06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Temperature Compensated <strong>Start</strong> Cooling Factor (TCS.H) —<br />

This factor is used in the equation of the Temperature Compensated<br />

<strong>Start</strong> Time Bias for heating. Refer to the Temperature<br />

Compensated <strong>Start</strong> section for more information. A setting of<br />

0 minutes indicates Temperature Compensated <strong>Start</strong> in Heating<br />

is not permitted.<br />

Fan Fail Shuts Downs Unit (SFS.S) — When fan status<br />

monitoring is configured on, this configuration will determine<br />

whether the unit should shut down on a supply fan status fail or<br />

simply alert the condition <strong>and</strong> continue to run. If set to YES,<br />

then the control will shut down the unit <strong>and</strong> send out an alarm<br />

if supply fan status monitoring fails. If set to NO, the control<br />

will not shut down the unit if supply fan status monitoring fails<br />

but the control will send out an alert.<br />

Fan Status Monitoring (SFS.M) — This configuration selects<br />

the type of fan status monitoring to be performed.<br />

0 - NONE — No switch or monitoring<br />

1 - SWITCH — Use of the fan status switch<br />

2 - SP RISE — Monitoring of the supply duct pressure.<br />

VAV Unoccupied Fan Retry Time (VAV.S) — Machine control<br />

types 1 <strong>and</strong> 2 (VAV-RAT,VAV-SPT) include a process for<br />

sampling the return-air temperature during unoccupied periods<br />

to prove a valid dem<strong>and</strong> for heating or cooling before initiating<br />

an unoccupied heating or cooling mode. If the sampling routine<br />

runs but concludes a valid dem<strong>and</strong> condition does not exist,<br />

the sampling process will not be permitted for the period of<br />

time defined by this configuration. Reducing this value allows<br />

a more frequent re-sampling process. Setting this value to zero<br />

will prevent any sampling sequence.<br />

50 Hertz Unit? (50.HZ) — This configuration is not used. Do<br />

not change the setting of this configuration.<br />

MAT Calc Config (MAT.S) — This configuration gives the<br />

user three options in the processing of the mixed-air temperature<br />

(MAT) calculation:<br />

• MAT.S = 0<br />

There will be no MAT calculation.<br />

• MAT.S = 1<br />

The control will attempt to learn MAT over time. Any time<br />

the system is in a vent mode <strong>and</strong> the economizer stays at a<br />

particular position for long enough, MAT = EDT (evaporator<br />

discharge temperature). Using this, the control has an internal<br />

table whereby it can more closely determine the true<br />

MAT value.<br />

• MAT.S = 2<br />

The control will stop learning <strong>and</strong> use whatever the control<br />

has already learned. Using this setting infers that the control<br />

has spent some time set to MAT.S = 1.<br />

First set MAT.S = 1, then go into the <strong>Service</strong> Test mode.<br />

Turn on the fan <strong>and</strong> open the economizer to a static position for<br />

5 minutes. Move to several positions (20%,40%,60%,80%). It<br />

is important that the difference between return <strong>and</strong> outside temperature<br />

be greater than 5 degrees. (The greater the delta, the<br />

better.) When done, set MAT.S = 2.<br />

Reset MAT Table Entries? (MAT.R) — This configuration<br />

allows the user to reset the internally stored MAT learned configuration<br />

data back to the default values. The defaults are set<br />

to a linear relationship between the economizer damper position<br />

<strong>and</strong> OAT <strong>and</strong> RAT in the calculation of MAT.<br />

MAT Outside Air Position Default (MAT.D) — This configuration<br />

is used to calculate MAT when the economizer option<br />

is disabled. The configuration is adjustable from 0 to 100%<br />

outside air. This defines the fixed ventilation position that will<br />

be used to correctly calculate MAT.<br />

44<br />

Altitude……..In Feet: (ALTI) — As the control does not include<br />

a barometric pressure sensor to define the calculation of<br />

enthalpy <strong>and</strong> cfm, the control does include an altitude parameter<br />

which will serve to set up a default barometric pressure for<br />

use with calculations. The effect of barometric pressure in<br />

these calculations is not great, but could have an effect depending<br />

on the installed elevation of the unit. If the rooftop is<br />

installed at a particularly high altitude <strong>and</strong> enthalpy or cfm are<br />

being calculated, set this configuration to the current elevation<br />

of the installed rooftop.<br />

<strong>Start</strong> <strong>Up</strong> Delay Time (DLAY) — This option inhibits the unit<br />

from operating after a power reset. The configuration may be<br />

adjusted from 0 to 900 seconds of delay.<br />

Auxiliary Relay Output Configuration (AUX.R) — This<br />

configuration allows the user to configure the function of the<br />

auxiliary relay output. The output is 1.4 vac, 5 va maximum.<br />

The configuration can be set from 0 to 3. If AUX.R is set to 0,<br />

the auxiliary relay contact will be energized during an alarm.<br />

The output can be used to turn on an indicator light or sound an<br />

alarm in a mechanical room. If AUX.R is set to 1, the auxiliary<br />

relay will energize when the controls determine dehumidification/reheat<br />

is needed. The relay would be wired to a third party<br />

dehumidification/reheat device <strong>and</strong> would energize the device<br />

when needed. If AUX.R is set to 2, the auxiliary relay will energize<br />

when the unit is in the occupied state. The relay could then<br />

be used to control lighting or other functions that need to be on<br />

during the occupied state. If AUX.R is set to 3, the auxiliary relay<br />

will energize when the supply fan is energized (<strong>and</strong>, if<br />

equipped with a VFD, the VFD output is not 0%). The default<br />

is 0.<br />

Space Temp Sensor (SPT.S) — If a space temperature sensor<br />

is installed (T55/T56), enable this configuration.<br />

Space Temp Offset Sensor (SP.O.S) — If a T56 sensor is installed<br />

with the space temperature offset slider, enable this<br />

configuration.<br />

Space Temp Offset Range (SP.O.R) — If a space temperature<br />

offset sensor is installed, it is possible to configure the<br />

range of the slider by adjusting this range configuration.<br />

Space Air RH Sensor (SRH.S) — If a space relative humidity<br />

sensor is installed, enable this configuration.<br />

Return RH Sensor (RRH.S) — If a return air relative humidity<br />

sensor is installed, enable this configuration.<br />

Filter Status Switch Enabled? (FLT.S) — If a filter status<br />

switch is installed, enable this configuration to begin the monitoring<br />

of the filter status input (InputsGEN.I FLT.S). See<br />

the Dirty Filter Switch section for more details on installation<br />

<strong>and</strong> operation.<br />

Cooling Control — The P Series ComfortLink controls<br />

offer two basic control approaches to mechanical cooling:<br />

multi-stage cooling (CV) <strong>and</strong> multiple stages of cooling (VAV).<br />

In addition, the ComfortLink controls offer the ability to run<br />

multiple stages of cooling for either a space temperature sensor<br />

or thermostat by controlling the unit to either a low or high cool<br />

supply air set point. The control type (Configuration<br />

UNITC.TYP) determines the selection of the type of cooling<br />

control as well as the technique for selecting a cooling mode.<br />

Unit staging tables are shown in Appendix C.<br />

NOTE: Whether a unit has a VFD or a supply fan installed for<br />

static pressure control has no effect on configuration of the<br />

machine control type (C.TYP). No matter what the control<br />

type, it is possible to run the unit in either CV or VAV mode<br />

provided there are enough stages to accommodate lower air<br />

volumes for VAV operation. Refer to the section on static pressure<br />

control on page 64 for information on how to set up the<br />

unit for the type of supply fan control desired.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!