APPENDIX B — CCN TABLES (cont)<br />
MAINTENANCE DISPLAY TABLES (cont)<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />
LINKDATA<br />
Supervisory Element # SUPE-ADR<br />
Supervisory Bus SUPE-BUS<br />
Supervisory Block Number BLOCKNUM<br />
Average Occup. Heat Stp. dF AOHS<br />
Average Occup. Cool Stp. dF AOCS<br />
Average Unocc. Heat Stp. dF AUHS<br />
Average Unocc. Cool Stp. dF AUCS<br />
Average Zone Temperature dF AZT<br />
Average Occup. Zone Temp dF AOZT<br />
Linkage System Occupied? LOCC<br />
Next Occupied Day LNEXTOCD<br />
Next Occupied Time LNEXTOCC<br />
Next Unoccupied Day LNEXTUOD<br />
Next Unoccupied Time LNEXTUNC<br />
Last Unoccupied Day LLASTUOD<br />
Last Unoccupied Time LLASTUNC<br />
MILLIAMP<br />
IAQ milliamps ma IAQ_MA<br />
OAQ milliamps ma OAQ_MA<br />
SP Reset milliamps ma SPRST_MA<br />
4-20 ma Dem<strong>and</strong> Signal ma DMDLMTMA forcible<br />
EDT Reset milliamps ma EDTRESMA<br />
OARH milliamps ma OARH_MA<br />
SPRH milliamps ma SPRH_MA<br />
RARH milliamps ma RARH_MA<br />
SACFM milliamps ma SACFM_MA<br />
RACFM milliamps ma RACFM_MA<br />
OACFM milliamps ma OACFM_MA<br />
BP milliamps ma BP_MA<br />
SP milliamps ma SP_MA<br />
MODES<br />
System Mode…………: ascii text strings<br />
HVAC Mode…………..: ascii text strings<br />
Control Mode………..: ascii text strings<br />
Currently Occupied On/Off MODEOCCP<br />
Timed Override in effect On/Off MODETOVR<br />
DCV resetting min pos On/Off MODEADCV<br />
Supply Air Reset On/Off MODESARS<br />
Dem<strong>and</strong> Limit in Effect On/Off MODEDMLT<br />
Temp.Compensated <strong>Start</strong> On/Off MODETCST<br />
IAQ pre-occ purge active On/Off MODEIQPG<br />
Linkage Active - DAV On/Off MODELINK<br />
Mech.Cooling Locked Out On/Off MODELOCK<br />
HVAC Mode Numerical Form number MODEHVAC<br />
OCCDEFME<br />
Current Day, Time & Date: ascii date & time TIMEDATE<br />
Occupancy Controlled By: ascii text OCDFTXT1<br />
ascii text OCDFTXT2<br />
ascii text OCDFTXT3<br />
Currently Occupied Yes/No MODE_OCC<br />
Current Occupied Time STRTTIME<br />
Current Unoccupied Time ENDTIME<br />
Next Occupied Day & Time NXTOC_DT<br />
Next Unocc. Day & Time NXTUN_DT<br />
Last Unocc. Day & Time PRVUN_DT<br />
Current Occup. Period # PER_NO<br />
Timed-Override in Effect Yes/No OVERLAST<br />
Timed-Override Duration hours OVR_HRS<br />
PRESBLDG<br />
Building Pressure "H2O BP<br />
Return Air CFM CFM RACFM<br />
Supply Air CFM CFM SACFM<br />
Power Exhaust Relay 1 On/Off PE1<br />
Power Exhaust Relay 2 On/Off PE2<br />
BP 1 Actuator Curr.Pos. % BP1_RPOS<br />
BP 1 Comm<strong>and</strong> Position % BP1_CPOS<br />
BP 2 Actuator Curr.Pos. % BP2_RPOS<br />
BP 2 Comm<strong>and</strong> Position % BP2_CPOS<br />
Exhaust Fan VFD Speed % EFAN_VFD<br />
Building Pressure Setp. "H2O BPSP config<br />
BP Setpoint Offset ^"H2O BPSO config<br />
Fan Track Learn Enable Yes/No DCFM_CFG config<br />
Fan Track Learn Rate min DCFMRATE config<br />
Fan Track Initial DCFM CFM DCFMSTRT config<br />
Fan Track Max Clamp CFM DCFM_MAX config<br />
Fan Track Max Correction CFM DCFM_ADJ config<br />
Fan Track Internl EEPROM CFM DCFM_OFF config<br />
Fan Track Reset Internal DCFMRSET config<br />
Fan Track Internal RAM CFM DCFM_RAM<br />
Fan Track Control D.CFM CFM DELTACFM<br />
189