APPENDIX B — CCN TABLES (cont)<br />

STATUS DISPLAY TABLES (cont)<br />

TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />

ECONOMZR<br />

Economizer Act.Curr.Pos. % ECONOPOS<br />

Economizer 2 Act.Curr.Pos. % ECON2POS<br />

Economizer Act.Cmd.Pos. % ECONOCMD forcible<br />

Economizer Active ? ECACTIVE<br />

Economizer Control Point dF ECONCPNT<br />

Outside Air Temperature dF OAT forcible<br />

Evaporator Discharge Tmp dF EDT<br />

Controlling Return Temp dF RETURN_T forcible<br />

Econo Current Min. Pos. % ECMINPOS<br />

Econo Current Min. CFM CFM ECMINCFM<br />

Outside Air CFM CFM OACFM<br />

GENERAL<br />

Occupied ? YES/NO OCCUPIED forcible<br />

Static Pressure "H2O SP<br />

Building Pressure "H2O BP<br />

Outside Air CFM CFM OACFM<br />

Return Air CFM CFM RACFM<br />

Supply Air CFM CFM SACFM<br />

Outside Air Rel.Humidity % OARH forcible<br />

Return Air Rel.Humidity % RARH forcible<br />

Space Relative Humidity % SPRH forcible<br />

Space Temperature Offset ^F SPTO forcible<br />

Supply Air Setpnt. Reset ^F SASPRSET forcible<br />

Static Pressure Reset SPRESET forcible<br />

IAQ - PPM Return CO2 IAQ forcible<br />

OAQ - PPM Return CO2 OAQ forcible<br />

IAQ Min.Pos.Override % IAQMINOV forcible<br />

GENERIC<br />

20 points dependent upon<br />

the configuration of the<br />

"generics" table in the<br />

<strong>Service</strong>-Config section on page 178<br />

HEATING<br />

HVAC Mode…………..: ascii text strings<br />

Control Mode………..: ascii text strings<br />

Heat Control Type……: ascii text strings<br />

Re-Heat Control Type...: ascii text strings<br />

Heating Mode………..: ascii text strings<br />

Requested Heat Stage HT_STAGE<br />

Ht.Coil Act.Current Pos. % HTCLRPOS<br />

Heating Control Point dF HEATCPNT<br />

Heat Relay 1 HS1<br />

Heat Relay 2 HS2<br />

Relay 3 W1 Gas Valve 2 HS3<br />

Relay 4 W2 Gas Valve 2 HS4<br />

Relay 5 W1 Gas Valve 3 HS5<br />

Relay 6 W2 Gas Valve 3 HS6<br />

Heat Interlock Relay HIR forcible<br />

HMZR<br />

HVAC Mode…………..: ascii text strings<br />

Humidimizer Capacity % HMZRCAPC<br />

Condenser EXV Position % COND_EXV<br />

Bypass EXV Position % BYP_EXV<br />

Humidimzer 3-Way Valve On/Off HUM3WVAL<br />

Cooling Control Point dF COOLCPNT<br />

Evaporator Discharge Tmp dF EDT<br />

Heating Control Point dF HEATCPNT<br />

Leaving Air Temperature dF LAT<br />

MODEDISP<br />

System Mode…………: ascii text strings<br />

HVAC Mode…………..: ascii text strings<br />

Control Mode………..: ascii text strings<br />

Currently Occupied On/Off MODEOCCP<br />

Timed Override in effect On/Off MODETOVR<br />

DCV resetting min pos On/Off MODEADCV<br />

Supply Air Reset On/Off MODESARS<br />

Dem<strong>and</strong> Limit in Effect On/Off MODEDMLT<br />

Temp.Compensated <strong>Start</strong> On/Off MODETCST<br />

IAQ pre-occ purge active On/Off MODEIQPG<br />

Linkage Active - DAV On/Off MODELINK<br />

Mech.Cooling Locked Out On/Off MODELOCK<br />

HVAC Mode Numerical Form number MODEHVAC<br />

177