Table 91 — Alert <strong>and</strong> Alarm Codes (cont)<br />

ALARM OR<br />

DESCRIPTION ACTION TAKEN BY CONTROL RESET METHOD<br />

ALERT NUMBER<br />

A171 Staged Gas Control Board Comm Failure Staged gas control disabled Automatic<br />

T172 Control Expansion Module Comm Failure All CEM board functions disabled Automatic<br />

A173 RXB board Communication Failure Unit shut down Automatic<br />

A174 EXB board Communication Failure All EXB board functions disabled Automatic<br />

A175 Supply Fan VFD Communication Failure Unit shut down Automatic<br />

T176 Exhaust Fan VFD Communication Failure No building pressure control Automatic<br />

T177 4-20 mA Dem<strong>and</strong> Limit Failure No dem<strong>and</strong> limiting Automatic<br />

T178 4-20 mA Static Pressure Reset Fail No static pressure reset Automatic<br />

A200 Linkage Timeout Error - Comm Failure Resorts to local unit setpoints Automatic<br />

T210 Building Pressure Transducer Failure No building pressure control function Automatic<br />

T211 Static Pressure Transducer Failure No static pressure control Automatic<br />

T220 Indoor Air Quality Sensor Failure No IAQ control Automatic<br />

T221 Outdoor Air Quality Sensor Failure OAQ defaults to 400 ppm Automatic<br />

T229 Economizer Min Pos Override Input Failure Operate without override Automatic<br />

T245 Outside Air Cfm Sensor Failure No OA CFM control Automatic<br />

T246 Supply Air Cfm Sensor Failure Unit shut down Automatic<br />

T247 Return Air Cfm Sensor Failure Unit shut down Automatic<br />

T300 Space Temperature Below Limit Alert only Automatic<br />

T301 Space Temperature Above Limit Alert only Automatic<br />

T302 Supply Temperature Below Limit Alert only Automatic<br />

T303 Supply Temperature Above Limit Alert only Automatic<br />

T304 Return Temperature Below Limit Alert only Automatic<br />

T305 Return Temperature Above Limit Alert only Automatic<br />

T308 Return Air Relative Humidity Below Limit Alert only Automatic<br />

T309 Return Air Relative Humidity Above Limit Alert only Automatic<br />

T310 Supply Duct Static Pressure Below Limit Alert only Automatic<br />

T311 Supply Duct Static Pressure Above Limit Alert only Automatic<br />

T312 Building Static Pressure Below Limit Alert only Automatic<br />

T313 Building Static Pressure Above Limit Alert only Automatic<br />

T314 IAQ Above Limit Alert only Automatic<br />

T316 OAT Below Limit Alert only Automatic<br />

T317 OAT Above Limit Alert only Automatic<br />

A400 Hydronic Freeze Stat Trip Unit in emergency mode Automatic<br />

A404 Fire Shut Down Emergency Mode (fire-smoke) Unit shut down Automatic<br />

A405 Evacuation Emergency Mode Run evacuation mode Automatic<br />

A406 Pressurization Emergency Mode Run pressurization mode Automatic<br />

A407 Smoke Purge Emergency Mode Run smoke purge mode Automatic<br />

T408 Dirty Air Filter Alert only Automatic<br />

T409 Supply Fan Status Failure Alert only Manual<br />

A409 Supply Fan Status Failure Unit shut down Manual<br />

A410 Supply Fan VFD Fault Unit shut down Manual<br />

A411 Exhuast Fan VFD Fault Unit shut down Manual<br />

T421 Thermostat Y2 Input On without Y1 On Run on Y2 Automatic<br />

T422 Thermostat W2 Input On without W1 On Run on W2 Automatic<br />

T423 Thermostat Y <strong>and</strong> W Inputs On No cooling or heating Automatic<br />

T424 Thermostat G Input Off On a Cooling Call Turn fan on <strong>and</strong> cool Automatic<br />

T430 Plenum Pressure Safety Switch Trip Alert only Automatic<br />

A430 Plenum Pressure Safety Switch Trip Unit shut down Manual<br />

T500 Current Sensor Board Failure - A1 Alert only Automatic<br />

T501 Current Sensor Board Failure - A2 Alert only Automatic<br />

T502 Current Sensor Board Failure - B1 Alert only Automatic<br />

T503 Current Sensor Board Failure - B2 Alert only Automatic<br />

T504 Current Sensor Board Failure - A3 Alert only Automatic<br />

T505 Current Sensor Board Failure - B3 Alert only Automatic<br />

109