06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

After the exhaust fan relay turns on, PID control ensues without<br />

an “I” term:<br />

Error = BP – BP.SP<br />

K = 1000 * BP.TM / 60 (normalize the PID control for run rate)<br />

P = K * BP.P * (error)<br />

D = K * BP.D * (error - error computed last time through the<br />

PID)<br />

VFD control signal (clamped between 0 <strong>and</strong> 100%) = VFD<br />

Output last time through + (P + D)<br />

NOTE: The sum of P + D will be clamped on any timed calculation<br />

to an internally calculated value which guarantees the<br />

VFD is not comm<strong>and</strong>ed more or less an amount, than it cannot<br />

achieve before the next time VFD capacity is again calculated.<br />

Bringing the single speed fan (P.E.2) ON <strong>and</strong> OFF is coordinated<br />

with the VFD speed. When building pressure first<br />

becomes active, P.E.2 is OFF, P.E.1 is ON <strong>and</strong> the VFD is<br />

allowed to climb to 100%. BP.CL will be used to act as hysteresis<br />

so that when the P + D term is evaluated <strong>and</strong> it exceeds<br />

BP.CL, the control will go through a one-minute period hold<br />

off time where the VFD is comm<strong>and</strong>ed to BP.CL, <strong>and</strong> P.E.2 is<br />

brought on. After the transition to P.E.2 ON is complete, the<br />

control will continue to control the VFD from BP.CL%. If BP<br />

rises, the control will speed up the VFD. Should the VFD drop<br />

to 0%, <strong>and</strong> the next time through the PID the P + D term calculation<br />

is less than – BP.CL, the control will go through another<br />

one-minute PID hold off period where P.E.2 is comm<strong>and</strong>ed<br />

OFF <strong>and</strong> the VFD is comm<strong>and</strong>ed to 100 – BP.CL.<br />

ConfigurationBPBP.CF =5 (Return/Exhaust Control)<br />

— Fan tracking is the method of control used on plenum return<br />

fan option. The fan tracking algorithm controls the exhaust/<br />

return fan VFD <strong>and</strong> the exhaust fan relay. The ComfortLink<br />

controls use a flow station to measure the flow of both the supply<br />

<strong>and</strong> the return fans. The speed of the return fan is controlled<br />

by maintaining a delta cfm (usually with supply airflow being<br />

greater of the two) between the two fans. The building pressure<br />

is controlled by maintaining this delta cfm between the two<br />

fans. In general, the greater the delta between supply airflow<br />

<strong>and</strong> return airflow, the higher the building pressure will be.<br />

Conversely, as the return airflow quantity increases above<br />

the supply airflow, the lower the building pressure will be.<br />

Whenever there is a request for the supply fan (or there is the<br />

presence of the IGC feedback on gas heat units), the return fan<br />

is started. The delta cfm is defined as S.CFM – R.CFM. The<br />

return fan VFD is controlled by a PID on the error of delta cfm<br />

actual from delta cfm set point. If the error is positive the drive<br />

will increase speed. If the error is negative the drive will<br />

decrease speed.<br />

NOTE: These configurations are used only if Fan Tracking<br />

Learning is enabled. When Fan Tracking Learning is enabled,<br />

the control will adjust the delta cfm (FT.ST) between the<br />

supply <strong>and</strong> return fan if the building pressure deviates from the<br />

Building Pressure Set Point (BP.SP). Periodically, at the rate<br />

set by the fan track learn rate (FT.TM), the delta cfm is<br />

adjusted upward or downward with a maximum adjustment<br />

at a given instance to be no greater than fan track max<br />

correction (FT.AD). The delta cfm can not ever be adjusted<br />

greater than or less than the fan track initial delta cfm (FT.ST)<br />

than by the Fan Track Max Clamp (FT.MX).<br />

CONFIGURING THE BUILDING PRESSURE ACTUA-<br />

TORS (BP.CF = 2) TO COMMUNICATE VIA ACTUATOR<br />

SERIAL NUMBER — Every actuator used in the P Series<br />

control system has its own unique serial number. The rooftop<br />

control uses this serial number to communicate with the<br />

actuator. These serial numbers are programmed at the factory<br />

<strong>and</strong> should not need changing. Should field replacement of an<br />

