Sensor Trim Configuration — The TRIM submenu<br />

is used to calibrate the sensor trim settings. The trim settings<br />

are used when the actual measured reading does not match the<br />

sensor output. The sensor can be adjusted to match the actual<br />

measured reading with the trim function. A list is shown in<br />

Table 63.<br />

IMPORTANT: Sensor trim must not be used to extend<br />

unit operation past the allowable operating range.<br />

Doing so may impair or negatively affect the Carrier<br />

product warranty.<br />

Air Temperature Leaving Supply Fan Sensor (SAT.T) — This<br />

variable is used to adjust the supply fan temperature sensor<br />

reading. The sensor reading can be adjusted ± 10° F to match<br />

the actual measured temperature.<br />

Return Air Temperature Sensor Trim (RAT.T) — This variable<br />

is used to adjust the return air temperature sensor reading.<br />

The sensor reading can be adjusted ± 10° F to match the actual<br />

measured temperature.<br />

Outdoor Air Temperature Sensor Trim (OAT.T) — This variable<br />

is used to adjust the outdoor air temperature sensor reading.<br />

The sensor reading can be adjusted ± 10° F to match the<br />

actual measured temperature.<br />

Space Temperature Sensor Trim (SPT.T) — This variable is<br />

used to adjust the space temperature sensor reading. The sensor<br />

reading can be adjusted ± 10° F to match the actual measured<br />

temperature.<br />

Limit Switch Trim (L.SW.T) — This variable is used to adjust<br />

the limit switch temperature sensor reading. The sensor<br />

reading can be adjusted ± 10° F to match the actual measured<br />

temperature.<br />

Table 62 — Alert Limit Configuration<br />

Table 63 — Sensor Trim Configuration<br />

85<br />

Air Temperature Leaving Evaporator Trim (CCT.T) — This<br />

variable is used to adjust the leaving evaporator temperature<br />

sensor reading. The sensor reading can be adjusted ± 10° F to<br />

match the actual measured temperature.<br />

A1 Discharge Temperature (DTA.1) — This variable is used<br />

to adjust the A1 compressor discharge temperature sensor reading.<br />

The sensor reading can be adjusted ± 10° F to match the<br />

actual measured temperature.<br />

Suction Pressure Circuit A Trim (SP.A.T) — This variable is<br />

used to adjust the suction pressure sensor reading for circuit A.<br />

The sensor reading can be adjusted ± 50 psig to match the actual<br />

measured pressure.<br />

Suction Pressure Circuit B Trim (SP.B.T) — This variable is<br />

used to adjust the suction pressure sensor reading for circuit B.<br />

The sensor reading can be adjusted ± 50 psig to match the actual<br />

measured pressure.<br />

Discharge Pressure Circuit A Trim (DP.A.T) — This variable<br />

is used to adjust the discharge pressure sensor reading for<br />

circuit A. The sensor reading can be adjusted ± 50 psig to<br />

match the actual measured pressure.<br />

Discharge Pressure Circuit B Trim (DP.B.T) — This variable<br />

is used to adjust the discharge pressure sensor reading for<br />

circuit B. The sensor reading can be adjusted ±50 psig to match<br />

the actual measured pressure.<br />

4 to 20 mA Inputs — There are a number of 4 to 20 mA inputs<br />

which may be calibrated. These inputs are located in<br />

Inputs4-20. They are:<br />

• SP.M.T — static pressure milliamp trim<br />

• BP.M.T — building pressure milliamp trim<br />

• OA.M.T — outside air cfm milliamp trim<br />

• RA.M.T — return air cfm milliamp trim<br />

• SA.M.T — supply air cfm milliamp trim<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

SP.L.O SPT lo alert limit/occ -10-245 dF SPLO 60<br />

SP.H.O SPT hi alert limit/occ -10-245 dF SPHO 85<br />

SP.L.U SPT lo alert limit/unocc -10-245 dF SPLU 45<br />

SP.H.U SPT hi alert limit/unocc -10-245 dF SPHU 100<br />

SA.L.O EDT lo alert limit/occ -40-245 dF SALO 40<br />

SA.H.O EDT hi alert limit/occ -40-245 dF SAHO 100<br />

SA.L.U EDT lo alert limit/unocc -40-245 dF SALU 40<br />

SA.H.U EDT hi alert limit/unocc -40-245 dF SAHU 100<br />

RA.L.O RAT lo alert limit/occ -40-245 dF RALO 60<br />

RA.H.O RAT hi alert limit/occ -40-245 dF RAHO 90<br />

RA.L.U RAT lo alert limit/unocc -40-245 dF RALU 40<br />

RA.H.U RAT hi alert limit/unocc -40-245 dF RAHU 100<br />

OAT.L OAT lo alert limit -40-245 dF OATL -40<br />

OAT.H OAT hi alert limit -40-245 dF OATH 150<br />

R.RH.L RARH low alert limit 0-100 % RRHL 0<br />

R.RH.H RARH high alert limit 0-100 % RRHH 100<br />

O.RH.L OARH low alert limit 0-100 % ORHL 0<br />

O.RH.H OARH high alert limit 0-100 % ORHH 100<br />

SP.L SP low alert limit 0-5 "H2O SPL 0<br />

SP.H SP high alert limit 0-5 "H2O SPH 2<br />

BP.L BP lo alert limit -0.25-0.25 "H2O BPL -0.25<br />

BP.H BP high alert limit -0.25-0.25 "H2O BPH 0.25<br />

IAQ.H IAQ high alert limit 0-5000 IAQH 1200<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

TRIM SENSOR TRIM CONFIG.<br />

SAT.T Air Temp Lvg SF Trim -10 - 10 ^F SAT_TRIM 0<br />

RAT.T RAT Trim -10 - 10 ^F RAT_TRIM 0<br />

OAT.T OAT Trim -10 - 10 ^F OAT_TRIM 0<br />

SPT.T SPT Trim -10 - 10 ^F SPT_TRIM 0<br />

L.SW.T Limit Switch Trim -10 - 10 ^F LSW_TRIM 0<br />

CCT.T Air Temp Lvg Evap Trim -10 - 10 ^F CCT_TRIM 0<br />

DTA.1 A1 Discharge Temp Trim -10 - 10 ^F DTA1TRIM 0<br />

SP.A.T Suct.Press.Circ.A Trim -50 - 50 PSIG SPA_TRIM 0<br />

SP.B.T Suct.Press.Circ.B Trim -50 - 50 PSIG SPB_TRIM 0<br />

DP.A.T Dis.Press.Circ.A Trim -50 - 50 PSIG DPA_TRIM 0<br />

DP.B.T Dis.Press.Circ.B Trim -50 - 50 PSIG DPB_TRIM 0