APPENDIX B — CCN TABLES (cont)<br />

MAINTENANCE DISPLAY TABLES (cont)<br />

TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />

COMPTRIP<br />

Comp. Security Password 0-10000 COMPPASS config<br />

Low Suction Trip Level 1 dF SSTLEV1<br />

Low Suction Trip Level 2 dF SSTLEV2<br />

Low Suction Trip Level 3 dF SSTLEV3<br />

Low Suction Trip Level 4 dF SSTLEV4<br />

Low Suction Clear Temp dF SSTOK<br />

Circuit A HPS Trip Press PSIG HPSATRIP<br />

Circuit B HPS Trip Press PSIG HPSBTRIP<br />

DMANDLIM<br />

Active Dem<strong>and</strong> Limit 0-100 % DEM_LIM forcible<br />

Current Running Capacity 0-100 % CAPTOTAL<br />

Dem<strong>and</strong> Limit Select 0-3 DMD_CTRL config<br />

Dem<strong>and</strong> Limit Switch 1 On/Off DMD_SW1 forcible<br />

Dem<strong>and</strong> Limit Switch 2 On/Off DMD_SW2 forcible<br />

Dem<strong>and</strong> Limit Sw.1 Setpt. 0-100 % DLSWSP1 config<br />

Dem<strong>and</strong> Limit Sw.2 Setpt. 0-100 % DLSWSP2 config<br />

4-20 ma Dem<strong>and</strong> Signal 4-20 ma DMDLMTMA forcible<br />

Dem<strong>and</strong> Limit at 20 ma 0-100 % DMT20MA config<br />

CCN Loadshed Signal 0-99 DL_STAT<br />

Loadshed Group Number 0-99 SHED_NUM config<br />

Loadshed Dem<strong>and</strong> Delta 0-60 % SHED_DEL config<br />

Maximum Loadshed Time 0-120 min SHED_TIM config<br />

ECON_MIN<br />

Economizer Act.Cmd.Pos. % ECONOCMD forcible<br />

Economizer Act.Curr.Pos. % ECONOPOS<br />

Economzr 2 Act.Curr.Pos. % ECON2POS<br />

Econo Current Min. Pos. % ECMINPOS<br />

Econo Current Min. CFM CFM ECMINCFM<br />

Outside Air CFM CFM OACFM<br />

Diff.Air Quality in PPM DAQ<br />

IAQ Min.Pos.Override % IAQMINOV forcible<br />

Econ Remote 10K Pot Val. ECON_POT forcible<br />

IAQ - PPM Return CO2 IAQ forcible<br />

OAQ - PPM Return CO2 OAQ forcible<br />

IAQ - Discrete Input IAQIN forcible<br />

IAQ Dem<strong>and</strong> Vent Min.Pos. % IAQMINP config<br />

Economizer Min.Position % ECONOMIN config<br />

IAQ Dem<strong>and</strong> Vent Min.Flow CFM OACFMMIN config<br />

Economizer Min.Flow CFM OACFMMAX config<br />

Econ OACFM MinPos Deadbd CFM OACFM_DB config<br />

IAQ Analog Sensor Config IAQANCFG config<br />

IAQ 4-20 ma Fan Config IAQANFAN config<br />

IAQ Discrete Input Confg IAQINCFG config<br />

IAQ Disc.In. Fan Config IAQINFAN config<br />

IAQ Econo Override Pos. % IAQOVPOS config<br />

Diff.Air Quality LoLimit DAQ_LOW config<br />

Diff.Air Quality HiLimit DAQ_HIGH config<br />

DAQ PPM Fan Off Setpoint DAQFNOFF config<br />

DAQ PPM Fan On Setpoint DAQFNON config<br />

Diff. AQ Responsiveness IAQREACT config<br />

IAQ Low Reference IAQREFL config<br />

IAQ High Reference IAQREFH config<br />

OAQ Lockout Value OAQLOCK config<br />

OAQ 4-20ma Sensor Config ma OAQANCFG config<br />

IAQ milliamps ma IAQ_MA<br />

OAQ milliamps OAQ_MA<br />