2. Under the Setpoints menu, set the following<br />
configurations:<br />
SA.HI Supply Air Set Point Hi<br />
SA.LO Supply Air Set Point Lo<br />
3. See the Economizer Options section on this page for additional<br />
economizer option configurations.<br />
4. See the Exhaust Options section on this page for additional<br />
exhaust option configurations.<br />
Multi-Stage Constant Volume Units with<br />
Space Sensor — To configure the unit, perform the<br />
following:<br />
1. Under ConfigurationUNITC.TYP, set C.TYP to 4<br />
(SPT MULTI).<br />
2. Under the Setpoints menu, the following configurations<br />
should be set:<br />
SA.HI Supply Air Set Point Hi<br />
SA.LO Supply Air Set Point Lo<br />
3. Under the Setpoints submenu, the heating <strong>and</strong> cooling set<br />
points must be configured:<br />
OHSP Occupied Heat Setpoint<br />
OCSP Occupied Cool Setpoint<br />
UHSP Unoccupied Heat Setpoint<br />
UCSP Unoccupied Cool Setpoint<br />
GAP Heat-Cool Setpoint Gap<br />
D.LV.T Cool/Heat Set Point Offsets (located in the<br />
Configuration menu)<br />
4. Under ConfigurationUNITSENSSPT.S, enable<br />
the space sensor by setting SPT.S to ENBL.<br />
5. Under ConfigurationUNITFN.MD, set FN.MD to<br />
1 for continuous fan or 0 for automatic fan.<br />
6. To program time schedules, set SCH.N=1 under ConfigurationCCNSC.OVSCH.N<br />
to configure the control<br />
to use local schedules.<br />
7. Under the TimeclockSCH.L submenu, enter the desired<br />
schedule. See Time Clock section for further<br />
descriptions of these configurations.<br />
8. See the Economizer Options section below for addition<br />
economizer option configurations.<br />
9. See the Exhaust Options section below for addition<br />
exhaust option configurations.<br />
Economizer Options — Under the Configuration<br />
ECON submenu, the following set points should be configured:<br />
EC.EN Economizer Enabled?<br />
EC2.E Econ Act.2 Installed?<br />
EC.MN Economizer Min.Position<br />
EC.MX Economizer Maximum Position<br />
E.TRM Economizer Trim for SumZ?<br />
E.SEL Econ Changeover Select<br />
OA.E.C OA Enthalpy Change Over Select<br />
OA.EN Outdoor Enthalpy Compare Value<br />
OAT.L High OAT Lockout Temp<br />
O.DEW OA Dew Point Temp Limit<br />
ORH.S Outside Air RH Sensor<br />
33<br />
ConfigurationECONEC.MN should always be set for<br />
the minimum damper position.<br />
If the unit is equipped with an outdoor air flow station, the<br />
following points in ConfigurationECONCFM.C need to<br />
be set.<br />
OCF.S Outdoor Air CFM Sensor<br />
O.C.MX Economizer Minimum Flow<br />
O.C.DB Economizer Minimum Flow Deadb<strong>and</strong><br />
If equipped with an outdoor flow station, make sure<br />
ConfigurationECONCFM.COCF.S is enabled. If an<br />
outdoor air cfm station is used, then the economizer will control<br />
to cfm, not a position, as long as the sensor is valid. Therefore,<br />
ConfigurationECONCFM.CO.C.MX supersedes<br />
ConfigurationECONEC.MN.<br />
Indoor Air Quality Options<br />
DEMAND CONTROL VENTILATION — Under ConfigurationIAQDCV.C,<br />
the following configuration parameters<br />
should be set to establish the minimum <strong>and</strong> maximum<br />
points for outdoor air damper position during dem<strong>and</strong> control<br />
ventilation (DCV):<br />
EC.MN Economizer Min.Position<br />
IAQ.M IAQ Dem<strong>and</strong> Vent Min.Pos.<br />
O.C.MX Economizer Min.Flow<br />
O.C.MN IAQ Dem<strong>and</strong> Vent Min.Flow<br />
ConfigurationIAQDCV.CIAQ.M is used to set the<br />
absolute minimum vent position (or maximum reset) under<br />
DCV.<br />
ConfigurationIAQDCV.CEC.MN is used to set the<br />
minimum damper position (or with no DCV reset). This is also<br />
referenced in the economizer section.<br />
ConfigurationIAQDCV.CO.C.MX is used only<br />
with the outdoor airflow station <strong>and</strong> will supersede<br />
ConfigurationIAQDCV.CEC.MN as long as the outdoor<br />
air cfm sensor is valid.<br />
ConfigurationIAQDCV.CO.C.MN is used only<br />
with the outdoor airflow station <strong>and</strong> will supersede<br />
ConfigurationIAQDCV.CIAQ.M as long as the outdoor<br />
air cfm sensor is valid.<br />
Exhaust Options — The following exhaust options<br />
should be configured.<br />
EXHAUST TYPE<br />
UNIT Modulating<br />
Power<br />
Exhaust<br />
S.O.<br />
VFD*<br />
High-<br />
Capacity<br />
Power<br />
Exhaust†<br />
Return<br />
Exhaust†<br />
48/50P2,P4 X S.O. X* NA<br />
48/50P3,P5 X S.O. X* NA<br />
LEGEND<br />
X — Available as Factory Option<br />
S.O. — Available as Special Order<br />
NA — Not Available on this Unit<br />
*Sizes 075-100 only.<br />
†Factory-installed option only.<br />
ConfigurationBPBF.CF=1 (Two-Stage Exhaust<br />
Option) — For two-stage exhaust, under the<br />
ConfigurationBP submenu, configure the following:<br />
BP.P1 Power Exhaust On Setp.1<br />
BP.P2 Power Exhaust On Setp.2