Table 87 — CCN/Linkage Display Table<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

LINK CCN - LINKAGE<br />

MODE Linkage Active - CCN ON/OFF MODELINK<br />

L.Z.T Linkage Zone Control Tmp dF LZT<br />

L.C.SP Linkage Curr. Cool Setpt dF LCSP<br />

L.H.SP Linkage Curr. Heat Setpt dF LHSP<br />

Table 88 — Compressor Run Hours Display Table<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

HRS COMPRESSOR RUN HOURS<br />

HR.A1 Compressor A1 Run Hours 0-999999 HRS HOURS_A1 config<br />

HR.A2 Compressor A2 Run Hours 0-999999 HRS HOURS_A2 config<br />

HR.A3 Compressor A3 Run Hours 0-999999 HRS HOURS_A3 config<br />

HR.B1 Compressor B1 Run Hours 0-999999 HRS HOURS_B1 config<br />

HR.B2 Compressor B2 Run Hours 0-999999 HRS HOURS_B2 config<br />

HR.B3 Compressor B3 Run Hours 0-999999 HRS HOURS_B3 config<br />

Alarms <strong>and</strong> Alerts — There are a variety of different<br />

alerts <strong>and</strong> alarms in the system.<br />

P — Pre-Alert: Part of the unit is temporarily down. The<br />

alarm is not broadcast on the CCN network. The alarm relay is<br />

not energized. After an allowable number of retries, if the<br />

function does not recover, the pre-alert will be upgraded to an<br />

alert or an alarm.<br />

T — Alert: Part of the unit is down, but the unit is still partially<br />

able to provide cooling or heating.<br />

A — Alarm: The unit is down <strong>and</strong> is unable to provide cooling<br />

or heating.<br />

All alarms are displayed with a code of AXXX where the A<br />

is the category of alarm (Pre-Alert, Alert, or Alarm) <strong>and</strong> XXX<br />

is the number.<br />

The response of the control system to various alerts <strong>and</strong><br />

alarms depends on the seriousness of the particular alert or<br />

alarm. In the mildest case, an alert does not affect the operation<br />

of the unit in any manner. An alert can also cause a “strike.” A<br />

“striking” alert will cause the circuit to shut down for 15 minutes.<br />

This feature reduces the likelihood of false alarms causing<br />

a properly working system to be shut down incorrectly. If three<br />

strikes occur before the circuit has an opportunity to show that<br />

it can function properly, the circuit will strike out, causing the<br />

shutdown alarm for that particular circuit. Once activated, the<br />

shutdown alarm can only be cleared via an alarm reset.<br />

Circuits with strikes are given an opportunity to reset their<br />

strike counter to zero. As discussed above, a strike typically<br />

causes the circuit to shut down. Fifteen minutes later, that<br />

Table 89 — Compressor <strong>Start</strong>s Display Table<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

STRT COMPRESSOR STARTS<br />

ST.A1 Compressor A1 <strong>Start</strong>s 0-999999 CY_A1 config<br />

ST.A2 Compressor A2 <strong>Start</strong>s 0-999999 CY_A2 config<br />

ST.A3 Compressor A3 <strong>Start</strong>s 0-999999 CY_A3 config<br />

ST.B1 Compressor B1 <strong>Start</strong>s 0-999999 CY_B1 config<br />

ST.B2 Compressor B2 <strong>Start</strong>s 0-999999 CY_B2 config<br />

ST.B3 Compressor B3 <strong>Start</strong>s 0-999999 CY_B3 config<br />

Table 90 — Software Version Numbers Display Table<br />

ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS<br />

VERS SOFTWARE VERSION NUMBERS<br />

MBB CESR131461-xx-xx string<br />

RXB CESR131465-xx-xx string<br />

EXB CESR131465-xx-xx string<br />

CEM CESR131174-xx-xx string<br />

CXB CESR131173-xx-xx string<br />

SCB CESR131226-xx-xx string<br />

VFD1 VERSION-313D string<br />

VFD2 VERSION-313D string<br />

MARQ CESR131171-xx-xx string<br />

NAVI CESR130227-xx-xx string<br />

106<br />

circuit will once again be allowed to run. If the circuit is able to<br />

run for 1 minute, its replacement circuit will be allowed to shut<br />

down (if not required to run to satisfy requested stages). However,<br />

the “troubled” circuit must run continuously for 5 minutes<br />

with no detectable problems before the strike counter is reset to<br />

zero.<br />

In addition, the compressors have several diagnostics<br />

monitoring the safety of the system which may cause a<br />

number of attempts to be re-tried before locking out the system<br />

from operation. This feature reduces the likelihood of false<br />

alarms causing a properly working system to be shutdown incorrectly.<br />

For the compressor <strong>and</strong> circuit diagnostics, some of these<br />

alerts/alarms will not broadcast an initial failure to the CCN<br />

network until all attempts to recover have occurred <strong>and</strong> failed.<br />

These alerts will be accessible in the alarm history of the<br />

control (AlarmsHIST).<br />

All the alarms <strong>and</strong> alerts are summarized in Table 91.<br />

DIAGNOSTIC ALARM CODES AND POSSIBLE<br />

CAUSES<br />

T048 (Ckt A, Oil Return Not Reliable with Only One Comp<br />

Available)<br />

T049 (Ckt B, Oil Return Not Reliable with Only One Comp<br />

Available) — Alert codes T048 <strong>and</strong> T049 are for circuits A<br />

<strong>and</strong> B respectively <strong>and</strong> are active for size 090 <strong>and</strong> 100 units only.<br />

Size 090 <strong>and</strong> 100 units have 3 compressors per circuit. If<br />

load conditions are such that only one compressor is running<br />

on a circuit, a second compressor is periodically turned on to