Sensor Trim Configuration — The TRIM submenu<br />
is used to calibrate the sensor trim settings. The trim settings<br />
are used when the actual measured reading does not match the<br />
sensor output. The sensor can be adjusted to match the actual<br />
measured reading with the trim function. A list is shown in<br />
Table 63.<br />
IMPORTANT: Sensor trim must not be used to extend<br />
unit operation past the allowable operating range.<br />
Doing so may impair or negatively affect the Carrier<br />
product warranty.<br />
Air Temperature Leaving Supply Fan Sensor (SAT.T) — This<br />
variable is used to adjust the supply fan temperature sensor<br />
reading. The sensor reading can be adjusted ± 10° F to match<br />
the actual measured temperature.<br />
Return Air Temperature Sensor Trim (RAT.T) — This variable<br />
is used to adjust the return air temperature sensor reading.<br />
The sensor reading can be adjusted ± 10° F to match the actual<br />
measured temperature.<br />
Outdoor Air Temperature Sensor Trim (OAT.T) — This variable<br />
is used to adjust the outdoor air temperature sensor reading.<br />
The sensor reading can be adjusted ± 10° F to match the<br />
actual measured temperature.<br />
Space Temperature Sensor Trim (SPT.T) — This variable is<br />
used to adjust the space temperature sensor reading. The sensor<br />
reading can be adjusted ± 10° F to match the actual measured<br />
temperature.<br />
Limit Switch Trim (L.SW.T) — This variable is used to adjust<br />
the limit switch temperature sensor reading. The sensor<br />
reading can be adjusted ± 10° F to match the actual measured<br />
temperature.<br />
Table 62 — Alert Limit Configuration<br />
Table 63 — Sensor Trim Configuration<br />
85<br />
Air Temperature Leaving Evaporator Trim (CCT.T) — This<br />
variable is used to adjust the leaving evaporator temperature<br />
sensor reading. The sensor reading can be adjusted ± 10° F to<br />
match the actual measured temperature.<br />
A1 Discharge Temperature (DTA.1) — This variable is used<br />
to adjust the A1 compressor discharge temperature sensor reading.<br />
The sensor reading can be adjusted ± 10° F to match the<br />
actual measured temperature.<br />
Suction Pressure Circuit A Trim (SP.A.T) — This variable is<br />
used to adjust the suction pressure sensor reading for circuit A.<br />
The sensor reading can be adjusted ± 50 psig to match the actual<br />
measured pressure.<br />
Suction Pressure Circuit B Trim (SP.B.T) — This variable is<br />
used to adjust the suction pressure sensor reading for circuit B.<br />
The sensor reading can be adjusted ± 50 psig to match the actual<br />
measured pressure.<br />
Discharge Pressure Circuit A Trim (DP.A.T) — This variable<br />
is used to adjust the discharge pressure sensor reading for<br />
circuit A. The sensor reading can be adjusted ± 50 psig to<br />
match the actual measured pressure.<br />
Discharge Pressure Circuit B Trim (DP.B.T) — This variable<br />
is used to adjust the discharge pressure sensor reading for<br />
circuit B. The sensor reading can be adjusted ±50 psig to match<br />
the actual measured pressure.<br />
4 to 20 mA Inputs — There are a number of 4 to 20 mA inputs<br />
which may be calibrated. These inputs are located in<br />
Inputs4-20. They are:<br />
• SP.M.T — static pressure milliamp trim<br />
• BP.M.T — building pressure milliamp trim<br />
• OA.M.T — outside air cfm milliamp trim<br />
• RA.M.T — return air cfm milliamp trim<br />
• SA.M.T — supply air cfm milliamp trim<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
SP.L.O SPT lo alert limit/occ -10-245 dF SPLO 60<br />
SP.H.O SPT hi alert limit/occ -10-245 dF SPHO 85<br />
SP.L.U SPT lo alert limit/unocc -10-245 dF SPLU 45<br />
SP.H.U SPT hi alert limit/unocc -10-245 dF SPHU 100<br />
SA.L.O EDT lo alert limit/occ -40-245 dF SALO 40<br />
SA.H.O EDT hi alert limit/occ -40-245 dF SAHO 100<br />
SA.L.U EDT lo alert limit/unocc -40-245 dF SALU 40<br />
SA.H.U EDT hi alert limit/unocc -40-245 dF SAHU 100<br />
RA.L.O RAT lo alert limit/occ -40-245 dF RALO 60<br />
RA.H.O RAT hi alert limit/occ -40-245 dF RAHO 90<br />
RA.L.U RAT lo alert limit/unocc -40-245 dF RALU 40<br />
RA.H.U RAT hi alert limit/unocc -40-245 dF RAHU 100<br />
OAT.L OAT lo alert limit -40-245 dF OATL -40<br />
OAT.H OAT hi alert limit -40-245 dF OATH 150<br />
R.RH.L RARH low alert limit 0-100 % RRHL 0<br />
R.RH.H RARH high alert limit 0-100 % RRHH 100<br />
O.RH.L OARH low alert limit 0-100 % ORHL 0<br />
O.RH.H OARH high alert limit 0-100 % ORHH 100<br />
SP.L SP low alert limit 0-5 "H2O SPL 0<br />
SP.H SP high alert limit 0-5 "H2O SPH 2<br />
BP.L BP lo alert limit -0.25-0.25 "H2O BPL -0.25<br />
BP.H BP high alert limit -0.25-0.25 "H2O BPH 0.25<br />
IAQ.H IAQ high alert limit 0-5000 IAQH 1200<br />
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />
TRIM SENSOR TRIM CONFIG.<br />
SAT.T Air Temp Lvg SF Trim -10 - 10 ^F SAT_TRIM 0<br />
RAT.T RAT Trim -10 - 10 ^F RAT_TRIM 0<br />
OAT.T OAT Trim -10 - 10 ^F OAT_TRIM 0<br />
SPT.T SPT Trim -10 - 10 ^F SPT_TRIM 0<br />
L.SW.T Limit Switch Trim -10 - 10 ^F LSW_TRIM 0<br />
CCT.T Air Temp Lvg Evap Trim -10 - 10 ^F CCT_TRIM 0<br />
DTA.1 A1 Discharge Temp Trim -10 - 10 ^F DTA1TRIM 0<br />
SP.A.T Suct.Press.Circ.A Trim -50 - 50 PSIG SPA_TRIM 0<br />
SP.B.T Suct.Press.Circ.B Trim -50 - 50 PSIG SPB_TRIM 0<br />
DP.A.T Dis.Press.Circ.A Trim -50 - 50 PSIG DPA_TRIM 0<br />
DP.B.T Dis.Press.Circ.B Trim -50 - 50 PSIG DPB_TRIM 0