APPENDIX B — CCN TABLES (cont)<br />
STATUS DISPLAY TABLES (cont)<br />
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS<br />
ECONOMZR<br />
Economizer Act.Curr.Pos. % ECONOPOS<br />
Economizer 2 Act.Curr.Pos. % ECON2POS<br />
Economizer Act.Cmd.Pos. % ECONOCMD forcible<br />
Economizer Active ? ECACTIVE<br />
Economizer Control Point dF ECONCPNT<br />
Outside Air Temperature dF OAT forcible<br />
Evaporator Discharge Tmp dF EDT<br />
Controlling Return Temp dF RETURN_T forcible<br />
Econo Current Min. Pos. % ECMINPOS<br />
Econo Current Min. CFM CFM ECMINCFM<br />
Outside Air CFM CFM OACFM<br />
GENERAL<br />
Occupied ? YES/NO OCCUPIED forcible<br />
Static Pressure "H2O SP<br />
Building Pressure "H2O BP<br />
Outside Air CFM CFM OACFM<br />
Return Air CFM CFM RACFM<br />
Supply Air CFM CFM SACFM<br />
Outside Air Rel.Humidity % OARH forcible<br />
Return Air Rel.Humidity % RARH forcible<br />
Space Relative Humidity % SPRH forcible<br />
Space Temperature Offset ^F SPTO forcible<br />
Supply Air Setpnt. Reset ^F SASPRSET forcible<br />
Static Pressure Reset SPRESET forcible<br />
IAQ - PPM Return CO2 IAQ forcible<br />
OAQ - PPM Return CO2 OAQ forcible<br />
IAQ Min.Pos.Override % IAQMINOV forcible<br />
GENERIC<br />
20 points dependent upon<br />
the configuration of the<br />
"generics" table in the<br />
<strong>Service</strong>-Config section on page 178<br />
HEATING<br />
HVAC Mode…………..: ascii text strings<br />
Control Mode………..: ascii text strings<br />
Heat Control Type……: ascii text strings<br />
Re-Heat Control Type...: ascii text strings<br />
Heating Mode………..: ascii text strings<br />
Requested Heat Stage HT_STAGE<br />
Ht.Coil Act.Current Pos. % HTCLRPOS<br />
Heating Control Point dF HEATCPNT<br />
Heat Relay 1 HS1<br />
Heat Relay 2 HS2<br />
Relay 3 W1 Gas Valve 2 HS3<br />
Relay 4 W2 Gas Valve 2 HS4<br />
Relay 5 W1 Gas Valve 3 HS5<br />
Relay 6 W2 Gas Valve 3 HS6<br />
Heat Interlock Relay HIR forcible<br />
HMZR<br />
HVAC Mode…………..: ascii text strings<br />
Humidimizer Capacity % HMZRCAPC<br />
Condenser EXV Position % COND_EXV<br />
Bypass EXV Position % BYP_EXV<br />
Humidimzer 3-Way Valve On/Off HUM3WVAL<br />
Cooling Control Point dF COOLCPNT<br />
Evaporator Discharge Tmp dF EDT<br />
Heating Control Point dF HEATCPNT<br />
Leaving Air Temperature dF LAT<br />
MODEDISP<br />
System Mode…………: ascii text strings<br />
HVAC Mode…………..: ascii text strings<br />
Control Mode………..: ascii text strings<br />
Currently Occupied On/Off MODEOCCP<br />
Timed Override in effect On/Off MODETOVR<br />
DCV resetting min pos On/Off MODEADCV<br />
Supply Air Reset On/Off MODESARS<br />
Dem<strong>and</strong> Limit in Effect On/Off MODEDMLT<br />
Temp.Compensated <strong>Start</strong> On/Off MODETCST<br />
IAQ pre-occ purge active On/Off MODEIQPG<br />
Linkage Active - DAV On/Off MODELINK<br />
Mech.Cooling Locked Out On/Off MODELOCK<br />
HVAC Mode Numerical Form number MODEHVAC<br />
177