actuator become necessary, it will be necessary to configure the<br />

serial numbers of the new actuator. Four individual numbers<br />

make up each serial number <strong>and</strong> these can be programmed to<br />

match the serial number of the actuators in the building<br />

74<br />

pressure actuator configurations group, ACT.C.BP.1 <strong>and</strong><br />

BP.2 (SN.1, SN.2, SN.3, SN.4).<br />

NOTE: The serial numbers can be found inside the control<br />

doors of the unit as well as on the actuator itself. If an actuator<br />

is replaced in the field, it is a good idea to remove the additional<br />

peel-off serial number sticker on the actuator <strong>and</strong> cover<br />

up the old one inside the control doors.<br />

CONTROL ANGLE ALARM CONFIGURATION C.ALM<br />

(BP.CF = 2) — The building pressure actuators learn what its<br />

end stops are though a calibration at the factory. Field-installed<br />

actuators may be calibrated in the <strong>Service</strong> Test mode. When an<br />

actuator learns its end stops through calibration, it stores the<br />

control angle. The actuator will resolve this control angle <strong>and</strong><br />

express its operation in a percent (%) of this learned range.<br />

If a building pressure actuator has not learned a sufficient<br />

control angle during calibration, the actuator will be unable to<br />

control building pressure. For this reason the building pressure<br />

actuators used in the P Series control system have configurable<br />

control angle alarm low limits in the Building Pressure Actuator<br />

Configurations group, ACT.CBP.1 <strong>and</strong> BP.2. (C.A.LM).<br />

If the control angle learned through calibration is less than<br />

C.A.LM, an alert will occur <strong>and</strong> the actuator will not function.<br />

NOTE: This configuration does not typically need adjustment.<br />

It is configurable for the small number of jobs which may<br />

require a custom solution or workaround.<br />

Smoke Control Modes — There are four smoke control<br />

modes that can be used to control smoke within areas serviced<br />

by the unit: Pressurization mode, Evacuation mode,<br />

Smoke Purge mode, <strong>and</strong> Fire Shutdown. Evacuation, Pressurization<br />

<strong>and</strong> Smoke Purge modes require the controls expansion<br />

board (CEM). The Fire Shutdown input is located on the main<br />

board (MBB) on terminals TB201-1 <strong>and</strong> 2. The unit may also<br />

be equipped with a factory-installed return air smoke detector<br />

that is wired to TB201-1,2 <strong>and</strong> will shut the unit down if a<br />

smoke condition is determined. Field-monitoring wiring can be<br />

connected to terminal TB201-1 <strong>and</strong> 2 to monitor the smoke detector.<br />

Inputs on the CEM board can be used to put the unit in<br />

the Pressurization, Evacuation, <strong>and</strong> Smoke Purge modes.<br />

These switches or inputs are connected to TB202 as shown below.<br />

Refer to Major System Components section on page 115<br />

for wiring diagrams.<br />

Pressurization — TB202-18 <strong>and</strong> 19<br />

Evacuation — TB202-16 <strong>and</strong> 17<br />

Smoke Purge — TB202-14 <strong>and</strong> 15<br />

Each mode must be energized individually on discrete inputs<br />

<strong>and</strong> the corresponding alarm is initiated when a mode is<br />

activated. The fire system provides a normally closed dry<br />

contact closure. Multiple smoke control inputs, sensed by the<br />

control will force the unit into a Fire Shutdown mode.<br />

FIRE SMOKE INPUTS — These discrete inputs can be<br />

found on the local display under InputsFIRE.<br />

CCN<br />

ITEM EXPANSION RANGE<br />

POINT WRITE<br />

STATUS<br />

FIRE FIRE-SMOKE INPUTS<br />

FSD Fire Shutdown Input ALRM/NORM FSD forcible<br />

PRES Pressurization Input ALRM/NORM PRES forcible<br />

EVAC Evacuation Input ALRM/NORM EVAC forcible<br />

PURG Smoke Purge Input ALRM/NORM PURG forcible<br />

Fire Shutdown Mode — This mode will cause an immediate<br />

<strong>and</strong> complete shutdown of the unit.<br />

Pressurization Mode — This mode attempts to raise the pressure<br />

of a space to prevent smoke infiltration from an adjacent<br />

space. Opening the economizer (thereby closing the return air<br />

damper), shutting down power exhaust <strong>and</strong> turning the indoor<br />

fan on will increase pressure in the space.<br />

Evacuation Mode — This mode attempts to lower the pressure<br />

of the space to prevent infiltrating an adjacent space with

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!