. A2 Status ascii CSBA2ASC<br />

CSB A2 Feedback Alarm Enable/Disable CSB_A2EN config<br />

Comp A2 Locked Out ? Yes/No CMPA2LOK<br />

Compressor A2 Strikes CMPA2STR<br />

Enable Compressor A2 Enable/Disable CMPA2ENA config<br />

Compressor A3 Relay On/Off CMPA3<br />

Compressor A3Feedback On/Off CSB_A3<br />

Curr.Sens.Brd. A3 Status ascii CSBA3ASC<br />

CSB A3 Feedback Alarm Enable/Disable CSB_A3EN config<br />

Comp A3 Locked Out ? Yes/No CMPA3LOK<br />

Compressor A3 Strikes CMPA3STR<br />

Enable Compressor A3 Enable/Disable CMPA3ENA config<br />

Compressor B1 Relay On/Off CMPB1<br />

Circ B High Press.Switch On/Off CIRCBHPS<br />

Compressor B1 Feedback On/Off CSB_B1<br />

Curr.Sens.Brd. B1 Status ascii CSBB1ASC<br />

CSB B1 Feedback Alarm Enable/Disable CSB_B1EN config<br />

Comp B1 Locked Out ? Yes/No CMPB1LOK<br />

Compressor B1 Strikes CMPB1STR<br />

Enable Compressor B1 Enable/Disable CMPB1ENA config<br />

Compressor B2 Relay On/Off CMPB2<br />

Compressor B2 Feedback On/Off CSB_B2<br />

Curr.Sens.Brd. B2 Status ascii CSBB2ASC<br />

CSB B2 Feedback Alarm Enable/Disable CSB_B2EN config<br />

Comp B2 Locked Out ? Yes/No CMPB2LOK<br />

Compressor B2 Strikes CMPB2STR<br />

Enable Compressor B2 Enable/Disable CMPB2ENA config<br />

Compressor B3 Relay On/Off CMPB3<br />

Compressor B3 Feedback On/Off CSB_B3<br />

Curr.Sens.Brd. B3 Status ascii CSBB3ASC<br />

CSB B3 Feedback Alarm Enable/Disable CSB_B3EN config<br />

Comp B3 Locked Out ? Yes/No CMPB3LOK<br />

Compressor B3 Strikes CMPB3STR<br />

Enable Compressor B3 Enable/Disable CMPB3ENA config<br />