All P Series units with ComtfortLink controls have a port<br />
for interface with the Carrier Comfort Network ® (CCN) system.<br />
On TB3 there is a J11 jack which can be used for temporary<br />
connection to the CCN network or to computers equipped<br />
with CCN software like the <strong>Service</strong> Tool. Also on TB3 there<br />
are screw connections that can be used for more permanent<br />
CCN connections.<br />
APPENDIX B — CCN TABLES<br />
STATUS DISPLAY TABLES<br />
176<br />
In the following tables the structure of the tables which are<br />
used with the <strong>Service</strong> Tool as well as the names <strong>and</strong> data that are<br />
included in each table are shown. There are several CCN variables<br />
that are not displayed through the scrolling marquee <strong>and</strong><br />
are used for more extensive diagnostics <strong>and</strong> system evaluations.<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />
COOLING<br />
HVAC Mode…………..: ascii text strings<br />
Control Mode………..: ascii text strings<br />
COOL_A<br />
COOL_B<br />
ECONDIAG<br />
Current Running Capacity % CAPTOTAL<br />
Total Capacity Needed % COOLCALC<br />
Current Cool Stage COOL_STG<br />
Requested Cool Stage CL_STAGE<br />
Maximum Cool Stage CLMAXSTG<br />
Cooling Control Point dF COOLCPNT<br />
Evaporator Discharge Tmp dF EDT<br />
Mixed Air Temperature dF MAT<br />
Next capacity step down % CAPNXTDN<br />
Next capacity step up % CAPNXTUP<br />
Current Cool Stage COOL_STG<br />
Cir A Discharge Pressure PSIG DP_A<br />
Cir A Suction Pressure PSIG SP_A<br />
Cir A Sat.Condensing Tmp dF SCTA<br />
Cir A Sat.Suction Temp. dF SSTA<br />
A1 Discharge Temperature dF DTA1<br />
Suction Gas Temp Circ A dF RGTA<br />
Compressor A1 Relay CMPA1<br />
Compressor A2 Relay CMPA2<br />
Compressor A3 Relay CMPA3<br />
Compressor A1 Feedback CSB_A1<br />
Compressor A2 Feedback CSB_A2<br />
Compressor A3 Feedback CSB_A3<br />
Circ A High Press.Switch CIRCAHPS<br />
Current Cool Stage COOL_STG<br />
Cir B Discharge Pressure DP_B<br />
Cir B Suction Pressure PSIG SP_B<br />
Cir B Sat.Condensing Tmp PSIG SCTB<br />
Cir B Sat.Suction Temp. dF SSTB<br />
Compressor B1 Relay CMPB1<br />
Compressor B2 Relay CMPB2<br />
Compressor B3 Relay CMPB3<br />
Compressor B1 Feedback CSB_B1<br />
Compressor B2 Feedback CSB_B2<br />
Compressor B3 Feedback CSB_B3<br />
Circ B High Press.Switch CIRCBHPS<br />
Economizer Active ? Yes/No ECACTIVE<br />
Conditions which prevent<br />
economizer being active:<br />
Econ Act. Unavailable? Yes/No ECONUNAV<br />
Econ2 Act. Unavailable Yes/No ECN2UNAV<br />
Enth.Switch Read High ? Yes/No ENTH<br />
DBC - OAT lockout? Yes/No DBC_STAT<br />
DEW - OA Dewpt. lockout? Yes/No DEW_STAT<br />
DDBC- OAT > RAT lockout? Yes/No DDBCSTAT<br />
OAEC- OA Enth Lockout? Yes/No OAECSTAT<br />
DEC - Diff.Enth.Lockout? Yes/No DEC_STAT<br />
EDT Sensor Bad ? Yes/No EDT_STAT<br />
OAT Sensor Bad ? Yes/No OAT_STAT<br />
Economizer forced ? Yes/No ECONFORC<br />
Supply Fan not on 30s ? Yes/No SFONSTAT<br />
Cool Mode not in effect? Yes/No COOL_OFF<br />
OAQ lockout in effect ? Yes/No OAQLOCKD<br />
Econ recovery hold off? Yes/No ECONHELD<br />
Dehumid. Disabled Econ.? Yes/No DHDISABL