Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
Controls, Start-Up, Operation, Service and ... - Climayoreo
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Table 50 — Static Pressure Control Configuration<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
SP SUPPLY STATIC PRESS.CFG.<br />
SP.CF Static Pressure Config Enable/Disable STATICFG Disable<br />
SP.S Static Pressure Sensor Enable/Disable SPSENS Disable<br />
SP.LO Static Press. Low Range –10 - 0 in. W.C. SP_LOW 0<br />
SP.HI Static Press. High Range 0 - 10 in. W.C. SP_HIGH 5<br />
SP.SP Static Pressure Setpoint 0 - 5 in. W.C. SPSP 1.5<br />
SP.MN VFD Minimum Speed 0 - 100 % STATPMIN 20<br />
SP.MX VFD Maximum Speed 0 - 100 % STATPMAX 100<br />
SP.FS VFD Fire Speed Over. 0 - 100 % STATPFSO 100<br />
SP.RS Stat. Pres. Reset Config 0 - 4 SPRSTCFG 0<br />
SP.RT SP Reset Ratio (/dF) 0 - 2.00 SPRRATIO 0.2<br />
SP.LM SP Reset Limit in iwc () 0 - 2.00 SPRLIMIT 0.75<br />
SP.EC SP Reset Econo.Position 0 - 100 % ECONOSPR 5<br />
S.PID STAT.PRESS.PID CONFIGS<br />
SP.TM Static Press. PID Run Rate 5 - 120 sec SPIDRATE 15<br />
SP.P Static Press. Prop. Gain 0 - 5 STATP_PG 0.5<br />
SP.I Static Pressure Intg. Gain 0 - 2 STATP_IG 0.5<br />
SP.D Static Pressure Derv. Gain 0 - 5 STATP_DG 0.3<br />
Static Pressure Reset Configuration (SP.RS) — This option<br />
is used to configure the static pressure reset function. When<br />
SP.RS = 0, there is no static pressure reset via an analog input.<br />
When SP.RS = 1, there is static pressure reset based on the<br />
CEM 4-20MA input <strong>and</strong> ranged from 0 to 3 in. wg. When<br />
SP.RS = 2, there is static pressure reset based on RAT <strong>and</strong><br />
defined by SP.RT <strong>and</strong> SP.LM. When SP.RS = 3, there is<br />
static pressure reset based on SPT <strong>and</strong> defined by SP.RT <strong>and</strong><br />
SP.LM. When SP.RS = 4, there is VFD speed control where<br />
0 mA = 0% speed <strong>and</strong> 20 mA = 100% (SP.MN <strong>and</strong> SP.MX will<br />
override).<br />
Static Pressure Reset Ratio (SP.RT) — This option defines<br />
the reset ratio in terms of static pressure versus temperature.<br />
The reset ratio determines how much the static pressure is<br />
reduced for every degree below set point for RAT or SPT.<br />
Static Pressure Reset Limit (SP.LM) — This option defines<br />
the maximum amount of static pressure reset that is allowed.<br />
This is sometimes called a “clamp.”<br />
NOTE: Resetting static pressure via RAT <strong>and</strong> SPT is primarily<br />
a constant volume application which utilizes a VFD. The reasoning<br />
is that there is significant energy savings in slowing<br />
down a supply fan as opposed to running full speed with<br />
supply air reset. Maintaining the supply air set point <strong>and</strong><br />
slowing down the fan has the additional benefit of working<br />
around dehumidification concerns.<br />
Static Pressure Reset Economizer Position (SP.EC) — This<br />
option effectively resets ECONOMIN to fully occupied ventilation<br />
position, to account for the drop in static pressure during<br />
static pressure reset control. The static pressure reset for the<br />
calculation cannot be larger than the supply air static set point<br />
(SPSP).<br />
The calculation is as follows:<br />
(Static Pressure Reset/SPSP) x (ECONOSPR – ECONOMIN)<br />
As an example, the static pressure set point (SPSP) =<br />
1.5 in. wg. The current static pressure reset is set to 0.5 in. wg.<br />
The settings for ECONOSPR = 50% <strong>and</strong> ECONOMIN = 20%.<br />
Therefore, the amount to add to the economizer’s<br />
ECONOMIN configuration is: (0.5/1.5) x (50-20) = 10%. In<br />
effect, for the positioning of the economizer, ECONOMIN<br />
would now be replaced by ECONOMIN + 10%.<br />
Static Pressure PID Config (S.PID) — Static pressure PID<br />
configuration can be accessed under this heading in the ConfigurationSP<br />
submenu. Under most operating conditions the<br />
control PID factors will not require any adjustment <strong>and</strong> the<br />
factory defaults should be used. If persistent static pressure<br />
65<br />
fluctuations are detected, small changes to these factors may<br />
improve performance. Decreasing the factors generally reduce<br />
the responsiveness of the control loop, while increasing the<br />
factors increase its responsiveness. Note the existing settings<br />
before making changes, <strong>and</strong> seek technical assistance from<br />
Carrier before making significant changes to these factors.<br />
Static Pressure PID Run Rate (S.PIDSP.TM) — This is the<br />
number of seconds between duct static pressure readings taken<br />
by the ComfortLink PID routine.<br />
Static Pressure Proportional Gain (S.PIDSP.P) — This is<br />
the proportional gain for the static pressure control PID control<br />
loop.<br />
Static Pressure Integral Gain (S.PIDSP.I) — This is the<br />
integral gain for the static pressure control PID control loop.<br />
Static Pressure Derivative Gain (S.PIDSP.D) — This is the<br />
derivative gain for the static pressure control PID control loop.<br />
STATIC PRESSURE RESET — The configuration for Static<br />
Pressure Reset is found under ConfigurationSP.<br />
ITEM EXPANSION RANGE CCN POINT DEFAULT<br />
SENSSP.RS<br />
Static Press.<br />
Reset Sensor.<br />
Enable/<br />
Disable<br />
SPRSTSEN Disable<br />
Static Pressure Reset Sensor (SP.RS) — If the outdoor air<br />
quality sensor is not configured (ConfigurationIAQ<br />
AQ.CFOQ.A.C=0), then it is possible to use the outdoor<br />
air quality sensor location on the CEM board to perform static<br />
pressure reset via an external 4 to 20 mA input. Enabling this<br />
sensor will give the user the ability to reset from 0 to 3-in. wg<br />
of static pressure. The reset will apply to the supply static<br />
pressure set point (ConfigurationSPSP.SP), where 4 mA<br />
= 0-in. wg <strong>and</strong> 20 mA = 3-in. wg.<br />
As an example, the static pressure reset input is measuring<br />
6 mA, <strong>and</strong> the input is resetting 2 mA of its 16 mA control<br />
range. The 4 to 20 mA range corresponds directly to the 0 to<br />
3 in. wg of reset. Therefore 2 mA reset is 2/16 * 3-in. wg =<br />
0.375-in. wg of reset. If the static pressure set point (SP.SP) =<br />
1.5-in. wg, then the static pressure control point for the system<br />
will be reset 1.5 – 0.375 = 1.125-in. wg.<br />
For third party 4 to 20 mA SP reset, wire the input to TB202<br />
terminals 6 <strong>and</strong> 7.<br />
For reset via a connected ComfortID system, the Linkage<br />
Coordinator terminal monitors the primary-air damper position<br />
of all the terminals in the system. It then calculates the amount of<br />
supply static pressure reduction necessary to cause the most<br />
open damper in the system to open more than the minimum