2. Under the Setpoints menu, set the following<br />

configurations:<br />

SA.HI Supply Air Set Point Hi<br />

SA.LO Supply Air Set Point Lo<br />

3. See the Economizer Options section on this page for additional<br />

economizer option configurations.<br />

4. See the Exhaust Options section on this page for additional<br />

exhaust option configurations.<br />

Multi-Stage Constant Volume Units with<br />

Space Sensor — To configure the unit, perform the<br />

following:<br />

1. Under ConfigurationUNITC.TYP, set C.TYP to 4<br />

(SPT MULTI).<br />

2. Under the Setpoints menu, the following configurations<br />

should be set:<br />

SA.HI Supply Air Set Point Hi<br />

SA.LO Supply Air Set Point Lo<br />

3. Under the Setpoints submenu, the heating <strong>and</strong> cooling set<br />

points must be configured:<br />

OHSP Occupied Heat Setpoint<br />

OCSP Occupied Cool Setpoint<br />

UHSP Unoccupied Heat Setpoint<br />

UCSP Unoccupied Cool Setpoint<br />

GAP Heat-Cool Setpoint Gap<br />

D.LV.T Cool/Heat Set Point Offsets (located in the<br />

Configuration menu)<br />

4. Under ConfigurationUNITSENSSPT.S, enable<br />

the space sensor by setting SPT.S to ENBL.<br />

5. Under ConfigurationUNITFN.MD, set FN.MD to<br />

1 for continuous fan or 0 for automatic fan.<br />

6. To program time schedules, set SCH.N=1 under ConfigurationCCNSC.OVSCH.N<br />

to configure the control<br />

to use local schedules.<br />

7. Under the TimeclockSCH.L submenu, enter the desired<br />

schedule. See Time Clock section for further<br />

descriptions of these configurations.<br />

8. See the Economizer Options section below for addition<br />

economizer option configurations.<br />

9. See the Exhaust Options section below for addition<br />

exhaust option configurations.<br />

Economizer Options — Under the Configuration<br />

ECON submenu, the following set points should be configured:<br />

EC.EN Economizer Enabled?<br />

EC2.E Econ Act.2 Installed?<br />

EC.MN Economizer Min.Position<br />

EC.MX Economizer Maximum Position<br />

E.TRM Economizer Trim for SumZ?<br />

E.SEL Econ Changeover Select<br />

OA.E.C OA Enthalpy Change Over Select<br />

OA.EN Outdoor Enthalpy Compare Value<br />

OAT.L High OAT Lockout Temp<br />

O.DEW OA Dew Point Temp Limit<br />

ORH.S Outside Air RH Sensor<br />

33<br />

ConfigurationECONEC.MN should always be set for<br />

the minimum damper position.<br />

If the unit is equipped with an outdoor air flow station, the<br />

following points in ConfigurationECONCFM.C need to<br />

be set.<br />

OCF.S Outdoor Air CFM Sensor<br />

O.C.MX Economizer Minimum Flow<br />

O.C.DB Economizer Minimum Flow Deadb<strong>and</strong><br />

If equipped with an outdoor flow station, make sure<br />

ConfigurationECONCFM.COCF.S is enabled. If an<br />

outdoor air cfm station is used, then the economizer will control<br />

to cfm, not a position, as long as the sensor is valid. Therefore,<br />

ConfigurationECONCFM.CO.C.MX supersedes<br />

ConfigurationECONEC.MN.<br />

Indoor Air Quality Options<br />

DEMAND CONTROL VENTILATION — Under ConfigurationIAQDCV.C,<br />

the following configuration parameters<br />

should be set to establish the minimum <strong>and</strong> maximum<br />

points for outdoor air damper position during dem<strong>and</strong> control<br />

ventilation (DCV):<br />

EC.MN Economizer Min.Position<br />

IAQ.M IAQ Dem<strong>and</strong> Vent Min.Pos.<br />

O.C.MX Economizer Min.Flow<br />

O.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow<br />

ConfigurationIAQDCV.CIAQ.M is used to set the<br />

absolute minimum vent position (or maximum reset) under<br />

DCV.<br />

ConfigurationIAQDCV.CEC.MN is used to set the<br />

minimum damper position (or with no DCV reset). This is also<br />

referenced in the economizer section.<br />

ConfigurationIAQDCV.CO.C.MX is used only<br />

with the outdoor airflow station <strong>and</strong> will supersede<br />

ConfigurationIAQDCV.CEC.MN as long as the outdoor<br />

air cfm sensor is valid.<br />

ConfigurationIAQDCV.CO.C.MN is used only<br />

with the outdoor airflow station <strong>and</strong> will supersede<br />

ConfigurationIAQDCV.CIAQ.M as long as the outdoor<br />

air cfm sensor is valid.<br />

Exhaust Options — The following exhaust options<br />

should be configured.<br />

EXHAUST TYPE<br />

UNIT Modulating<br />

Power<br />

Exhaust<br />

S.O.<br />

VFD*<br />

High-<br />

Capacity<br />

Power<br />

Exhaust†<br />

Return<br />

Exhaust†<br />

48/50P2,P4 X S.O. X* NA<br />

48/50P3,P5 X S.O. X* NA<br />

LEGEND<br />

X — Available as Factory Option<br />

S.O. — Available as Special Order<br />

NA — Not Available on this Unit<br />

*Sizes 075-100 only.<br />

†Factory-installed option only.<br />

ConfigurationBPBF.CF=1 (Two-Stage Exhaust<br />

Option) — For two-stage exhaust, under the<br />

ConfigurationBP submenu, configure the following:<br />

BP.P1 Power Exhaust On Setp.1<br />

BP.P2 Power Exhaust On Setp.2