Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Temperature Compensated <strong>Start</strong> Cooling Factor (TCS.H) —<br />
This factor is used in the equation of the Temperature Compensated<br />
<strong>Start</strong> Time Bias for heating. Refer to the Temperature<br />
Compensated <strong>Start</strong> section for more information. A setting of<br />
0 minutes indicates Temperature Compensated <strong>Start</strong> in Heating<br />
is not permitted.<br />
Fan Fail Shuts Downs Unit (SFS.S) — When fan status<br />
monitoring is configured on, this configuration will determine<br />
whether the unit should shut down on a supply fan status fail or<br />
simply alert the condition <strong>and</strong> continue to run. If set to YES,<br />
then the control will shut down the unit <strong>and</strong> send out an alarm<br />
if supply fan status monitoring fails. If set to NO, the control<br />
will not shut down the unit if supply fan status monitoring fails<br />
but the control will send out an alert.<br />
Fan Status Monitoring (SFS.M) — This configuration selects<br />
the type of fan status monitoring to be performed.<br />
0 - NONE — No switch or monitoring<br />
1 - SWITCH — Use of the fan status switch<br />
2 - SP RISE — Monitoring of the supply duct pressure.<br />
VAV Unoccupied Fan Retry Time (VAV.S) — Machine control<br />
types 1 <strong>and</strong> 2 (VAV-RAT,VAV-SPT) include a process for<br />
sampling the return-air temperature during unoccupied periods<br />
to prove a valid dem<strong>and</strong> for heating or cooling before initiating<br />
an unoccupied heating or cooling mode. If the sampling routine<br />
runs but concludes a valid dem<strong>and</strong> condition does not exist,<br />
the sampling process will not be permitted for the period of<br />
time defined by this configuration. Reducing this value allows<br />
a more frequent re-sampling process. Setting this value to zero<br />
will prevent any sampling sequence.<br />
50 Hertz Unit? (50.HZ) — This configuration is not used. Do<br />
not change the setting of this configuration.<br />
MAT Calc Config (MAT.S) — This configuration gives the<br />
user three options in the processing of the mixed-air temperature<br />
(MAT) calculation:<br />
• MAT.S = 0<br />
There will be no MAT calculation.<br />
• MAT.S = 1<br />
The control will attempt to learn MAT over time. Any time<br />
the system is in a vent mode <strong>and</strong> the economizer stays at a<br />
particular position for long enough, MAT = EDT (evaporator<br />
discharge temperature). Using this, the control has an internal<br />
table whereby it can more closely determine the true<br />
MAT value.<br />
• MAT.S = 2<br />
The control will stop learning <strong>and</strong> use whatever the control<br />
has already learned. Using this setting infers that the control<br />
has spent some time set to MAT.S = 1.<br />
First set MAT.S = 1, then go into the <strong>Service</strong> Test mode.<br />
Turn on the fan <strong>and</strong> open the economizer to a static position for<br />
5 minutes. Move to several positions (20%,40%,60%,80%). It<br />
is important that the difference between return <strong>and</strong> outside temperature<br />
be greater than 5 degrees. (The greater the delta, the<br />
better.) When done, set MAT.S = 2.<br />
Reset MAT Table Entries? (MAT.R) — This configuration<br />
allows the user to reset the internally stored MAT learned configuration<br />
data back to the default values. The defaults are set<br />
to a linear relationship between the economizer damper position<br />
<strong>and</strong> OAT <strong>and</strong> RAT in the calculation of MAT.<br />
MAT Outside Air Position Default (MAT.D) — This configuration<br />
is used to calculate MAT when the economizer option<br />
is disabled. The configuration is adjustable from 0 to 100%<br />
outside air. This defines the fixed ventilation position that will<br />
be used to correctly calculate MAT.<br />
44<br />
Altitude……..In Feet: (ALTI) — As the control does not include<br />
a barometric pressure sensor to define the calculation of<br />
enthalpy <strong>and</strong> cfm, the control does include an altitude parameter<br />
which will serve to set up a default barometric pressure for<br />
use with calculations. The effect of barometric pressure in<br />
these calculations is not great, but could have an effect depending<br />
on the installed elevation of the unit. If the rooftop is<br />
installed at a particularly high altitude <strong>and</strong> enthalpy or cfm are<br />
being calculated, set this configuration to the current elevation<br />
of the installed rooftop.<br />
<strong>Start</strong> <strong>Up</strong> Delay Time (DLAY) — This option inhibits the unit<br />
from operating after a power reset. The configuration may be<br />
adjusted from 0 to 900 seconds of delay.<br />
Auxiliary Relay Output Configuration (AUX.R) — This<br />
configuration allows the user to configure the function of the<br />
auxiliary relay output. The output is 1.4 vac, 5 va maximum.<br />
The configuration can be set from 0 to 3. If AUX.R is set to 0,<br />
the auxiliary relay contact will be energized during an alarm.<br />
The output can be used to turn on an indicator light or sound an<br />
alarm in a mechanical room. If AUX.R is set to 1, the auxiliary<br />
relay will energize when the controls determine dehumidification/reheat<br />
is needed. The relay would be wired to a third party<br />
dehumidification/reheat device <strong>and</strong> would energize the device<br />
when needed. If AUX.R is set to 2, the auxiliary relay will energize<br />
when the unit is in the occupied state. The relay could then<br />
be used to control lighting or other functions that need to be on<br />
during the occupied state. If AUX.R is set to 3, the auxiliary relay<br />
will energize when the supply fan is energized (<strong>and</strong>, if<br />
equipped with a VFD, the VFD output is not 0%). The default<br />
is 0.<br />
Space Temp Sensor (SPT.S) — If a space temperature sensor<br />
is installed (T55/T56), enable this configuration.<br />
Space Temp Offset Sensor (SP.O.S) — If a T56 sensor is installed<br />
with the space temperature offset slider, enable this<br />
configuration.<br />
Space Temp Offset Range (SP.O.R) — If a space temperature<br />
offset sensor is installed, it is possible to configure the<br />
range of the slider by adjusting this range configuration.<br />
Space Air RH Sensor (SRH.S) — If a space relative humidity<br />
sensor is installed, enable this configuration.<br />
Return RH Sensor (RRH.S) — If a return air relative humidity<br />
sensor is installed, enable this configuration.<br />
Filter Status Switch Enabled? (FLT.S) — If a filter status<br />
switch is installed, enable this configuration to begin the monitoring<br />
of the filter status input (InputsGEN.I FLT.S). See<br />
the Dirty Filter Switch section for more details on installation<br />
<strong>and</strong> operation.<br />
Cooling Control — The P Series ComfortLink controls<br />
offer two basic control approaches to mechanical cooling:<br />
multi-stage cooling (CV) <strong>and</strong> multiple stages of cooling (VAV).<br />
In addition, the ComfortLink controls offer the ability to run<br />
multiple stages of cooling for either a space temperature sensor<br />
or thermostat by controlling the unit to either a low or high cool<br />
supply air set point. The control type (Configuration<br />
UNITC.TYP) determines the selection of the type of cooling<br />
control as well as the technique for selecting a cooling mode.<br />
Unit staging tables are shown in Appendix C.<br />
NOTE: Whether a unit has a VFD or a supply fan installed for<br />
static pressure control has no effect on configuration of the<br />
machine control type (C.TYP). No matter what the control<br />
type, it is possible to run the unit in either CV or VAV mode<br />
provided there are enough stages to accommodate lower air<br />
volumes for VAV operation. Refer to the section on static pressure<br />
control on page 64 for information on how to set up the<br />
unit for the type of supply fan control desired.