06.03.2013 Views

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

Controls, Start-Up, Operation, Service and ... - Climayoreo

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Whenever the outdoor ambient temperature (OAT), is<br />

above 70 F, the maximum stage will always be on when the<br />

compressors are on.<br />

On the initial start-up of a circuit, the condenser fans will<br />

start 5 seconds prior to the compressor starting in order to ensure<br />

proper head pressure of the compressor immediately at<br />

start-up. After the compressor starts, the normal head pressure<br />

routine is followed. What stage fans starts depends on the outdoor<br />

ambient temperature. The three situations are:<br />

OAT < 50 F<br />

50 F < OAT < 70 F<br />

OAT > 70 F<br />

See Fig. 7 for what stage of fans starts for each scenario.<br />

ECONOMIZER INTEGRATION WITH MECHANICAL<br />

COOLING — When the economizer is able to provide free<br />

cooling (Run StatusECONACTV = YES), mechanical<br />

cooling may be delayed or even held off indefinitely.<br />

NOTE: Once mechanical cooling has started, this delay logic<br />

is no longer relevant.<br />

Multi-Stage Cooling Economizer Mechanical Cooling<br />

Delay — This type of mechanical cooling delay is relevant to<br />

the following machine control types:<br />

C.TYP = 1 VAV-RAT<br />

C.TYP = 2 VAV-SPT<br />

C.TYP = 3 TSTAT-MULTI<br />

C.TYP = 4 SPT-MULTI<br />

If the economizer is able to provide free cooling at the start<br />

of a cooling session, the mechanical cooling algorithm<br />

(SumZ), checks the economizer’s current position (Run Status<br />

ECONECN.P) <strong>and</strong> compares it to the economizer’s<br />

maximum position (ConfigurationECONEC.MX) – 5%.<br />

Once the economizer has opened beyond this point a 150 second<br />

timer starts. If the economizer stays beyond this point for<br />

2.5 minutes continuously, the mechanical cooling algorithm is<br />

allowed to start computing dem<strong>and</strong> <strong>and</strong> stage compressors <strong>and</strong><br />

unloaders.<br />

Heating Control — The P Series ComfortLink controls<br />

offers control for four different types of heating systems to<br />

satisfy general space heating requirements: 2-stage gas heat,<br />

2-stage electric heat, multiple-stage gas heat <strong>and</strong> hydronic heat.<br />

Heating control also provides tempering <strong>and</strong> reheat functions.<br />

These functions are discussed in separate sections. Reheat is discussed<br />

under Dehumidification function on page 79.<br />

Variable air volume (VAV) type applications (C.TYP = 1 or<br />

2) require that the space terminal positions be comm<strong>and</strong>ed to<br />

open to minimum heating positions when gas or electric heat<br />

systems are active, to provide for the unit heating system’s<br />

Minimum Heating Airflow rate.<br />

Also, for VAV applications, the heat interlock relay (HIR)<br />

function provides the switching of a control signal intended for<br />

use by the VAV terminals. This signal must be used to comm<strong>and</strong><br />

the terminals to open to their Heating Open positions.<br />

The HIR is energized whenever the Heating mode is active, an<br />

IAQ pre-occupied force is active, or if fire smoke modes, pressurization,<br />

or smoke purge modes are active.<br />

Table 39 — Dem<strong>and</strong> Limit Configuration<br />

ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT<br />

DMD.L DEMAND LIMIT CONFIG.<br />

DM.L.S Dem<strong>and</strong> Limit Select 0 - 3 DMD_CTRL 0<br />

D.L.20 Dem<strong>and</strong> Limit at 20 ma 0 - 100 % DMT20MA 100<br />

SH.NM Loadshed Group Number 0 - 99 SHED_NUM 0<br />

SH.DL Loadshed Dem<strong>and</strong> Delta 0 - 60 % SHED_DEL 0<br />

SH.TM Maximum Loadshed Time 0 - 120 min SHED_TIM 60<br />

D.L.S1 Dem<strong>and</strong> Limit Sw.1 Setpt. 0 - 100 % DLSWSP1 80<br />

D.L.S2 Dem<strong>and</strong> Limit Sw.2 Setpt. 0 - 100 % DLSWSP2 50<br />

57<br />

Hydronic heating applications that use the unit’s control<br />

require the installation of a communicating actuator on the hydronic<br />

heating coil’s control valve. This actuator (with or without<br />

matching control valve) may be separately shipped for field<br />

installation.<br />

All heating systems are available as factory-installed<br />

options. The hydronic heating coil may also be field-supplied<br />

<strong>and</strong> field-installed; the actuator is still required if unit control<br />

will be used to manage this heating sequence.<br />

SETTING UP THE SYSTEM — The essential heating configurations<br />

located at the local display under Configuration<br />

HEAT. See Table 40.<br />

Heating Control Type (HT.CF) — The heating control types<br />

available are selected/configured with this variable.<br />

0 = No Heat<br />

1 = Electric Heat<br />

2 = 2 Stage Gas Heat<br />

3 = Staged Gas Heat<br />

4 = Hydronic Heat<br />

Heating Supply Air Set Point (HT.SP) — In a low heat mode<br />

for either staged gas or hydronic heat, this is the supply air set<br />

point for heating.<br />

Occupied Heating Enable (OC.EN) — This configuration<br />

only applies when the unit’s control type (Configuration<br />

UNITC.TYP) is configured for 1 (VAV-RAT) or 2 (VAV-<br />

SPT). If the user wants to have the capability of performing<br />

heating throughout the entire occupied period, then this<br />

configuration needs to be set to “YES”. Most installations do<br />

not require this capability, <strong>and</strong> if heating is installed, it is used<br />

to heat the building up in the morning. In this case set OC.EN<br />

to “NO”.<br />

NOTE: This unit des not support simultaneous heating <strong>and</strong><br />

cooling. If significant simultaneous heating <strong>and</strong> cooling<br />

dem<strong>and</strong> is expected, it may be necessary to provide additional<br />

heating or cooling equipment <strong>and</strong> a control system to provide<br />

occupants with proper comfort.<br />

MBB Sensor Heat Relocate (LAT.M) — This option allows<br />

the user additional performance benefit when under CCN<br />

Linkage for the 2-stage electric <strong>and</strong> gas heating types. As twostage<br />

heating types do not “modulate” to a supply air set point,<br />

no leaving air thermistor is required <strong>and</strong> none is provided. The<br />

evaporator discharge thermistor, which is initially installed upstream<br />

of the heater, can be repositioned downstream <strong>and</strong> the<br />

control can expect to sense this heat. While the control does not<br />

need this to energize stages of heat, the control can wait for a<br />

sufficient temperature rise before announcing a heating mode<br />

to a CCN Linkage system (ComfortID).<br />

If the sensor is relocated, the user will now have the<br />

capability to view the leaving-air temperature at all times at<br />

TemperaturesAIR.TCTRLLAT.<br />

NOTE: If the user does not relocate this sensor for the 2-stage<br />

electric or gas heating types <strong>and</strong> is under CCN Linkage, then<br />

the control will send a heating mode (if present)<br />

unconditionally to the linkage coordinator in the CCN zoning<br />

system regardless of the leaving-air temperature.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!