APPENDIX A — LOCAL DISPLAY TABLES (cont)<br />
MODE — INPUTS<br />
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />
GEN.I GENERAL INPUTS<br />
FLT.S Filter Status Input DRTY/CLN FLTS forcible<br />
G.FAN Fan Request From IGC ON/OFF IGCFAN<br />
REMT Remote Input State * RMTIN forcible<br />
ENTH Enth. Switch Read High ? YES/NO ENTH forcible<br />
S.FN.S Supply Fan Status Switch ON/OFF SFS forcible<br />
FRZ.S Freeze Status Switch ALRM/NORM FRZ forcible<br />
PP.SW Plenum Press.Safety Sw. HIGH/LOW PPS forcible<br />
DL.S1 Dem<strong>and</strong> Limit Switch 1 ON/OFF DMD_SW1 forcible<br />
DL.S2 Dem<strong>and</strong> Limit Switch 2 ON/OFF DMD_SW2 forcible<br />
DH.IN Dehumidify Switch Input ON/OFF DHDISCIN forcible<br />
FD.BK COMPRESSOR FEEDBACK<br />
HPS.A Circ A High Press. Switch HIGH/LOW CIRCAHPS<br />
HPS.B Circ B High Press. Switch HIGH/LOW CIRCBHPS<br />
CS.A1 Compressor A1 Feedback ON/OFF CSB_A1<br />
CS.A2 Compressor A2 Feedback ON/OFF CSB_A2<br />
CS.A3 Compressor A3 Feedback ON/OFF CSB_A3<br />
CS.B1 Compressor B1 Feedback ON/OFF CSB_B1<br />
CS.B2 Compressor B2 Feedback ON/OFF CSB_B2<br />
CS.B3 Compressor B3 Feedback ON/OFF CSB_B3<br />
STAT THERMOSTAT INPUTS<br />
G Thermostat G Input ON/OFF G forcible<br />
W1 Thermostat W1 Input ON/OFF W1 forcible<br />
W2 Thermostat W2 Input ON/OFF W2 forcible<br />
Y1 Thermostat Y1 Input ON/OFF Y1 forcible<br />
Y2 Thermostat Y2 Input ON/OFF Y2 forcible<br />
FIRE FIRE-SMOKE INPUTS<br />
FSD Fire Shutdown Input ALRM/NORM FSD forcible<br />
PRES Pressurization Input ALRM/NORM PRES forcible<br />
EVAC Evacuation Input ALRM/NORM EVAC forcible<br />
PURG Smoke Purge Input ALRM/NORM PURG forcible<br />
REL.H RELATIVE HUMIDITY<br />
OA.RH Outside Air Rel. Humidity % OARH forcible<br />
OA.EN Outdoor Air Enthalpy OAE<br />
OA.DP OutsideAir Dewpoint Temp dF OADEWTMP<br />
RA.RH Return Air Rel. Humidity % RARH forcible<br />
RA.EN Return Air Enthalpy RAE<br />
SP.RH Space Relative Humidity % SPRH forcible<br />
SP.EN Space Enthalpy SPE<br />
AIR.Q AIR QUALITY SENSORS<br />
IAQ.I IAQ - Discrete Input HIGH/LOW IAQIN forcible<br />
IAQ IAQ - PPM Return CO2 IAQ forcible<br />
OAQ OAQ - PPM Return CO2 OAQ forcible<br />
DAQ Diff.Air Quality in PPM DAQ<br />
IQ.P.O IAQ Min.Pos. Override % IAQMINOV forcible<br />
CFM CFM SENSORS<br />
O.CFM Outside Air CFM CFM OACFM<br />
R.CFM Return Air CFM CFM RACFM<br />
S.CFM Supply Air CFM CFM SACFM<br />
D.CFM Fan Track Control D.CFM CFM DELTACFM<br />
RSET RESET INPUTS<br />
SA.S.R Supply Air Setpnt. Reset ^F SASPRSET forcible<br />
SP.RS Static Pressure Reset SPRESET forcible<br />
4-20 4-20 MILLIAMP INPUTS<br />
IAQ.M IAQ Milliamps ma IAQ_MA<br />
OAQ.M OAQ Milliamps ma OAQ_MA<br />
SP.R.M SP Reset milliamps ma SPRST_MA<br />
DML.M 4-20 ma Dem<strong>and</strong> Signal ma DMDLMTMA forcible<br />
EDR.M EDT Reset Milliamps ma EDTRESMA<br />
ORH.M OARH Milliamps ma OARH_MA<br />
SRH.M SPRH Milliamps ma SPRH_MA<br />
RRH.M RARH Milliamps ma RARH_MA<br />
SAC.M SACFM Milliamps ma SACFM_MA<br />
SA.M.T Supply Air CFM Trim (ma) -2.0 2.0 SAMATRIM<br />
RAC.M RACFM Milliamps ma RACFM_MA<br />
RA.M.T Return Air CFM Trim (ma) -2.0 2.0 RAMATRIM config<br />
OAC.M OACFM Milliamps ma OACFM_MA<br />
OA.M.T Outside Air CFM Trim(ma) -2.0 2.0 OAMATRIM config<br />
BP.M BP Milliamps ma BP_MA<br />
BP.M.T Bldg. Pressure Trim (ma) -2.0 2.0 BPMATRIM config<br />
SP.M SP Milliamps ma SP_MA<br />
SP.M.T Static Press. Trim (ma) -2.0 2.0 SPMATRIM config<br />
*The display text changes depending on the remote switch configuration (ConfigurationUNITRM.CF). If RM.CF is set to 0 (No Remote Switch), then the display<br />
text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (<strong>Start</strong>/Stop),<br />
then the display text will be “Stop” or “<strong>Start</strong>.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”<br />
169