06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

NOTE: “Error” is clamped between –10 <strong>and</strong> +50 <strong>and</strong> “Error<br />

rate” is clamped between –5 <strong>and</strong> +5.<br />

This “SUM” will be compared against the “Z” calculations<br />

in determining whether cooling stages should be added or<br />

subtracted.<br />

Z Calculation — For the “Z” calculation, the control attempts<br />

to determine the entering <strong>and</strong> the leaving-air temperature of the<br />

evaporator coil <strong>and</strong> based upon the difference between the two<br />

during mechanical cooling, determines whether to add or<br />

subtract a stage of cooling. This is the adaptive element.<br />

The entering-air temperature is referred to as MAT<br />

(mixed-air temperature) <strong>and</strong> the leaving-air temperature of the<br />

evaporator coil is referred to as EDT (evaporator discharge<br />

temperature). They are found at the local display under the<br />

TemperaturesCTRL sub-menu.<br />

The main elements to be calculated <strong>and</strong> used in the calculation<br />

of SumZ are:<br />

1) the rise per percent capacity (R.PCT)<br />

2) the amount of expected rise for the next cooling stage<br />

addition<br />

3) the amount of expected rise for the next cooling stage<br />

subtraction<br />

The calculation of “Z” requires two variables, Z.PLU used<br />

when adding a stage <strong>and</strong> Z.MIN used when subtracting a stage.<br />

They are calculated with the following formulas:<br />

Z.PLU = Z.GN * (10 + (4*(–ADD.R))) * 0.6<br />

Z.MIN = Z.GN * (–10 + (4*(–SUB.R))) * 0.6<br />

Where:<br />

Z.GN = configuration used to modify the threshold levels used<br />

for staging (ConfigurationCOOLZ.GN)<br />

ADD.R = R.PCT * (C.CAP – capacity after adding a cooling<br />

stage)<br />

SUB.R = R.PCT * (C.CAP – capacity after subtracting a cooling<br />

stage)<br />

Both of these terms, Z.PLU <strong>and</strong> Z.MIN, represent a threshold<br />

both positive <strong>and</strong> negative upon which the “SUM” calculation<br />

must build up to in order to cause the compressor to stage<br />

up or down.<br />

Comparing SUM <strong>and</strong> Z — The “SUM” calculation is compared<br />

against Z.PLU <strong>and</strong> Z.MIN.<br />

• If “SUM” rises above Z.PLU, a cooling stage is added.<br />

• If “SUM” falls below Z.MIN, a cooling stage is subtracted.<br />

There is a variable called SMZ which is described in the<br />

reference section <strong>and</strong> which can simplify the task of watching<br />

the dem<strong>and</strong> build up or down over time. It is calculated as<br />

follows:<br />

If SUM is positive: SMZ = 100*(SUM/Z.PLU)<br />

If SUM is negative: SMZ = 100*(SUM/Z.MIN)<br />

Mixed Air Temperature Calculation (MAT) — The mixedair<br />

temperature is calculated <strong>and</strong> is a function of the economizer<br />

position. Additionally there are some calculations in the control<br />

which can zero in over time on the relationship of return<br />

<strong>and</strong> outside air as a function of economizer position. There are<br />

two configurations which relate to the calculation of “MAT”.<br />

These configurations can be located at the local display under<br />

ConfigurationUNIT.<br />

ITEM EXPANSION RANGE<br />

CCN<br />

POINT<br />

DEFAULTS<br />

UNIT UNIT CONFIGURATION<br />

MAT.S MAT Calc Config 0 - 2 MAT_SEL 1<br />

MAT.R Reset MAT Table<br />

Entries?<br />

Yes/No MATRESET No<br />

52<br />

MAT Calc Config (MAT.S) — This configuration gives the<br />

user three options in the processing of the mixed-air temperature<br />

(MAT) calculation:<br />

• MAT.S = 0<br />

There will be no MAT calculation.<br />

• MAT.S = 1<br />

The control will attempt to learn MAT over time. Any time<br />

the system is in a vent mode <strong>and</strong> the economizer stays at a<br />

particular position for long enough, MAT = EDT. Using<br />

this, the control has an internal table whereby it can more<br />

closely determine the true MAT value.<br />

• MAT.S = 2<br />

The control will stop learning <strong>and</strong> use whatever the control<br />

has already learned. Using this setting infers that the control<br />

has spent some time set to MAT.S = 1.<br />

First set MAT.S = 1. Then go into the <strong>Service</strong> Test mode,<br />

turn on the fan <strong>and</strong> open the economizer to a static position for<br />

5 minutes. Move to several positions (20%,40%,60%,80%). It<br />

is important that the difference between return <strong>and</strong> outside<br />

temperature be greater than 5 degrees. (The greater the delta,<br />

the better). When done, set MAT.S = 2 <strong>and</strong> the system has been<br />

commissioned.<br />

Reset MAT Table Entries? (MAT.R) — This configuration<br />

allows the user to reset the internally stored MAT learned<br />

configuration data back to the default values. The defaults are<br />

set to a linear relationship between the economizer damper<br />

position <strong>and</strong> OAT <strong>and</strong> RAT in the calculation of MAT.<br />

SumZ Overrides — There are a number of overrides to the<br />

SumZ algorithm which may add or subtract stages of cooling.<br />

• High Temp Cap Override (H.TMP)<br />

• Low Temp Cap Override (L.TMP)<br />

• Pull Down Cap Override (PULL)<br />

• Slow Change Cap Override (SLOW)<br />

Economizer Trim Override — The unit may drop stages of<br />

cooling when the economizer is performing free cooling <strong>and</strong><br />

the configuration ConfigurationECONE.TRM is set to<br />

Yes. The economizer controls to the same supply air set point<br />

as mechanical cooling does for SumZ when E.TRM = Yes.<br />

This allows for much tighter temperature control as well as cutting<br />

down on the cycling of compressors.<br />

For a long cooling session where the outside-air temperature<br />

may drop over time, there may be a point at which the<br />

economizer has closed down far enough were the unit could<br />

remove a cooling stage <strong>and</strong> open up the economizer further to<br />

make up the difference.<br />

Mechanical Cooling Lockout (ConfigurationCOOL<br />

MC.LO) — This configuration allows a configurable outsideair<br />

temperature set point below which mechanical cooling will<br />

be completely locked out.<br />

DEMAND LIMIT CONTROL — Dem<strong>and</strong> Limit Control<br />

may override the cooling algorithm <strong>and</strong> clamp or shed<br />

cooling capacity during run time. The term Dem<strong>and</strong> Limit<br />

Control refers to the restriction of the machine capacity<br />

to control the amount of power that a machine will use.<br />

Dem<strong>and</strong> limit control is intended to interface with an external<br />

Loadshed Device either through CCN communications, external<br />

switches, or 4 to 20 mA input.<br />

The control has the capability of loadshedding <strong>and</strong> limiting<br />

in 3 ways:<br />

• Two discrete inputs tied to configurable dem<strong>and</strong> limit set<br />

point percentages.<br />

• An external 4 to 20 mA input that can reset capacity back<br />

linearly to a set point percentage.<br />

• CCN loadshed functionality.<br />

NOTE: It is also possible to force the dem<strong>and</strong> limit variable<br />

(Run StatusCOOLDEM.L).

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!