Table 91 — Alert <strong>and</strong> Alarm Codes (cont)<br />

ALARM OR<br />

DESCRIPTION ACTION TAKEN BY CONTROL RESET METHOD<br />

ALERT NUMBER<br />

T610 Economizer Actuator Out of Calibration Alert only Automatic<br />

T611 Economizer Actuator Comm Failure No economizer functions Automatic<br />

T612 Economizer Actuator Control Range Increased Alert only Automatic<br />

T613 Econ Actuator Overload, Setpt Not Reached Alert only Automatic<br />

T614 Econ Actuator Hunting Excessively Alert only Automatic<br />

A620 Economizer 2 Actuator Out of Calibration Alarm only Automatic<br />

A621 Economizer 2 Actuator Comm Failure No IGV functions Automatic<br />

T622 Economizer 2 Actuator Control Range Increased Alert only Automatic<br />

A623 Econ2 Overload, Setpt Not Reached Alarm only Automatic<br />

A624 Econ2 Actuator Hunting Excessively Alert only Automatic<br />

T630 Humidifier Actuator Out of Calibration Alert only Automatic<br />

T631 Humidifier Actuator Communication Failure No humidifer functions Automatic<br />

T632 Humidifier Actuator Control Range Increased Alert only Automatic<br />

T633 Humidifier Act Overload, Setpt Not Reached Alert only Automatic<br />

T634 Humidifier Actuator Hunting Excessively Alert only Automatic<br />

A640 Heating Coil Actuator Out of Calibration Alarm only Automatic<br />

A641 Heating Coil Actuator Comm Fail No heating coil functions Automatic<br />

T642 Heat Coil Actuator Control Range Increased Alert only Automatic<br />

A643 Ht Coil Act Ovrload, Setpt Pos Not Reached Alarm only Automatic<br />

A644 Heat Coil Actuator Hunting Excessively alarm only Automatic<br />

A650 Bldg.Press. Actuator 1 Out of Calibration Alarm only Automatic<br />

A651 Bldg.Press. Actuator 1 Comm Failure No building pressure control Automatic<br />

T652 Bldg.Press. Act. 1 Control Range Increased Alert only Automatic<br />

A653 BP Act. 1 Overload, Setpnt Pos Not Reached Alarm only Automatic<br />

A654 Bldg.Press. Actuator 1 Hunting Excessively Alert only Automatic<br />

A660 Bldg.Press. Actuator 2 Out of Calibration Alarm only Automatic<br />

A661 Bldg.Press. Actuator 2 Comm Failure No building pressure control Automatic<br />

T662 Bldg.Press. Act. 2 Control Range Increased Alert only Automatic<br />

A663 BP Act. 2 Overload, Setpnt Pos Not Reached Alarm only Automatic<br />

A664 BP Actuator 2 Hunting Excessively Alert only Automatic<br />

A700 Air Temp Lvg Supply Fan Thermistor Failure Unit shut down Automatic<br />

T701 Staged Gas 1 Thermistor Failure Average remaning sensors Automatic<br />

T702 Staged Gas 2 Thermistor Failure Average remaning sensors Automatic<br />

T703 Staged Gas 3 Thermistor Failure Average remaning sensors Automatic<br />

A704 Staged Gas Lvg Air Temp Sum Total Failure No staged gas function Automatic<br />

T705 Limit Switch Thermistor Failure No software limit switch function Automatic<br />

A706 Hydronic Evap Discharge Thermistor Failure Unit shut down Automatic<br />

T707 Digital Scroll Discharge Temperature Failure Digital compressor A1 llimited to 50% Automatic<br />