06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

T072 (Evaporator Discharge Reset Sensor Failure) — This<br />

sensor is responsible for third party reset of the cooling supply<br />

air set point. If the unit is configured for “third party reset”<br />

(ConfigurationEDT.RRS.CF=3) <strong>and</strong> this alert occurs, no<br />

reset will be applied to the cooling supply air set point. Recovery<br />

from this alert is automatic. Reason for error is either a<br />

faulty sensor, wiring error, or damaged input on the CEM<br />

board.<br />

T073 (Outside Air Temperature Thermistor Failure) — Failure<br />

of this thermistor (TemperaturesAIR.TOAT) will disable<br />

any elements of the control which requires its use. Economizer<br />

control beyond the vent position <strong>and</strong> the calculation of<br />

mixed air temperature for the SumZ algorithm will not be possible.<br />

Recovery from this alert is automatic. Reason for error is<br />

either a faulty thermistor, wiring error, or damaged input on the<br />

MBB control board.<br />

T074 (Space Temperature Thermistor Failure) — Failure of<br />

this thermistor (TemperaturesAIR.TSPT) will disable<br />

any elements of the control which requires its use. If the unit is<br />

configured for SPT 2 stage or SPT multi-stage operation <strong>and</strong><br />

the sensor fails, no cooling or heating mode may be chosen.<br />

Recovery from this alert is automatic. Reason for error is either<br />

a faulty thermistor in the T55, T56 or T58 device, wiring error,<br />

or damaged input on the MBB control board.<br />

T075 (Return Air Thermistor Failure) — Failure of this<br />

thermistor (TemperaturesAIR.TRAT) will disable any elements<br />

of the control which requires its use. Elements of failure<br />

include:<br />

• the calculation of mixed air temperature for sumZ control<br />

• the selection of a mode for VAV units<br />

• economizer differential enthalpy or dry bulb control<br />

• RAT offset control for dehumidification<br />

• return air temperature supply air reset<br />

• fan tracking for building pressure control.<br />

Recovery from this alert is automatic. Reason for error is<br />

either a faulty thermistor, wiring error, or damaged input on the<br />

MBB control board.<br />

T076 (Outside Air Relative Humidity Sensor Failure) —<br />

Failure of this sensor (InputsREL.HOA.RH) will disable<br />

any elements of the control which requires its use. Elements of<br />

failure include: economizer outdoor <strong>and</strong> differential enthalpy<br />

control. Recovery from this alert shall be automatic. Reason for<br />

error is either a faulty sensor, wiring error or damaged input on<br />

the CEM control board.<br />

T077 (Space Relative Humidity Sensor Failure) — Failure<br />

of this sensor (InputsREL.HSP.RH) will disable any elements<br />

of the control which requires its use. Elements of failure<br />

include humidification <strong>and</strong> dehumidification. Recovery from<br />

this alert is automatic. Reason for error is either a faulty sensor,<br />

wiring error, or damaged input on the CEM control board.<br />

T078 (Return Air Relative Humidity Sensor Fail) — Failure<br />

of this sensor (InputsREL.HRA.RH) will disable any elements<br />

of the control which requires its use. Elements of failure<br />

include economizer differential enthalpy control, humidification,<br />

<strong>and</strong> dehumidification. Recovery from this alert is automatic.<br />

Reason for error is either a faulty sensor, wiring error, or<br />

damaged input on the CEM control board.<br />

T082 (Space Temperature Offset Sensor Failure) — When<br />

this failure occurs, there is no offset available that may be applied<br />

to space temperature. Recovery from this alert is automatic.<br />

Reason for error is either a faulty slider potentiometer, wiring<br />

error, or damaged input on the MBB control board.<br />

T090 (Circ A Discharge Press Transducer Failure)<br />

T091 (Circ B Discharge Press Transducer Failure) — The<br />

associated circuit becomes disabled whenever this transducer<br />

(PressuresREF.PDP.A, DP.B) fails. Recovery from this<br />

alert is automatic. Reason for error is either a faulty sensor, wiring<br />

error, or damaged input on the MBB control board.<br />

111<br />

T092 (Circ A Suction Press Transducer Failure)<br />

T093 (Circ B Suction Press Transducer Failure) — The associated<br />

circuit becomes disabled whenever this transducer<br />

(PressuresREF.PSP.A, SP.B) fails. Recovery from this<br />

alert is automatic. Reason for error is either a faulty sensor, wiring<br />

error, or damaged input on the MBB control board.<br />

T110 (Circuit A Loss of Charge)<br />

T111 (Circuit B Loss of Charge) — Alert codes 110 <strong>and</strong> 111<br />

are for circuits A <strong>and</strong> B respectively. These alerts occur when<br />

