Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
value (60%) but not more than the maximum value (90% or negligible<br />
static pressure drop). This is a dynamic calculation, which<br />
occurs every two minutes whenever the system is operating. It<br />
ensures that the supply static is sufficient to supply the required<br />
airflow at the worst case terminal but not more than necessary, so<br />
that the air terminals do not have to operate with a pressure drop<br />
greater than required to maintain the airflow set point of each individual<br />
terminal in the system. As the system operates, if the<br />
most open damper opens more than 90%, the system recalculates<br />
the pressure reduction variable <strong>and</strong> Configuration<br />
SPSENSSP.RS, the amount of reset, is reduced. If the<br />
most open damper closes to less than 60%, the system recalculates<br />
the pressure reduction variable <strong>and</strong> SP.RS is increased.<br />
With this system, one needs to enter as the static pressure set<br />
point SP.SP either a maximum duct design pressure or maximum<br />
equipment pressure, whichever is less. The system will<br />
determine the actual set point required <strong>and</strong> deliver the required<br />
airflow to every terminal under the current load conditions. As<br />
the conditions <strong>and</strong> airflow requirements at each terminal<br />
change throughout the operating period, so will SP.RS <strong>and</strong> the<br />
unit’s effective static pressure set point.<br />
In the unlikely chance that both static pressure reset control<br />
signals are simultaneously present, the CCN signal will take<br />
precedence.<br />
RELATED POINTS — These points represent static pressure<br />
control <strong>and</strong> static pressure reset inputs <strong>and</strong> outputs. See Table 51.<br />
Static Pressure mA (SP.M) — This variable reflects the value<br />
of the static pressure sensor signal received by the<br />
ComfortLink controls. It may in some cases be helpful in<br />
troubleshooting.<br />
Static Pressure mA Trim (SP.M.T) — This input allows a<br />
modest amount of trim to the 4 to 20 mA static pressure transducer<br />
signal, <strong>and</strong> can be used to calibrate a transducer.<br />
Static Pressure Reset mA (SP.R.M) — This input reflects the<br />
value of a 4 to 20 mA static pressure reset signal applied to<br />
TB202 terminals 6 <strong>and</strong> 7, from a third party control system.<br />
Static Pressure Reset (SP.RS) — This variable reflects the<br />
value of a static pressure reset signal applied from a CCN system.<br />
The means of applying this reset is by forcing the value of<br />
the variable SPRESET through CCN.<br />
Supply Fan VFD Speed (S.VFD) — This output can be used<br />
to check on the actual speed of the VFD. This may be helpful<br />
in some cases for troubleshooting.<br />
Fan Status Monitoring<br />
GENERAL — The P Series ComfortLink controls offer the<br />
capability to detect a failed supply fan through either a duct<br />
static pressure transducer or an accessory discrete switch. The<br />
fan status switch accessory (part no. CRFANSTATUS001A00)<br />
allows for the discrete monitoring of the ON/OFF status of the<br />
the unit supply fan. The switch closes when the delta pressure<br />
across the switch rises above a configurable threshold value.<br />
The switch connects to plug PL34, which is located in the supply<br />
fan compartment. See Carrier accessory literature for more<br />
details. For any unit with a factory-installed duct static pressure<br />
sensor, it is possible to measure duct pressure rise directly,<br />
Table 51 — Static Pressure Reset Related Points<br />
66<br />
which removes the need for a differential switch. Any unit with<br />
an installed supply fan VFD will have the duct static pressure<br />
sensor as st<strong>and</strong>ard.<br />
SETTING UP THE SYSTEM — The fan status monitoring<br />
configurations are located in ConfigurationUNIT. See<br />
Table 52.<br />
Table 52 — Fan Status Monitoring Configuration<br />
ITEM EXPANSION RANGE CCN POINT<br />
SFS.S Fan Fail Shuts Down Unit Yes/No SFS_SHUT<br />
SFS.M Fan Stat Monitoring Type 0 - 2 SFS_MON<br />
Fan Stat Monitoring Type (SFS.M) — This configuration selects<br />
the type of fan status monitoring to be performed.<br />
0 - NONE — No switch or monitoring<br />
1 - SWITCH — Use of the fan status switch<br />
2 - SP RISE — Monitoring of the supply duct pressure.<br />
Fan Fail Shuts Down Unit (SFS.S) — This configuration<br />
will configure the unit to shut down on a supply fan status fail<br />
or simply alert the condition <strong>and</strong> continue to run. When configured<br />
to YES, the control will shut down the unit if supply fan<br />
status monitoring fails <strong>and</strong> send out an alarm. If set to no, the<br />
control will not shut down the unit if supply fan status monitoring<br />
fails but send out an alert.<br />
SUPPLY FAN STATUS MONITORING LOGIC — Regardless<br />
of whether the user is monitoring a discrete switch or is<br />
monitoring static pressure, the timings for both techniques are<br />
the same <strong>and</strong> rely upon the configuration of static pressure<br />
control. The configuration that determines static pressure<br />
control is ConfigurationSPSP.CF. If this configuration is<br />
set to 0 (none), a fan failure condition must wait 60 continuous<br />
seconds before taking action. If this configuration is 1 (VFD), a<br />
fan failure condition must wait 3 continuous minutes before<br />
taking action.<br />
If the unit is configured to monitor a fan status switch<br />
(SFS.M = 1), <strong>and</strong> if the supply fan comm<strong>and</strong>ed state does not<br />
match the supply fan status switch for 3 continuous minutes,<br />
then a fan status failure has occurred.<br />
If the unit is configured for supply duct pressure monitoring<br />
(SFS.M = 2), then<br />
• If the supply fan is requested ON <strong>and</strong> the static pressure<br />
reading is not greater than 0.2 in. wg for 3 continuous<br />
minutes, a fan failure has occurred.<br />
• If the supply fan is requested OFF <strong>and</strong> the static pressure<br />
reading is not less than 0.2-in. wg for 3 continuous minutes,<br />
a fan failure has occurred.<br />
Dirty Filter Switch — The unit can be equipped with a<br />
field-installed accessory dirty filter switch. The switch is located<br />
in the filter section. If a dirty filter switch is not installed, the<br />
switch input is configured to read “clean” all the time.<br />
To enable the sensor for dirty filter monitoring set<br />
ConfigurationUNITSENSFLT.S to ENABLE. The<br />
state of the filter status switch can be read at InputsGEN.I<br />
FLT.S. See Table 53.<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
Inputs<br />
4-20 SP.M Static Pressure mA 4-20 mA SP_MA<br />
4-20 SP.M.T Static Pressure mA Trim -2.0 +2.0 mA SPMATRIM<br />
4-20 SP.R.M Static Pressure Reset mA 4-20 mA SPRST_MA 0.0<br />
RSET SP.RS<br />
Outputs<br />
Static Pressure Reset 0.0-3.0 in. wg SPRESET 0.0<br />
FANS S.VFD Supply Fan VFD Speed 0-100 % SFAN_VFD