06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

value (60%) but not more than the maximum value (90% or negligible<br />

static pressure drop). This is a dynamic calculation, which<br />

occurs every two minutes whenever the system is operating. It<br />

ensures that the supply static is sufficient to supply the required<br />

airflow at the worst case terminal but not more than necessary, so<br />

that the air terminals do not have to operate with a pressure drop<br />

greater than required to maintain the airflow set point of each individual<br />

terminal in the system. As the system operates, if the<br />

most open damper opens more than 90%, the system recalculates<br />

the pressure reduction variable <strong>and</strong> Configuration<br />

SPSENSSP.RS, the amount of reset, is reduced. If the<br />

most open damper closes to less than 60%, the system recalculates<br />

the pressure reduction variable <strong>and</strong> SP.RS is increased.<br />

With this system, one needs to enter as the static pressure set<br />

point SP.SP either a maximum duct design pressure or maximum<br />

equipment pressure, whichever is less. The system will<br />

determine the actual set point required <strong>and</strong> deliver the required<br />

airflow to every terminal under the current load conditions. As<br />

the conditions <strong>and</strong> airflow requirements at each terminal<br />

change throughout the operating period, so will SP.RS <strong>and</strong> the<br />

unit’s effective static pressure set point.<br />

In the unlikely chance that both static pressure reset control<br />

signals are simultaneously present, the CCN signal will take<br />

precedence.<br />

RELATED POINTS — These points represent static pressure<br />

control <strong>and</strong> static pressure reset inputs <strong>and</strong> outputs. See Table 51.<br />

Static Pressure mA (SP.M) — This variable reflects the value<br />

of the static pressure sensor signal received by the<br />

ComfortLink controls. It may in some cases be helpful in<br />

troubleshooting.<br />

Static Pressure mA Trim (SP.M.T) — This input allows a<br />

modest amount of trim to the 4 to 20 mA static pressure transducer<br />

signal, <strong>and</strong> can be used to calibrate a transducer.<br />

Static Pressure Reset mA (SP.R.M) — This input reflects the<br />

value of a 4 to 20 mA static pressure reset signal applied to<br />

TB202 terminals 6 <strong>and</strong> 7, from a third party control system.<br />

Static Pressure Reset (SP.RS) — This variable reflects the<br />

value of a static pressure reset signal applied from a CCN system.<br />

The means of applying this reset is by forcing the value of<br />

the variable SPRESET through CCN.<br />

Supply Fan VFD Speed (S.VFD) — This output can be used<br />

to check on the actual speed of the VFD. This may be helpful<br />

in some cases for troubleshooting.<br />

Fan Status Monitoring<br />

GENERAL — The P Series ComfortLink controls offer the<br />

capability to detect a failed supply fan through either a duct<br />

static pressure transducer or an accessory discrete switch. The<br />

fan status switch accessory (part no. CRFANSTATUS001A00)<br />

allows for the discrete monitoring of the ON/OFF status of the<br />

the unit supply fan. The switch closes when the delta pressure<br />

across the switch rises above a configurable threshold value.<br />

The switch connects to plug PL34, which is located in the supply<br />

fan compartment. See Carrier accessory literature for more<br />

details. For any unit with a factory-installed duct static pressure<br />

sensor, it is possible to measure duct pressure rise directly,<br />

Table 51 — Static Pressure Reset Related Points<br />

66<br />

which removes the need for a differential switch. Any unit with<br />

an installed supply fan VFD will have the duct static pressure<br />

sensor as st<strong>and</strong>ard.<br />

SETTING UP THE SYSTEM — The fan status monitoring<br />

configurations are located in ConfigurationUNIT. See<br />

Table 52.<br />

Table 52 — Fan Status Monitoring Configuration<br />

ITEM EXPANSION RANGE CCN POINT<br />

SFS.S Fan Fail Shuts Down Unit Yes/No SFS_SHUT<br />

SFS.M Fan Stat Monitoring Type 0 - 2 SFS_MON<br />

Fan Stat Monitoring Type (SFS.M) — This configuration selects<br />

the type of fan status monitoring to be performed.<br />

0 - NONE — No switch or monitoring<br />

1 - SWITCH — Use of the fan status switch<br />

2 - SP RISE — Monitoring of the supply duct pressure.<br />

Fan Fail Shuts Down Unit (SFS.S) — This configuration<br />

will configure the unit to shut down on a supply fan status fail<br />

or simply alert the condition <strong>and</strong> continue to run. When configured<br />

to YES, the control will shut down the unit if supply fan<br />

status monitoring fails <strong>and</strong> send out an alarm. If set to no, the<br />

control will not shut down the unit if supply fan status monitoring<br />

fails but send out an alert.<br />

SUPPLY FAN STATUS MONITORING LOGIC — Regardless<br />

of whether the user is monitoring a discrete switch or is<br />

monitoring static pressure, the timings for both techniques are<br />

the same <strong>and</strong> rely upon the configuration of static pressure<br />

control. The configuration that determines static pressure<br />

control is ConfigurationSPSP.CF. If this configuration is<br />

set to 0 (none), a fan failure condition must wait 60 continuous<br />

seconds before taking action. If this configuration is 1 (VFD), a<br />

fan failure condition must wait 3 continuous minutes before<br />

taking action.<br />

If the unit is configured to monitor a fan status switch<br />

(SFS.M = 1), <strong>and</strong> if the supply fan comm<strong>and</strong>ed state does not<br />

match the supply fan status switch for 3 continuous minutes,<br />

then a fan status failure has occurred.<br />

If the unit is configured for supply duct pressure monitoring<br />

(SFS.M = 2), then<br />

• If the supply fan is requested ON <strong>and</strong> the static pressure<br />

reading is not greater than 0.2 in. wg for 3 continuous<br />

minutes, a fan failure has occurred.<br />

• If the supply fan is requested OFF <strong>and</strong> the static pressure<br />

reading is not less than 0.2-in. wg for 3 continuous minutes,<br />

a fan failure has occurred.<br />

Dirty Filter Switch — The unit can be equipped with a<br />

field-installed accessory dirty filter switch. The switch is located<br />

in the filter section. If a dirty filter switch is not installed, the<br />

switch input is configured to read “clean” all the time.<br />

To enable the sensor for dirty filter monitoring set<br />

ConfigurationUNITSENSFLT.S to ENABLE. The<br />

state of the filter status switch can be read at InputsGEN.I<br />

FLT.S. See Table 53.<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

Inputs<br />

4-20 SP.M Static Pressure mA 4-20 mA SP_MA<br />

4-20 SP.M.T Static Pressure mA Trim -2.0 +2.0 mA SPMATRIM<br />

4-20 SP.R.M Static Pressure Reset mA 4-20 mA SPRST_MA 0.0<br />

RSET SP.RS<br />

Outputs<br />

Static Pressure Reset 0.0-3.0 in. wg SPRESET 0.0<br />

FANS S.VFD Supply Fan VFD Speed 0-100 % SFAN_VFD

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!