all the compressors on a circuit are OFF <strong>and</strong> the suction pressure<br />

is less than 18 psig, if the OAT is above –5 F for 1 continuous<br />

minute. The alert will automatically clear when the suction<br />

pressure transducer reading is valid <strong>and</strong> greater than<br />

54 psig. The cause of the alert is usually low refrigerant pressure<br />

or a faulty suction pressure transducer.<br />

P120 (Circuit A Low Saturated Suction Temp. Comp Shutdown)<br />

T120 (Circuit A Low Saturated Suction Temperature Alert)<br />

A120 (Circuit A Low Saturated Suction Temperature<br />

Alarm)<br />

P121 (Circuit B Low Saturated Suction Temp. Comp Shutdown)<br />

T121 (Circuit B Low Saturated Suction Temperature Alert)<br />

A121 (Circuit B Low Saturated Suction Temperature<br />

Alarm) — This alert/alarm is used to keep the evaporator coils<br />

from freezing <strong>and</strong> the saturated suction temperature above the<br />

low limit for the compressors.<br />

When TemperaturesREF.TSSTA or Temperatures<br />

REF.TSSTB is less than 20 F for 4 minutes, less than 10 F<br />

for 2 minutes, less than 0° F for 1 minute, or less than –20 F for<br />

20 seconds continuously, a compressor of the affected circuit<br />

will be shut down with a local pre-alert (P120, P121) <strong>and</strong> a<br />

15-minute timeguard will be added to the compressor. If the<br />

saturated suction temperature continues to be less than 20 F for<br />

4 minutes, less than 10 F for 2 minutes, less than 0° F for 1<br />

minute, or less than –20 F for 20 seconds continuously, another<br />

compressor of the affected circuit, if it exists, will be shut down<br />

with a local pre-alert (P120, P121) <strong>and</strong> a 15-minute timeguard<br />

will be added to the compressor. This sequence will continue<br />

until the last compressor on the circuit is shutdown, at which<br />

time the circuit will be shut down with alert (T120, T121).<br />

This failure follows a 3-strike methodology. When the circuit<br />

is shutdown entirely, an alert (T120, T121) is generated<br />

<strong>and</strong> a strike is logged on the circuit. The Alert <strong>and</strong> strikes<br />

logged will automatically reset if the saturated suction temperature<br />

remains above 29.4 F for 15 minutes. On the third strike,<br />

alarm (A120, A121) will be generated which will necessitate a<br />

manual reset to get the circuit back running. It is important to<br />

note that a strike is called out only if all compressors in the circuit<br />

are off at the time of alert.<br />

To prevent nuisance alerts, P120 <strong>and</strong> P121 show up in the<br />

alarm history <strong>and</strong> locally at the display, but are never broadcast<br />

to the network. To recover from these pre-alerts, both a 15 minute<br />

hold off timer <strong>and</strong> saturated suction temperature rising<br />

above 29.4 F must occur. If recovery occurs, staging will be allowed<br />

on the circuit once again. A strike is tied to the circuit<br />

going off entirely, not reducing capacity <strong>and</strong> recovering. Therefore<br />

it is possible that multiple P120 <strong>and</strong> P121 alerts may be<br />

stored in alarm history but not broadcast.<br />

T122 (Circuit A High Saturated Suction Temperature)<br />

T123 (Circuit B High Saturated Suction Temperature) —<br />

This alert is for display purposes only. No action is taken by the<br />

control when the alert occurs.<br />

When TemperaturesREF.TSSTA or Temperatures<br />

REF.TSSTB is greater than 70 F for Configuration<br />

COOLH.SST minutes, local alert T122 or T123 will occur.<br />

The alerts automatically reset when the corresponding saturated<br />

suction temperature drops below 70 F.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!